第一篇:电业安全工作规程(发电厂和变电所电气部分)目录
电业安全工作规程
(发电厂和变电所电气部分)
目录
1总则 ······························································································································ 186 2高压设备工作的基本要求 ·························································································· 186 3保证安全的组织措施 ·································································································· 189 4保证安全的技术措施 ·································································································· 193 5线路作业时发电厂和变电所的安全措施 ·································································· 195 6带电作业 ······················································································································ 196 7发电机、同期调相机和高压电动机的维护工作 ······················································ 206 8在六氟化硫电气设备上的工作 ·················································································· 207 9在停电的低压配电装置和低压导线上的工作 ·························································· 208 10在继电保护、仪表第二次回路上的工作 ································································ 208 11电气试验 ···················································································································· 209 12电力电缆工作 ············································································································ 211 13其他安全措施 ············································································································ 212 附录A倒闸操作票格式 ································································································· 213 附录B第一种工作票格式 ····························································································· 214
第二篇:电业安全工作规程发电厂和变电所电气部分
电业安全工作规程发电厂和变电所电气部分 DL408-1991 第一章 总则
第二章 高压设备工作的基本要求 第一节 发电厂和变电所的值班工作 第二节 高压设备的巡视 第三节 倒闸操作
第四节 高压设备上工作的安全措施分类 第三章 保证安全的组织措施 第一节 工作票制度 第二节 工作许可制度 第三节 工作监护制度
第四节 工作间断、转移和终结制度 第四章 保证安全的技术措施 第一节 停电 第二节 验电
第三节 装设接地线
第四节 悬挂标示牌和装设遮拦
第五章 线路作业时发电厂和变电所的安全措施 第六章 带电作业 第一节 一般规定 第二节 一般技术措施 第三节 等电位作业 第四节 带电断、接引线 第五节 带电短路设备 第六节 带电水冲洗 第七节 带电爆炸压接 第八节 感应电压防护 第九节 高架绝缘斗臂车 第十节 带电气吹清扫 第十一节 保护间隙
第十二节 带电检测绝缘子 第十三节 低压带电作业
第十四节 带电作业工具的保管与试验
第七章 发电机、同期调相机和高压电动机的维护工作 第八章 在六氟化硫电气设备上的工作
第九章 在停电的低压配电装置和低压导线上的工作 第十章 在继电保护、仪表等二次回路上的工作 第十一章 电气试验 第一节 高压试验
第二节 使用携带型仪器的测量工作 第三节 使用钳形电流表的测量工作 第四节 使用摇表测量绝缘的工作 第十二章 电力电缆工作 第十三章 其他安全措施 附录一 倒闸操作票格式 附录二 第一种工作票格式 附录三 第二种工作票格式 附录四 标示牌式样
附录五 常用电气绝缘工具试验一览表 附录六 登高安全工具试验标准表 附录七 紧急救护法 1 通则 2 触电急救 3 创伤急救
附录八 SF6新气质量暂行标准 第一章 总 则
第 1 条 为了切实保证职工在生产中的安全和健康以及电力系统、发供配电设备的安全 运行,结合电力生产多年来的实践经验,制定本规程。各单位的领导干部和电气工作人员,必须严格执行本规程。
第 2 条 安全生产,人人有责。各级领导必须以身作则,要充分发动群众,依靠群众; 要发挥安全监察机构和群众性的安全组织的作用,严格监督本规程的贯彻执行。
第 3 条 本规程适用于运用中的发、变、送、配、农电和用户电气设备上工作的一切人 员(包括基建安装人员)。
各单位可根据现场情况制定补充条文,经厂(局)主管生产的领导(总工程师)批准后 执行。
所谓运用中的电气设备,系指全部带有电压或一部分带有电压及一经操作即带有电压的 电气设备。
第 4 条 电气设备分为高压和低压两种: 高压:设备对地电压在 250V 以上者: 低压:设备对地电压在 250V 及以下者。第 5 条 电气工作人员必须具备下列条件:
一、经医师鉴定,无妨碍工作的病症(体格检查约两年一次)。
二、具备必要的电气知识,且按其职务和工作性质,熟悉《电业安全工作规程》(发电 厂和变电所电气部分、电力线路部分、热力和机械部分)的有关部分,并经考试合格。
三、学会紧急救护法(附录七),特别要学会触电急救。
第 6 条 电气工作人员对本规程应每年考试一次。因故间断电气工作连续三个月以上者,必须重新温习本规程,并经考试合格后,方能恢复工作。
参加带电作业人员,应经专门培训,并经考试合格、领导批准后,方能参加工作。新参加电气工作的人员、实习人员和临时参加劳动的人员(干部、临时工等),必须经 过安全知识教育后,方可下现场随同参加指定的工作,但不得单独工作。
对外单位派来支援的电气工作人员,工作前应介绍现场电气设备接线情况和有关安全措 施。
第 7 条 任何工作人员发现有违反本规程,并足以危及人身和设备安全者,应立即制止。第 8 条 对认真遵守本规程者,应给予表扬和奖励。对违反本规程者,应认真分析,加 强教育,分别情况,严肃处理。对造成严重事故者,应按情节轻重,予以行政或刑事处分。第 9 条 本规程所指的安全用具必须符合附录
五、附录六的要求。第二章 高压设备工作的基本要求 第一节 发电厂和变电所的值班工作
第 10 条 值班人员必须熟悉电气设备。单独值班人员或值班负责人还应有实际工作经 验。
第 11 条 高压设备符合下列条件者,可由单人值班:
一、室内高压设备的隔离室设有遮栏,遮栏的高度在 1.7m 以上,安装牢固并加锁者;
二、室内高压开关的操作机构用墙或金属板与该开关隔离,或装有远方操作机构者。单人值班不得单独从事修理工作。
第 12 条 不论高压设备带电与否,值班人员不得单独移开或越过遮栏进行工作;若有必 要移开遮栏时,必须有监护人在场,并符合表 1 的安全距离。表 1 设备不停电时的安全距离 第二节 高压设备的巡视
第 13 条 经企业领导批准允许单独巡视高压设备的值班员和非值班员,巡视高压设备 时,不得进行其他工作,不得移开或越过遮栏。
第 14 条 雷雨天气,需要巡视室外高压设备时,应穿绝缘靴,并不得靠近避雷器和避雷 针。
第 15 条 高压设备发生接地时,室内不得接近故障点 4m 以内,室外不得接近故障点 8m 以内。进入上述范围人员必须穿绝缘靴,接触设备的外壳和架构时,应戴绝缘手套。第 16 条 巡视配电装置,进出高压室,必须随手将门锁好。
第 17 条 高压室的钥匙至少应有三把,由配电值班人员负责保管,按值移交。一把专供 紧急时使用,一把专供值班员使用,其他可以借给许可单独巡视高压设备的人员和工作负责 人使用,但必须登记签名,当日交回。第三节 倒闸操作
第 18 条 倒闸操作必须根据值班调度员或值班负责人命令,受令人复诵无误后执行。发 布命令应准确、清晰、使用正规操作术语和设备双重名称,即设备名称和编号。发令人使用 电话发布命令前,应先和受令人互报姓名。值班调度员发布命令的全过程(包括对方复诵命 令)和听取命令的报告时,都要录音并作好记录。倒闸操作由操作人填写操作票(见附录一)。单人值班,操作票由发令人用电话向值班员传达,值班员应根据传达,填写操作票,复诵无 误,并在“监护人”签名处填入发 令人的姓名。每张操作票只能填写一个操作任务。
第 19 条 停电拉闸操作必须按照断路器(开关)——负荷侧隔离开关(刀闸)——母线 侧隔离开关(刀闸)的顺序依次操作,送电合闸操作应按与上述相反的顺序进行。严防带负 荷拉合刀闸。
为防止误操作,高压电气设备都应加装防误操作的闭锁装置(少数特殊情况下经上级主 管部门批准,可加机械锁)。闭锁装置的解锁用具(包括钥匙)应妥善保管,按规定使用,不许乱用。机械锁要一把钥匙开一把锁,钥匙要编号并妥善保管,方便使用。所有投运的闭 锁装置(包括机械锁)不经值班调度员或值长同意不得退出或解锁。第 20 条 下列项目应填入操作票内:
应拉合的断路器(开关)和隔离开关(刀闸),检查断路器(开关)和隔离开关(刀闸)的位置,检查接地线是否拆除,检查负荷分配,装拆接地线,安装或拆除控制回路或电压互 感器回路的熔断器(保险),切换保护回路和检验是否确无电压等。操作票应填写设备的双重名称,即设备名称和编号。
第 21 条 操作票应用钢笔或圆珠笔填写,票面应清楚整洁,不得任意涂改。操作人和监 护人应根据模拟图板或接线图核对所填写的操作项目,并分别签名,然后经值班负责人审核 签名。特别重要和复杂的操作还应由值长审核签名。第 22 条 开始操作前,应先在模拟图板上进行核对性模拟预演,无误后,再进行设备操 作。操作前应核对设备名称、编号和位置,操作中应认真执行监护复诵制。发布操作命令和 复诵操作命令都应严肃认真,声音宏亮清晰。必须按操作票填写的顺序逐项操作。每操作完 一项,应检查无误后做一个“√”记号,全部操作完毕后进行复查。
第 23 条 倒闸操作必须由两人执行,其中一人对设备较为熟悉者作监护。单人值班的变 电所倒闸操作可由一人执行。
特别重要和复杂的倒闸操作,由熟练的值班员操作,值班负责人或值长监护。
第 24 条 操作中发生疑问时,应立即停止操作并向值班调度员或值班负责人报告,弄清 问题后,再进行操作。不准擅自更改操作票,不准随意解除闭锁装置。
第 25 条 用绝缘棒拉合隔离开关(刀闸)或经传动机构拉合隔离开关(刀闸)和断路器(开关),均应戴绝缘手套。雨天操作室外高压设备时,绝缘棒应有防雨罩,还应穿绝缘靴。接地网电阻不符合要求的,晴天也应穿绝缘靴。雷电时,禁止进行倒闸操作。第 26 条 装卸高压熔断器(保险),应戴护目眼镜和绝缘手套,必要时使用绝缘夹钳,并站在绝缘垫或绝缘台上。
第 27 条 断路器(开关)遮断容量应满足电网要求。如遮断容量不够,必须将操作机构 用墙或金属板与该断路器(开关)隔开,并设远方控制,重合闸装置必须停用。
第 28 条 电气设备停电后,即使是事故停电,在未拉开有关隔离开关(刀闸)和做好安 全措施以前,不得触及设备或进入遮栏,以防突然来电。
第 29 条 在发生人身触电事故时,为了解救触电人,可以不经许可,即行断开有关设备 的电源,但事后必须立即报告上级。
第 30 条 下列各项工作可以不用操作票:
一、.事故处理;
二、拉合断路器(开关)的单一操作;
三、拉开接地刀闸或拆除全厂(所)仅有的一组接地线。上述操作应记入操作记录簿内。
第 31 条 操作票应先编号,按照编号顺序使用。作废的操作票,应注明“作废”字样,已操作的注明“已执行”的字样。上述操作票保存三个月。第四节 高压设备上工作的安全措施分类
第 32 条 在运用中的高压设备上工作,分为三类:
一、全部停电的工作,系指室内高压设备全部停电(包括架空线路与电缆引入线在内),通至邻接高压室的门全部闭锁,以及室外高压设备全部停电(包括架空线路与电缆引入线在 内)。
二、部分停电的工作,系指高压设备部分停电,或室内虽全部停电,而通至邻接高压室 的门并未全部闭锁。
三、不停电工作系指:
1.工作本身不需要停电和没有偶然触及导电部分的危险者; 2.许可在带电设备外壳上或导电部分上进行的工作。第 33 条 在高压设备上工作,必须遵守下列各项:
一、填用工作票或口头、电话命令;
二、至少应有两人在一起工作;
三、完成保证工作人员安全的组织措施和技术措施。第三章 保证安全的组织措施
第 34 条 在电气设备上工作,保证安全的组织措施为:
一、工作票制度;
二、工作许可制度;
三、工作监护制度;
四、工作间断、转移和终结制度。第一节 工作票制度
第 35 条 在电气设备上工作,应填用工作票或按命令执行,其方式有下列三种:
一、填用第一种工作票(见附录二);
二、填用第二种工作票(见附录三);
三、口头或电话命令。
第 36 条 填用第一种工作票的工作为:
一、高压设备上工作需要全部停电或部分停电者;
二、高压室内的二次接线和照明等回路上的工作,需要将高压设备停电或做安全措施者。第 37 条 填用第二种工作票的工作为:
一、带电作业和在带电设备外壳上的工作;
二、控制盘和低压配电盘、配电箱、电源干线上的工作; 三、二次接线回路上的工作,无需将高压设备停电者;
四、转动中的发电机、同期调相机的励磁回路或高压电动机转子电阻回路上的工作;
五、非当值值班人员用绝缘棒和电压互感器定相或用钳形电流表测量高压回路的电流。第 38 条 其他工作用口头或电话命令。
口头或电话命令,必须清楚正确,值班员应将发令人、负责人及工作任务详细记入操作 记录簿中,并向发令人复诵核对一遍。
第 39 条 工作票要用钢笔或圆珠笔填写一式两份,应正确清楚,不得任意涂改,如有个 别错、漏字需要修改时,应字迹清楚。
两份工作票中的一份必须经常保存在工作地点,由工作负责人收执,另一份由值班员收 执,按值移交。值班员应将工作票号码、工作任务、许可工作时间及完工时间记入操作记录 簿中。
在无人值班的设备上工作时,第二份工作票由工作许可人收执。
第 40 条 一个工作负责人只能发给一张工作票。工作票上所列的工作地点,以一个电气 连接部分为限。
如施工设备属于同一电压、位于同一楼层、同时停送电,且不会触及带电导体时,则允 许在几个电气连接部分共用一张工作票。开工前工作票内的全部安全措施应一次做完。
建筑工、油漆工等非电气人员进行工作时,工作票发给监护人。
第 41 条 在几个电气连接部分上依次进行不停电的同一类型的工作,可以发给一张第二 种工作票。
第 42 条 若一个电气连接部分或一个配电装置全部停电,则所有不同地点的工作,可以 发给一张工作票,但要详细填明主要工作内容。几个班同时进行工作时,工作票可发给一个 总的负责人,在工作班成员栏内只填明各班的负责人,不必填写全部工作人员名单。若至预定时间,一部分工作尚未完成,仍须继续工作而不妨碍送电者,在送电前,应按 照送电后现场设备带电情况,办理新的工作票,布置好安全措施后,方可继续工作。第 43 条 事故抢修工作可不用工作票,但应记入操作记录簿内,在开始工作前必须按本 规程第四章的规定做好安全措施,并应指定专人负责监护。
第 44 条 线路、用户检修班或基建施工单位在发电厂或变电所进行工作时,必须由所在 单位(发电厂、变电所或工区)签发工作票并履行工作许可手续。
第 45 条 第一种工作票应在工作前一日交给值班员。临时工作可在工作开始以前直接交 给值班员。
第二种工作票应在进行工作的当天预先交给值班员。
第 46 条 若变电所距离工区较远或因故更换新工作票不能在工作前一日将工作票送到,工作票签发人可根据自己填好的工作票用电话全文传达给变电所值班员,传达必须清楚,值 班员应根据传达做好记录,并复诵核对。若电话联系有困难,也可在进行工作的当天预先将 工作票交给值班员。
第 47 条 第一、二种工作票的有效时间,以批准的检修期为限。第一种工作票至预定时 间,工作尚未完成,应由工作负责人办理延期手续。延期手续应由工作负责人向值班负责人 申请办理,主要设备检修延期要通过值长办理。工作票有破损不能继续使用时,应补填新的 工作票。
第 48 条 需要变更工作班中的成员时,须经工作负责人同意。需要变更工作负责人时,应由工作票签发人将变动情况记录在工作票上。若扩大工作任务,必须由工作负责人通过工 作许可人,并在工作票上增填工作项目。若须变更或增设安全措施者,必须填用新的工作票,并重新履行工作许可手续。
第 49 条 工作票签发人不得兼任该项工作的工作负责人。工作负责人可以填写工作票。工作许可人不得签发工作票。
第 50 条 工作票签发人应由分场、工区(所)熟悉人员技术水平、熟悉设备情况、熟悉 本规程的生产领导人、技术人员或经厂、局主管生产领导批准的人员担任。工作票签发人员 名单应书面公布。
工作负责人和允许办理工作票的值班员(工作许可人)应由分场或工区主管生产的领导 书面批准。
第 51 条 工作票中所列人员的安全责任:
一、工作票签发人: 1.工作必要性; 2.工作是否安全;
3.工作票上所填安全措施是否正确完备;
4.所派工作负责人和工作班人员是否适当和足够,精神状态是否良好。
二、工作负责人(监护人): 1.正确安全地组织工作;
2.结合实际进行安全思想教育; 3.督促、监护工作人员遵守本规程;
4.负责检查工作票所载安全措施是否正确完备和值班员所做的安全措施是否符合现场 实际条件;
5.工作前对工作人员交待安全事项; 6.工作班人员变动是否合适。
三、工作许可人:
1.负责审查工作票所列安全措施是否正确完备,是否符合现场条件; 2.工作现场布置的安全措施是否完善; 3.负责检查停电设备有无突然来电的危险;
4.对工作票中所列内容即使发生很小疑问,也必须向工作票签发人询问清楚,必要时应 要求作详细补充。
四、值长:
负责审查工作的必要性和检修工期是否与批准期限相符以及工作票所列安全措施是否 正确完备。
五、工作班成员:
认真执行本规程和现场安全措施,互相关心施工安全,并监督本规程和现场安全措施的 实施。
第二节 工作许可制度
第 52 条 工作许可人(值班员)在完成施工现场的安全措施后,还应:
一、会同工作负责人到现场再次检查所做的安全措施,以手触试,证明检修设备确无电 压;
二、对工作负责人指明带电设备的位置和注意事项;
三、.和工作负责人在工作票上分别签名。完成上述许可手续后,工作班方可开始工作。
第 53 条 工作负责人、工作许可人任何一方不得擅自变更安全措施,值班人员不得变更 有关检修设备的运行接线方式。工作中如有特殊情况需要变更时,应事先取得对方的同意。第三节 工作监护制度
第 54 条 完成工作许可手续后,工作负责人(监护人)应向工作班人员交待现场安全措 施、带电部位和其他注意事项。工作负责人(监护人)必须始终在工作现场,对工作班人员 的安全认真监护,及时纠正违反安全的动作。第 55 条 所有工作人员(包括工作负责人),不许单独留在高压室内和室外变电所高压 设备区内。
若工作需要(如测量极性、回路导通试验等),且现场设备具体情况允许时,可以准许 工作班中有实际经验的一人或几人同时在他室进行工作,但工作负责人应在事前将有关安全 注意事项予以详尽的指示。
第 56 条 工作负责人(监护人)在全部停电时,可以参加工作班工作。在部分停电时,只有在安全措施可靠,人员集中在一个工作地点,不致误碰导电部分的情况下,方能参加工 作。
工作票签发人或工作负责人,应根据现场的安全条件、施工范围、工作需要等具体情况,增设专人监护和批准被监护的人数。专责监护人不得兼做其他工作。
第 57 条 工作期间,工作负责人若因故必须离开工作地点时,应指定能胜任的人员临时 代替,离开前应将工作现场交待清楚,并告知工作班人员。原工作负责人返回工作地点时,也应履行同样的交接手续。
若工作负责人需要长时间离开现场,应由原工作票签发人变更新工作负责人,两工作负 责人应做好必要的交接。
第 58 条 值班员如发现工作人员违反安全规程或任何危及工作人员安全的情况,应向工 作负责人提出改正意见,必要时可暂时停止工作,并立即报告上级。第四节 工作间断、转移和终结制度
第 59 条 工作间断时,工作班人员应从工作现场撤出,所有安全措施保持不动,工作票 仍由工作负责人执存。间断后继续工作,无需通过工作许可人。每日收工,应清扫工作地点,开放已封闭的通路,并将工作票交回值班员。次日复工时,应得值班员许可,取回工作票,工作负责人必须事前重新认真检查安全措施是否符合工作票的要求后,方可工作。若无工作 负责人或监护人带领,工作人员不得进入工作地点。
第 60 条 在未办理工作票终结手续以前,值班员不准将施工设备合闸送电。
在工作间断期间,若有紧急需要,值班员可在工作票未交回的情况下合闸送电,但应先 将工作班全班人员已经离开工作地点的确切根据通知工作负责人或电气分场负责人,在得到 他们可以送电的答复后方可执行,并应采取下列措施:
一、拆除临时遮栏、接地线和标示牌,恢复常设遮栏,换挂“止步,高压危险!”的标 示牌;
二、必须在所有通路派专人守候,以便告诉工作班人员“设备已经合闸送电,不得继续 工作”,守候人员在工作票未交回以前,不得离开守候地点。
第 61 条 检修工作结束以前,若需将设备试加工作电压,可按下列条件进行:
一、全体工作人员撤离工作地点;
二、将该系统的所有工作票收回,拆除临时遮栏、接地线和标示牌,恢复常设遮栏;
三、.应在工作负责人和值班员进行全面检查无误后,由值班员进行加压试验。工作班若需继续工作时,应重新履行工作许可手续。
第 62 条 在同一电气连接部分用同一工作票依次在几个工作地点转移工作时,全部安全 措施由值班员在开工前一次做完,不需再办理转移手续,但工作负责人在转移工作地点时,应向工作人员交待带电范围、安全措施和注意事项。
第 63 条 全部工作完毕后,工作班应清扫、整理现场。工作负责人应先周密的检查,待 全体工作人员撤离工作地点后,再向值班人员讲清所修项目、发现的问题、试验结果和存在 问题等,并与值班人员共同检查设备状况,有无遗留物件,是否清洁等,然后在工作票上填 明工作终结时间,经双方签名后,工作票方告终结。
第 64 条 只有在同一停电系统的所有工作票结束,拆除所有接地线、临时遮栏和标示牌,恢复常设遮栏,并得到值班调度员或值班负责人的许可命令后,方可合闸送电。第 65 条 已结束的工作票,保存三个月。第四章 保证安全的技术措施
第 66 条 在全部停电或部分停电的电气设备上工作,必须完成下列措施:
一、停电;
二、验电;
三、装设接地线;
四、悬挂标示牌和装设遮栏。
上述措施由值班员执行。对于无经常值班人员的电气设备,由断开电源人执行,并应有 监护人在场[两线一地制系统验电、装设接地线措施,由局(厂)自行规定]。第一节 停电
第 67 条 工作地点,必须停电的设备如下:
一、检修的设备;
二、与工作人员在进行工作中正常活动范围的距离小于表 2 规定的设备;
三、在 44kV 以下的设备上进行工作,上述安全距离虽大于表 2 规定,但小于表 1 规定,同时又无安全遮栏措施的设备;
表 2 工作人员工作中正常活动范围与带电设备的安全距离
四、带电部分在工作人员后面或两侧无可靠安全措施的设备。
第 68 条 将检修设备停电,必须把各方面的电源完全断开(任何运用中的星形接线设备 的中性点,必须视为带电设备)。禁止在只经断路器(开关)断开电源的设备上工作。必须 拉开隔离开关(刀闸),使各方面至少有一个明显的断开点。与停电设备有关的变压器和电 压互感器,必须从高、低压两侧断开,防止向停电检修设备反送电。
第 69 条 断开断路器(开关)和隔离开关(刀闸)的操作能源。隔离开关(刀闸)操作 把手必须锁住。第二节 验电
第 70 条 验电时,必须用电压等级合适而且合格的验电器,在检修设备进出线两侧各相 分别验电。验电前,应先在有电设备上进行试验,确证验电器良好。如果在木杆、木梯或木 架构上验电,不接地线不能指示者,可在验电器上接地线,但必须经值班负责人许可。第 71 条 高压验电必须戴绝缘手套。验电时应使用相应电压等级的专用验电器。
330kV 及以上的电气设备,在没有相应电压等级的专用验电器的情况下,可使用绝缘棒 代替验电器,根据绝缘棒端有无火花和放电噼啪声来判断有无电压。
第 72 条 表示设备断开和允许进入间隔的信号、经常接入的电压表等,不得作为设备无 电压的根据。但如果指示有电,则禁止在该设备上工作。第三节 装设接地线
第 73 条 当验明设备确已无电压后,应立即将检修设备接地并三相短路。这是保护工作 人员在工作地点防止突然来电的可靠安全措施,同时设备断开部分的剩余电荷,亦可因接地 而放尽。
第 74 条 对于可能送电至停电设备的各方面或停电设备可能产生感应电压的都要装设 接地线,所装接地线与带电部分应符合安全距离的规定。
第 75 条 检修母线时,应根据母线的长短和有无感应电压等实际情况确定地线数量。检 修 10m 及以下的母线,可以只装设一组接地线。在门型架构的线路侧进行停电检修,如工作
地点与所装接地线的距离小于 10m,工作地点虽在接地线外侧,也可不另装接地线。第 76 条 检修部分若分为几个在电气上不相连接的部分[如分段母线以隔离开关(刀闸)或断路器(开关)隔开分成几段],则各段应分别验电接地短路。接地线与检修部分之间不 得连有断路器(开关)或熔断器(保险)。降压变电所全部停电时,应将各个可能来电侧的 部分接地短路,其余部分不必每段都装设接地线。
第 77 条 在室内配电装置上,接地线应装在该装置导电部分的规定地点,这些地点的油 漆应刮去,并划下黑色记号。
所有配电装置的适当地点,均应设有接地网的接头。接地电阻必须合格。
第 78 条 装设接地线必须由两人进行。若为单人值班,只允许使用接地刀闸接地,或使 用绝缘棒合接地刀闸。
第 79 条 装设接地线必须先接接地端,后接导体端,且必须接触良好。拆接地线的顺序 与此相反。装、拆接地线均应使用绝缘棒和戴绝缘手套。
第 80 条 接地线应用多股软裸铜线,其截面应符合短路电流的要求,但不得小于 25。接地线在每次装设以前应经过详细检查。损坏的接地线应及时修理或更换。禁止使用不符合 规定的导线作接地或短路之用。
接地线必须使用专用的线夹固定在导体上,严禁用缠绕的方法进行接地或短路。
第 81 条 高压回路上的工作,需要拆除全部或一部分接地线后始能进行工作者〔如测量 母线和电缆的绝缘电阻,检查断路器(开关)触头是否同时接触〕,如:
一、拆除一相接地线;
二、拆除接地线,保留短路线;
三、将接地线全部拆除或拉开接地刀闸。
必须征得值班员的许可(根据调度员命令装设的接地线,必须征得调度员的许可),方 可进行。工作完毕后立即恢复。
第 82 条 每组接地线均应编号,并存放在固定地点。存放位置亦应编号,接地线号码与 存放位置号码必须一致。
第 83 条 装、拆接地线,应做好记录,交接班时应交待清楚。第四节 悬挂标示牌和装设遮栏
第 84 条 在一经合闸即可送电到工作地点的断路器(开关)和隔离开关(刀闸)的操作 把手上,均应悬挂“禁止合闸,有人工作!”的标示牌(见附录四)。如果线路上有人工作,应在线路断路器(开关)和隔离开关(刀闸)操作把手上悬挂“禁 止合闸,线路有人工作!”的标示牌,标示牌的悬挂和拆除,应按调度员的命令执行。第 85 条 部分停电的工作,安全距离小于表 1 规定距离以内的未停电设备,应装设临时 遮栏。临时遮栏与带电部分的距离,不得小于表 2 的规定数值。临时遮栏可用干燥木材、橡
胶或其他坚韧绝缘材料制成,装设应牢固,并悬挂“止步,高压危险!”的标示牌。
35kV 及以下设备的临时遮栏,如因工作特殊需要,可用绝缘挡板与带电部分直接接触。但此种挡板必须具有高度的绝缘性能,并符合附录 E 的要求。
第 86 条 在室内高压设备上工作,应在工作地点两旁间隔和对面间隔的遮栏上和禁止通 行的过道上悬挂“止步,高压危险!”的标示牌。
第 87 条 在室外地面高压设备上工作,应在工作地点四周用绳子做好围栏,围栏上悬挂 适当数量的“止步,高压危险!”标示牌,标示牌必须朝向围栏里面。第 88 条 在工作地点悬挂“在此工作!”的标示牌。
第 89 条 在室外架构上工作,则应在工作地点邻近带电部分的横梁上,悬挂“止步,高 压危险!”的标示牌。此项标示牌在值班人员的监护下,由工作人员悬挂。在工作人员上下 铁架和梯子上应悬挂“从此上下!”的标示牌。在邻近其他可能误登的带电架构上,应悬挂 “禁止攀登,高压危险!”的标示牌。
第 90 条 严禁工作人员在工作中移动或拆除遮栏、接地线和标示牌。第五章 线路作业时发电厂和变电所的安全措施
第 91 条 线路的停送电均应按照值班调度员或有关单位书面指定的人员的命令执行。严 禁约时停、送电。停电时,必须先将该线路可能来电的所有断路器(开关)、线路隔离开关(刀闸)、母线隔离开关(刀闸)全部拉开,用验电器验明确无电压后,在所有线路上可能 来电的各端装接地线,线路隔离开关(刀闸)操作把手上挂“禁止合闸,线路有人工作!” 的标示牌。
第 92 条 值班调度员必须将线路停电检修的工作班组数目、工作负责人姓名、工作地点 和工作任务记入记录簿。
工作结束时,应得到工作负责人(包括用户)的竣工报告,确认所有工作班组均已竣工,接地线已拆除,工作人员已全部撤离线路,并与记录簿核对无误后,方可下令拆除发电厂或 变电所内的安全措施,向线路送电。
第 93 条 当用户管辖的线路要求停电时,必须得到用户工作负责人的书面申请方可停 电,并做好安全措施,恢复送电,必须接到原申请人的通知后方可进行。第六章 带电作业 第一节 一般规定
第 94 条 本章的规定适用于在海拔 1000m 及以下交流 10~500kV 的高压架空电力线路、变电所(发电厂)电气设备上采用等电位、中间电位和地电位方式进行的带电作业,以及低 压带电作业。
两线一地的线路及其电气设备上不宜进行带电作业。
第 95 条 带电作业应在良好天气下进行。如遇雷、雨、雪、雾不得进行带电作业,风力 大于 5 级时,一般不宜进行带电作业。
在特殊情况下,必须在恶劣天气进行带电抢修时,应组织有关人员充分讨论并采取必要 的安全措施,经厂(局)主管生产领导(总工程师)批准后方可进行。
第 96 条 对于比较复杂,难度较大的带电作业新项目和研制的新工具必须进行科学试 验,确认安全可靠,编出操作工艺方案和安全措施,并经厂(局)主管生产领导(总工程师)批准后方可进行和使用。第 97 条 带电作业工作票签发人和工作负责人应具有带电作业实践经验。工作票签发人 必须经厂(局)领导批准,工作负责人也可经工区领导批准。
第 98 条 带电作业必须设专人监护。监护人应由有带电作业实践经验的人员担任。监护 人不得直接操作。监护的范围不得超过一个作业点。复杂的或高杆塔上的作业应增设(塔上)监护人。
第 99 条 带电作业工作票签发人和工作负责人对带电作业现场情况不熟悉时,应组织有 经验的人员到现场查勘。根据查勘结果作出能否进行带电作业的判断,并确定作业方法和所 需工具以及应采取的措施。
第 100 条 带电作业工作负责人在带电作业工作开始前应与调度联系,工作结束后向调 度汇报。
第 101 条 带电作业有下列情况之一者应停用重合闸,并不得强送电:
一、中性点有效接地的系统中有可能引起单相接地的作业。
二、中性点非有效接地的系统中有可能引起相间短路的作业。
三、工作票签发人或工作负责人认为需要停用重合闸的作业。严禁约时停用或恢复重合闸。
第 102 条 在带电作业过程中如设备突然停电,作业人员应视设备仍然带电。工作负责 人应尽快与调度联系,调度未与工作负责人取得联系前不得强送电。第二节 一般技术措施
第 103 条 进行地电位带电作业时,人身与带电体间的安全距离不得小于表 3 的规定。表 3 人身与带电体的安全距离
注:1)因受设备限制达不到 1.8m 时,经厂(局)主管生产领导(总工程师)批准,并 采取必要的措施后,可采用括号内(1.6m)的数值。2)由于 500kV 带电作业经验不多,此数据为暂定数据。
第 104 条 35kV 及以下的带电设备,不能满足表 3 规定的最小安全距离时,必须采取可 靠的绝缘隔离措施。
第 105 条 绝缘操作杆,绝缘承力工具和绝缘绳索的有效长度不得小于表 4 的规定。表 4 绝缘工具最小有效绝缘长度
第 106 条 更换绝缘子或在绝缘子串上作业时,良好绝缘子片数不得少于表 5 的规定。表 5 良好绝缘子最少片数
第 107 条 更换直线绝缘子串或移动导线的作业,当采用单吊线装置时,应采取防止导 线脱落时的后备保护措施。
第 108 条 在绝缘子串未脱离导线前,拆、装靠近横担的第一片绝缘子时,必须采用专 用短接线或穿屏蔽服方可直接进行操作。
第 109 条 在市区或人口稠密的地区进行带电作业时,工作现场应设置围栏,严禁非工 作人员入内。
第三节 等电位作业
第 110 条 等电位作业一般在 63(66)kV 及以上电压等级的电力线路和电气设备上进行。若须在 35kV 及以下电压等级采用等电位作业时,应采取可靠的绝缘隔离措施。
第 111 条 等电位作业人员必须在衣服外面穿合格的全套屏蔽服(包括帽、衣、裤、手 套、袜和鞋),且各部分应连接好,屏蔽服内还应穿阻燃内衣。
严禁通过屏蔽服断、接接地电流、空载线路和耦合电容器的电容电流。
第 112 条 等电位作业人员对地距离应不小于表 3 的规定,对邻相导线的距离应不小于 表 6 的规定。
表 6 等电位作业人员对邻相导线的最小距离 第 113 条 等电位作业人员在绝缘梯上作业或沿绝缘梯进入强电场时,其与接地体和带 电体两部分间所组成的组合间隙不得小于表 7 的规定。表 7 组合间隙最小距离
第 114 条 等电位作业人员沿绝缘子串进入强电场的作业,只能在 220kV 及以上电压等 级的绝缘子串上进行。扣除人体短接的和零值的绝缘子片后,良好绝缘子片数不得小于表 5 的规定,其组合间隙不得小于表 7 的规定。若组合间隙不满足表 7 的规定,应加装保护间隙。
第 115 条 等电位作业人员在电位转移前,应得到工作负责人的许可,并系好安全带。转移电位时人体裸露部分与带电体的距离不应小于表 8 的规定。表 8 转移电位时人体裸露部分与带电体的最小距离
第 116 条 等电位作业人员与地面作业人员传递工具和材料时,必须使用绝缘工具或绝 缘绳索进行,其有效长度不得小于表 4 的规定。
第 117 条 沿导、地线上悬挂的软、硬梯或飞车进入强电场的作业应遵守下列规定:
一、在连接档距的导、地线上挂梯(或飞车)时,其导、地线的截面不得小于: 钢芯铝绞线 120mm 2 铜 绞 线 70 mm 2 钢 绞 线 50 mm 2
二、有下列情况之一者,应经验算合格,并经厂(局)主管生产领导(总工程师)批准 后才能进行:
1.在孤立档距的导、地线上的作业; 2.在有断股的导、地线上的作业; 3.在有锈蚀的地线上的作业; 4.在其它型号导、地线上的作业; 5.二人以上在导、地线上的作业。
三、在导、地线上悬挂梯子前,必须检查本档两端杆塔处导、地线的紧固情况。挂梯载 荷后地线及人体对导线的最小间距应比表 3 中的数值增大 0.5m,导线及人体对被跨越的电
力线路、通信线路和其他建筑物的最小距离应比表 3 的安全距离增大 1m。
四、在瓷横担线路上严禁挂梯作业,在转动横担的线路上挂梯前应将横担固定。
第 118 条 等电位作业人员在作业中严禁用酒精、汽油等易燃品擦拭带电体及绝缘部分,防止起火。
第四节 带电断、接引线
第 119 条 带电断、接空载线路,必须遵守下列规定:
一、带电断、接空载线路时,必须确认线路的终端断路器(开关)[或隔离开关(刀闸)] 确已断开,接入线路侧的变压器、电压互感器确已退出运行后,方可进行。严禁带负荷断、接引线。
二、带电断、接空载线路时,作业人员应戴护目镜,并应采取消弧措施,消弧工具的断 流能力应与被断、接的空载线路电压等级及电容电流相适应。如使用消弧绳,则其断、接的 空载线路的长度不应大于表 9 的规定,且作业人员与断开点应保持 4m 以上的距离。表 9 使用消弧绳断、接空载线路的最大长度
注:线路长度包括分支在内,但不包括电缆线路。
三、在查明线路确无接地,绝缘良好,线路上无人工作且相位确定无误后才可进行带电 断、接引线。
四、带电接引时未接通相的导线及带电断引时已断开相的导线将因感应而带电。为防止 电击,应采取措施后才能触及。
五、严禁同时接触未接通的或已断开的导线两个断头,以防人体串入电路。第 120 条 严禁用断、接空载线路的方法使两电源解列或并列。
第 121 条 带电断、接耦合电容器时,应将其信号、接地刀闸合上并应停用高频保护。被断开的电容器应立即对地放电。
第 122 条 带电断、接空载线路、耦合电容器、避雷器等设备时,应采取防止引流线摆 动的措施。
第五节 带电短接设备
第 123 条 用分流线短接断路器(开关)、隔离开关(刀闸)等载流设备时,必须遵守 下列规定:
一、短接前一定要核对相位。
二、组装分流线的导线处必须清除氧化层,且线夹接触应牢固可靠。
三、35kV 及以下设备使用的绝缘分流线的绝缘水平应符合表 17 的规定。
四、断路器(开关)必须处于合闸位置,并取下跳闸回路熔断器(保险),锁死跳闸机 构后,方可短接。
五、分流线应支撑好,以防摆动造成接地或短路。
第 124 条 阻波器被短路前,严防等电位作业人员人体短接阻波器。
第 125 条 短接开关设备或阻波器的分流线截面和两端线夹的载流容量,应满足最大负 荷电流的要求。第六节 带电水冲洗
第 126 条 带电水冲洗一般应在良好天气时进行,风力大于四级,气温低于零下 3℃,雨天、雪天、雾天及雷电天气不宜进行。
第 127 条 带电水冲洗作业前应掌握绝缘子的脏污情况,当盐密值大于表 10 临界盐密值 的规定时,一般不宜进行水冲洗,否则,应增大水电阻率来补救。避雷器及密封不良的设备 不宜进行带电水冲洗。
第 128 条 带电水冲洗用水的电阻率一般不低于 1500Ωcm,冲洗 220kV 变电设备时水 电阻率不应低于 3000Ωcm,并应符合表 10 的要求。每次冲洗前都应用合格的水阻表测量 水电阻率,应从水枪出口处取水样进行测量。如用水车等容器盛水,每车水都应测量水电阻 率。
表 10 带电水冲洗临界盐密值 1)
(仅适用于 220kV 及以下)
注:1)330kV 及 500kV 等级的临界盐密值尚不成熟,暂不列入。2)爬电比距指电力设备外绝缘的爬电距离与设备最高工作电压之比。
第 129 条 以水柱为主绝缘的大、中、小型水冲(喷嘴直径为 3mm 及以下者称小水冲; 直径为 4~8mm 者称中水冲;直径为 9mm 及以上者称大水冲),其水枪喷嘴与带电体之间的
水柱长度不得小于表 11 的规定。大、中型水冲水枪喷嘴均应可靠接地。表 11 喷嘴与带电体之间的水柱长度(m)
第 130 条 由水柱、绝缘杆、引水管(指有效绝缘部分)组成的小水冲工具,其组合绝 缘应满足如下要求:
一、在工作状态下应能耐受表 17 规定的试验电压。
二、在最大工频过电压下流经操作人员人体的电流应不超过 1mA,试验时间不小于 5min。第 131 条 利用组合绝缘的小水冲工具进行冲洗时,冲洗工具严禁触及带电体。引水管 的有效绝缘部分不得触及接地体。
操作杆的使用及保管均按带电作业工具的有关规定执行。
第 132 条 带电冲洗前应注意调整好水泵压强,使水柱射程远且水流密集。当水压不足 时,不得将水枪对准被冲的带电设备。冲洗用水泵应良好接地。
第 133 条 带电水冲洗应注意选择合适的冲洗方法。直径较大的绝缘子宜采用双枪跟踪 法或其它方法,并应防止被冲洗设备表面出现污水线。当被冲绝缘子未冲洗干净时,水枪切 勿强行离开,以免造成闪络。
第 134 条 带电水冲洗前要确知设备绝缘是否良好。有零值及低值的绝缘子及瓷质有裂 纹时,一般不可冲洗。
第 135 条 冲洗悬垂绝缘子串、瓷横担、耐张绝缘子串时,应从导线侧向横担侧依次冲 洗。冲洗支柱绝缘子及绝缘瓷套时,应从下向上冲洗。
第 136 条 冲洗绝缘子时应注意风向,必须先冲下风侧,后冲上风侧,对于上、下层布 置的绝缘子应先冲下层,后冲上层,还要注意冲洗角度,严防临近绝缘子在溅射的水雾中发 生闪络。
第七节 带电爆炸压接
第 137 条 带电爆炸压接应使用工业 8 号纸壳火雷管。
第 138 条 为防止雷管在电场中自行起爆,引爆系统(包括雷管、导火索、拉火管)必 须全部屏蔽。
引爆方式可采用地面引爆和等电位引爆。当采用等电位引爆时,应做到:引爆系统与导 线连接牢固;安装引爆系统时,作业人员应始终与导线保持等电位;导火索应有足够的长度,以保证作业人员安全撤离。
第 139 条 炸药爆炸会降低空气绝缘。为保证安全,应遵守下列规定:
一、爆炸时对地及相间的安全距离应满足表 12 的规定。
二、如不能满足表 12 的规定,可在药包外包食盐或聚胺脂泡沫塑料,以减小由于爆炸 时造成的空气绝缘降低。
表 12 爆炸点对地及相间的安全距离
第140条 爆炸压接时所有工作人员均应撤到爆炸点30m以外雷管开口端反向的安全区。第 141 条 爆炸压接时,爆炸点距绝缘子、分流线、金属承力工具、绝缘工具的距离应 大于表 13 的规定,否则,应采取保护措施。表 13 爆炸点距邻近物的最小距离
第 142 条 若分裂导线间距小于 0.4m,应设法加大距离或采取保护措施。第 143 条 出现瞎炮时,应按《电业安全工作规程》(热力和机械部分)的有关规定处
理。爆炸压接使用的炸药、雷管、导火索、拉火管均为易燃易爆物品,均应按上述规程有关 规定加以管理。
第八节 感应电压防护
第 144 条 在 220~500kV 电压等级的线路杆塔上及变电所构架上作业,必须采取防静电 感应措施,例如,穿着静电感应防护服或导电鞋等。
第 145 条 带电更换架空地线或架设耦合地线时,应通过放线滑车可靠接地。
第 146 条 绝缘架空地线应视为带电体。作业人员与绝缘架空地线之间的距离不应小于 0.4m。如需在绝缘架空地线上作业应用接地线将其可靠接地或采用等电位方式进行。第 147 条 用绝缘绳索传递大件金属物品(包括工具、材料等)时,杆塔或地面上作业 人员应将金属物品接地后再接触,以防电击。第九节 高架绝缘斗臂车
第 148 条 使用前应认真检查,并在预定位置空斗试操作一次,确认液压传动、回转、升降、伸缩系统工作正常,操作灵活,制动装置可靠,方可使用。
第 149 条 绝缘臂的有效绝缘长度应大于表 14 的规定,并应在其下端装设泄漏电流监视 装置。
第 150 条 绝缘臂下节的金属部分,在仰起回转过程中,对带电体的距离应按表 3 的规 定值增加 0.5m。
工作中车体应良好接地。表 14 绝缘臂的最小长度
第 151 条 绝缘斗用于 10~35kV 带电作业时,其壁厚及层间绝缘水平应满足表 17 耐受 电压的规定。
第 152 条 操作绝缘斗臂车人员应熟悉带电作业的有关规定,并经专门培训,在工作过 程中不得离开操作台,且斗臂车的发动机不得熄火。第十节 带电气吹清扫
第 153 条 用于气吹的操作杆和出气软管,应按表 17 相应电压等级要求耐压试验合格。储气风包、出气软管及辅助罐等压力容器应作水压试验(108N/cm 2)。
第 154 条 喷嘴宜用硬质绝缘材料制成。若用金属材料制作时,其长度不宜超过 100mm。喷嘴内径以 3.5~6mm 为宜。第 155 条 用作辅料的锯末,须经 16~30 目筛网筛选和干燥。装入辅料罐前,应用 2500V 摇表测量,其绝缘电阻应大于 9000MΩ。
第 156 条 现场作业前,应认真检查空气压缩机是否正常,风包安全阀门是否动作可靠,风包内有余水时,应先放完。空气压缩机的排气压力以 59~98N/cm 2为宜。
第 157 条 带电气吹操作人员工作中,必须戴护目镜、口罩和防尘帽。操作人员宜站在上风侧位置作业,且须保持表 3 规定的安全距离。
第 158 条 在带电气吹作业时,作业人员应注意喷嘴不得垂直电瓷表面及定点气吹,以 免损坏电瓷和釉质表面层。
第 159 条 带电气吹清扫时,如遇喷嘴锯末阻塞,应先减压,再行消除障碍。第十一节 保护间隙
第 160 条 保护间隙的接地线应用多股软铜线。其截面应满足接地短路容量的要求,但 最小不得小于 25mm 2 第 161 条 圆弧形保护间隙的距离应按表 15 的规定进行整定。表 15 圆弧形保护间隙定值
第 162 条 使用保护间隙时,应遵守下列规定:
一、悬挂保护间隙前,应与调度联系停用重合闸。
二、悬挂保护间隙应先将其与接地网可靠接地,再将保护间隙挂在导线上,并使其接触 良好。拆除程序相反。
三、保护间隙应挂在相邻杆塔的导线上,悬挂后,须派专人看守,在有人畜通过的地区,还应增设围栏。
四、装、拆保护间隙的人员应穿全套屏蔽服。第十二节 带电检测绝缘子 第 163 条 使用火花间隙检测器检测绝缘子时,应遵守下列规定:
一、检测前应对检测器进行检测,保证操作灵活,测量准确。
二、针式及少于 3 片的悬式绝缘子不得使用火花间隙检测器进行检测。
三、当检测 35kV 及以上电压等级的绝缘子串时,发现同一串中的零值绝缘子片数达到 表 16 的规定,应立即停止。
如绝缘子串的总片数超过表 16 规定时,零值绝缘子片数可相应增加。表 16 一串中允许零值绝缘子片数
四、应在干燥天气进行。第十三节 低压带电作业
第 164 条 低压带电作业应设专人监护,使用有绝缘柄的工具,工作时站在干燥的绝缘 物上进行,并戴手套和安全帽,必须穿长袖衣工作,严禁使用锉刀、金属尺和带有金属物的 毛刷、毛掸等工具。
第 165 条 高低压同杆架设,在低压带电线路上工作时,应先检查与高压线的距离,采 取防止误碰带电高压设备的措施。在低压带电导线未采取绝缘措施时,工作人员不得穿越。在带电的低压配电装置上工作时,应采取防止相间短路和单相接地的绝缘隔离措施。第 166 条 上杆前应先分清火、地线,选好工作位置。断开导线时,应先断开火线,后 断开地线。搭接导线时,顺序应相反。人体不得同时接触两根线头。
第十四节 带电作业工具的保管与试验
第 167 条 带电作业工具应置于通风良好、备有红外线灯泡或去湿设施的清洁干燥的专 用房间存放。
第 168 条 高架绝缘斗臂车的绝缘部分应有防潮保护罩,并应存放在通风、干燥的车库 内。
第 169 条 在运输过程中,带电绝缘工具应装在专用工具袋、工具箱或专用工具车内,以防受潮和损伤。
第 170 条 不合格的带电作业工具应及时检修或报废,不得继续使用。
第 171 条 发现绝缘工具受潮或表面损伤、脏污时,应及时处理并经试验合格后方可使 用。
第 172 条 使用工具前应仔细检查其是否损坏、变形、失灵,并使用 2500V 绝缘摇表或 绝缘检测仪进行分段绝缘检测(电极宽 2cm,极间宽 2cm),阻值应不低于 700MΩ。操作绝
缘工具时应戴清洁、干燥的手套,并应防止绝缘工具在使用中脏污和受潮。
第 173 条 带电作业工具应设专人保管,登记造册,并建立每件工具的试验记录。第 174 条 带电作业工具应定期进行电气试验及机械试验。其试验周期为: 电气试验:预防性试验每年一次,检查性试验每年一次,两次试验间隔半年。机械试验:绝缘工具每年一次,金属工具两年一次。第 175 条 绝缘工具电气试验项目及标准见表 17。
操作冲击耐压试验宜采用 250/2500μs 的标准波,以无一次击穿、闪络为合格。工频耐压试验以无击穿、无闪络及过热为合格。
高压电极应使用直径不小于 30mm 的金属管,被试品应垂直悬挂。接地极的对地距离为 1.0~1.2m。接地极及接高压的电极(无金具时)处以 50mm 宽金属泊缠绕。试品间距不小于
500mm,单导线两侧均压球直径不小于 200mm,均压球距试品不小于 1.5m。试品应整根进行试验,不得分段。表 17 绝缘工具的试验项目及标准
第 176 条 绝缘工具的检查性试验条件是:将绝缘工具分成若干段进行工频耐压,每 300mm 耐压 75kV,时间为 1min,以无击穿、闪络及过热为合格。
第 177 条 组合绝缘的水冲洗工具应在工作状态下进行电气试验。除按表 17 的项目和标 准试验外(指 220kV 及以下电压等级),还应增加工频泄漏试验,试验电压见表 18。泄漏 电流以不超过 1mA 为合格,试验时间 5min。
试验时的水电阻率为 1500Ωcm(适用于 220kV 及以下电压等级)。表 18 组合绝缘水冲洗工具工频泄漏试验电压值 第 178 条 带电作业工具的机械试验标准:
静荷重试验:2.5 倍允许工作负荷下持续 5min,工具无变形及损伤者为合格。
动荷重试验:1.5 倍允许工作负荷下实际操作 3 次,工具灵活、轻便,无卡住现象者为 合格。
第 179 条 屏蔽服衣裤最远端点之间的电阻值均不得大于 20Ω。第七章 发电机、同期调相机和高压电动机的维护工作
第 180 条 检修发电机、同期调相机和高压电动机应填用第一种工作票。
第 181 条 发电厂主要机组(锅炉、汽机、发电机)停运检修,只需第一天办理开工 手续,以后每天开工时,应由工作负责人检查现场,核对安全措施。检修期间工作票始终由 工作负责人保存。工作全部结束,再办理工作票结束手续。在同一机组的几个电动机上依次工作时,可填用一张工作票。第 182 条 检修发电机、同期调相机必须做好下列安全措施:
一、断开发电机、同期调相机的断路器(开关)和隔离开关(刀闸);
二、待发电机和同期调相机完全停止后,在操作把手、按钮、机组的启动装置、并车装 置插座和盘车装置的操作把手上悬挂“禁止合闸,有人工作!”的标示牌;
三、若本机尚可从其他电源获得励磁电流,则此项电源亦必须断开,并悬挂“禁止合闸,有人工作!”的标示牌;
四、断开断路器(开关)、隔离开关(刀闸)的操作能源。如调相机有启动用的电动机,还应断开此电动机的断路器(开关)和隔离开关(刀闸),并悬挂“禁止合闸,有人工作!” 的标示牌;
五、将电压互感器从高、低压两侧断开;
六、经验明无电压后,在发电机和断路器(开关)间装设接地线;
七、检修机组中性点与其他发电机的中性点连在一起的,则在工作前必须将检修发电机 的中性点分开;
八、检修机组装有二氧化碳或蒸汽灭火装置的,则在风道内工作前,应采取防止灭火装 置误动的必要措施;
九、检修机组装有可以堵塞机内空气流通的自动闸板风门的,应采取措施保证使风门不 能关闭,以防窒息。
第 183 条 转动着的发电机、同期调相机,即使未加励磁,亦应认为有电压。
禁止在转动着的发电机、同期调相机的回路上工作,或用手触摸高压绕组。必须不停机 进行紧急修理时,应先将励磁回路切断,投入自动灭磁装置,然后将定子引出线与中性点短 路接地。在拆装短路接地线时,应戴绝缘手套,穿绝缘靴或站在绝缘垫上,并戴护目眼镜。第 184 条 测量轴电压和在转动着的发电机上用电压表测量转子绝缘的工作,应使用专 用电刷,电刷上应装有 300mm 以上的绝缘柄。
第 185 条 在转动着的电机上调整、清扫电刷及滑环时,应由有经验的电工担任,并遵 守下列规定:
一、工作人员必须特别小心,不使衣服及擦拭材料被机器挂住,扣紧袖口,发辫应放在 帽内;
二、工作时站在绝缘垫上(该绝缘垫为常设固定型绝缘垫),不得同时接触两极或一极 与接地部分,也不能两人同时进行工作。
第 186 条 检修高压电动机和启动装置时,应做好下列安全措施:
一、断开电源断路器(开关)、隔离开关(刀闸),经验明确无电压后装设接地线或在 隔离开关(刀闸)间装绝缘隔板,小车开关应从成套配电装置内拉出并关门上锁;
二、在断路器(开关)、隔离开关(刀闸)把手上悬挂“禁止合闸,有人工作!”的标 示牌;
三、拆开后的电缆头须三相短路接地;
四、做好防止被其带动的机械(如水泵、空气压缩机、引风机等)引起电动机转动的 措施,并在阀门上悬挂“禁止合闸,有人工作!”的标示牌。
第 187 条 禁止在转动着的高压电动机及其附属装置回路上进行工作。必须在转动着的 电动机转子电阻回路上进行工作时,应先提起碳刷或将电阻完全切除。工作时要戴手套或使 用有绝缘把手的工具,穿绝缘靴或站在绝缘垫上。
第 188 条 电动机的引出线和电缆头以及外露的转动部分均应装设牢固的遮栏或护罩。第 189 条 电动机及起动装置的外壳均应接地。禁止在运转中的电动机的接地线上进行 工作。
第 190 条 工作尚未全部终结,而需送电试验电动机或起动装置时,应收回全部工作票 并通知有关机械部分检修人员后,方可送电。第八章 在六氟化硫电气设备上的工作
第 191 条 装有 SF6设备的配电装置室和 SF6气体实验室,必须装设强力通风装置。风口 应设置在室内底部。
第 192 条 在室内,设备充装 SF6气体时,周围环境相对湿度应≤80%,同时必须开启通 风系统,并避免 SF6气体漏泄到工作区。工作区空气中 SF6气体含量不得超过 1000ppm。第 193 条 SF6新气应具有厂家名称、装灌日期、批号及质量检验单。SF6新气到货后应 按有关规定进行复核、检验,合格后方准使用。SF6新气标准见附录八。
在气瓶内存放半年以上的 SF6气体,使用前应先检验其水份和空气含量,符合标准后方 准使用。
第 194 条 SF6电气设备投运前,应检验设备气室内 SF6气体水份和空气含量。
设备运行后每三个月检查一次 SF6气体含水量,直至稳定后,方可每年检测一次含水量。SF6气体有明显变化时,应请上级复核。
第 195 条 主控制室与 SF6配电装置室间要采取气密性隔离措施。
第 196 条 工作人员进入 SF6配电装置室,必须先通风 15min,并用检漏仪测量 SF6气体 含量。尽量避免一人进入 SF6配电装置室进行巡视,不准一人进入从事检修工作。
第 197 条 工作人员不准在 SF6设备防爆膜附近停留,若在巡视中发现异常情况,应立 即报告,查明原因,采取有效措施进行处理。
第 198 条 进入 SF6配电装置低位区或电缆沟进行工作应先检测含氧量(不低于 18%)和 SF6气体含量是否合格。
第 199 条 在 SF6配电装置室低位区应安装能报警的氧量仪和 SF6气体泄漏警报仪。这些 仪器应定期试验,保证完好。
第 200 条 设备解体检修前,必须对 SF6气体进行检验。根据有毒气体的含量,采取安 全防护措施。检修人员需着防护服并根据需要配戴防毒面具。打开设备封盖后,检修人员应 暂离现场 30min。取出吸附剂和清除粉尘时,检修人员应戴防毒面具和防护手套。第 201 条 设备内的 SF6气体不得向大气排放,应采用净化装置回收,经处理合格后方 准使用。
设备抽真空后,用高纯氮气冲洗 3 次[压力为 9.8×10 4Pa(1 个大气压)]。将清出的
吸附剂、金属粉末等废物放入 20%氢氧化钠水溶液中浸泡 12h 后深埋。
第 202 条 从 SF6气体钢瓶引出气体时,必须使用减压阀降压。当瓶内压力降至 9.8×10 4Pa(1 个大气压)时,即停止引出气体,并关紧气瓶阀门,戴上瓶帽,防止气体泄 漏。
第 203 条 发生紧急事故应立即开启全部通风系统进行通风。发生设备防爆膜破裂事故 时,应停电处理,并用汽油或丙酮擦拭干净。
第 204 条 进行气体采样和处理一般渗漏时,要戴防毒面具并进行通风。
第 205 条 检修结束后,检修人员应洗澡,把用过的工器具、防护用具清洗干净。
第 206 条 SF6气瓶应放置在阴凉干燥、通风良好、敞开的专门场所,直立保存,并应远 离热源和油污的地方,防潮、防阳光曝晒,并不得有水份或油污粘在阀门上。搬运时,应轻装轻卸。
第 207 条 未经检验的 SF6新气气瓶和已检验合格的气体气瓶应分别存放,不得混淆。第九章 在停电的低压配电装置和低压导线上的工作
第 208 条 低压配电盘、配电箱和电源干线上的工作,应填用第二种工作票。在低压电动机和照明回路上工作,可用口头联系。上述工作至少由两人进行。
第 209 条 低压回路停电的安全措施:
一、将检修设备的各方面电源断开,取下熔断器(保险),在刀闸操作把手上挂“禁止 合闸,有人工作!”的标示牌。
二、工作前必须验电。
三、根据需要采取其他安全措施。
第 210 条 停电更换保险器后,恢复操作时,应戴手套和护目眼镜。第十章 在继电保护、仪表第二次回路上的工作 第 211 条 下列情况应填用第一种工作票:
一、在高压室遮栏内或与导电部分小于表 1 规定的安全距离进行继电器和仪表等的检查 试验时,需将高压设备停电的。
二、检查高压电动机和起动装置的继电器和仪表需将高压设备停电的。第 212 条 下列情况应填用第二种工作票: 一、一次电流继电器有特殊装置可以在运行中改变定值的。
二、对于连于电流互感器或电压互感器二次绕组并装在通道上或配电盘上的继电器和保 护装置,可以不断开所保护的高压设备的。上述工作至少由两人进行。
第 213 条 继电保护人员在现场工作过程中,凡遇到异常情况(如直流系统接地等)或 开关跳闸时,不论与本身工作是否有关,应立即停止工作,保持现状,待查明原因,确定与 本工作无关时方可继续工作;若异常情况是本身工作所引起,应保留现场并立即通知值班人 员,以便及时处理。
第 214 条 工作前应做好准备,了解工作地点一次及二次设备运行情况和上次的检验记 录、图纸是否符合实际。
第 215 条 现场工作开始前,应查对已做的安全措施是否符合要求,运行设备与检修设 备是否明确分开,还应看清设备名称,严防走错位置。
第 216 条 在全部或部分带电的盘上进行工作时,应将检修设备与运行设备前后以明显 的标志隔开(如盘后用红布帘,盘前用“在此工作”标志牌等)。
第 217 条 在保护盘上或附近进行打眼等振动较大的工作时,应采取防止运行中设备掉 闸的措施,必要时经值班调度员或值班负责人同意,将保护暂时停用。
第 218 条 在继电保护屏间的通道上搬运或安放试验设备时,要与运行设备保持一定距 离,防止误碰运行设备,造成保护误动作。清扫运行设备和二次回路时,要防止振动,防止 误碰,要使用绝缘工具。
第 219 条 继电保护装置做传动试验或一次通电时,应通知值班员和有关人员,并由工 作负责人或由他派人到现场监视,方可进行。
第 220 条 所有电流互感器和电压互感器的二次绕组应有永久性的、可靠的保护接地。第 221 条 在带电的电流互感器二次回路上工作时,应采取下列安全措施:
一、严禁将电流互感器二次侧开路;
二、短路电流互感器二次绕组,必须使用短路片或短路线,短路应妥善可靠,严禁用导 线缠绕;
三、严禁在电流互感器与短路端子之间的回路和导线上进行任何工作;
四、工作必须认真、谨慎,不得将回路的永久接地点断开;
五、工作时,必须有专人监护,使用绝缘工具,并站在绝缘垫上。
第 222 条 在带电的电压互感器二次回路上工作时,应采取下列安全措施:
一、严格防止短路或接地。应使用绝缘工具,戴手套。必要时,工作前停用有关保护装 置;
二、接临时负载,必须装有专用的刀闸和熔断器(保险)。
第 223 条 二次回路通电或耐压试验前,应通知值班员和有关人员,并派人到各现场看 守,检查回路上确无人工作后,方可加压。
电压互感器的二次回路通电试验时,为防止由二次侧向一次侧反充电,除应将二次回路 断开外,还应取下一次熔断器(保险)或断开刀闸。
第 224 条 检验继电保护和仪表的工作人员,不准对运行中的设备、信号系统、保护压 板进行操作,但在取得值班人员许可并在检修工作盘两侧开关把手上采取防误操作措施后,可拉合检修开关。
第 225 条 试验用刀闸必须带罩,禁止从运行设备上直接取试验电源,熔丝配合要适当,要防止越级熔断总电源熔丝。试验结线要经第二人复查后,方可通电。
第 226 条 保护装置二次回路变动时,严防寄生回路存在,没用的线应拆除,临时所垫 纸片应取出,接好已拆下的线头。第十一章 电气试验 第一节 高压试验
第 227 条 高压试验应填写第一种工作票。
在一个电气连接部分同时有检修和试验时,可填写一张工作票,但在试验前应得到检修 工作负责人的许可。
在同一电气连接部分,高压试验的工作票发出后,禁止再发出第二张工作票。
如加压部分与检修部分之间的断开点,按试验电压有足够的安全距离,并在另一侧有接 地短路线时,可在断开点的一侧进行试验,另一侧可继续工作。但此时在断开点应挂有“止 步,高压危险!”的标示牌,并设专人监护。
第 228 条 高压试验工作不得少于两人。试验负责人应由有经验的人员担任,开始试验 前,试验负责人应对全体试验人员详细布置试验中的安全注意事项。第 229 条 因试验需要断开设备接头时,拆前应做好标记,接后应进行检查。
第 230 条 试验装置的金属外壳应可靠接地;高压引线应尽量缩短,必要时用绝缘物支 持牢固。
试验装置的电源开关,应使用明显断开的双极刀闸。为了防止误合刀闸,可在刀刃上加 绝缘罩。
试验装置的低压回路中应有两个串联电源开关,并加装过载自动掉闸装置。
第 231 条 试验现场应装设遮栏或围栏,向外悬挂“止步,高压危险!”的标示牌,并派 人看守。被试设备两端不在同一地点时,另一端还应派人看守。
第 232 条 加压前必须认真检查试验结线,表计倍率、量程,调压器零位及仪表的开始 状态,均正确无误,通知有关人员离开被试设备,并取得试验负责人许可,方可加压。加压 过程中应有人监护并呼唱。
高压试验工作人员在全部加压过程中,应精力集中,不得与他人闲谈,随时警戒异常现 象发生,操作人应站在绝缘垫上。
第 233 条 变更结线或试验结束时,应首先断开试验电源,放电,并将升压设备的高压 部分短路接地。
第 234 条 未装地线的大电容被试设备,应先行放电再做试验。高压直流试验时,每告 一段落或试验结束时,应将设备对地放电数次并短路接地。
第 235 条 试验结束时,试验人员应拆除自装的接地短路线,并对被试设备进行检查和 清理现场。
第 236 条 特殊的重要电气试验,应有详细的试验措施,并经厂(局)主管生产的领导(总工程师)批准。
第二节 使用携带型仪器的测量工作
第 237 条 使用携带型仪器在高压回路上进行工作,需要高压设备停电或做安全措施的,应填用第一种工作票,并至少由两人进行。
第 238 条 除使用特殊仪器外,所有使用携带型仪器的测量工作,均应在电流互感器和 电压互感器的低压侧进行。
第 239 条 电流表、电流互感器及其他测量仪表的接线和拆卸,需要断开高压回路者,应将此回路所连接的设备和仪器全部停电后,始能进行。
第 240 条 电压表、携带型电压互感器和其他高压测量仪器的接线和拆卸无需断开高压 回路者,可以带电工作。但应使用耐高压的绝缘导线,导线长度应尽可能缩短,不准有接头,并应连接牢固,以防接地和短路。必要时用绝缘物加以固定。
使用电压互感器进行工作时,先应将低压侧所有接线接好,然后用绝缘工具将电压互感 器接到高压侧。工作时应带手套和护目眼镜,站在绝缘垫上,并应有专人监护。
第 241 条 连接电流回路的导线截面,应适合所测电流数值。连接电压回路的导线截面 不得小于 1.5mm 2。
第 242 条 非金属外壳的仪器,应与地绝缘,金属外壳的仪器和变压器外壳应接地。第 243 条 所有测量用装置均应设遮栏和围栏,并悬挂“止步,高压危险!”的标示牌。仪器的布置应使工作人员距带电部分不小于表 1 规定的安全距离。第三节 使用钳形电流表的测量工作
第 244 条 值班人员在高压回路上使用钳形电流表的测量工作,应由两人进行。非值班 人员测量时,应填第二种工作票。
第 245 条 在高压回路上测量时,严禁用导线从钳形电流表另接表计测量。
第 246 条 测量时若需拆除遮栏,应在拆除遮栏后立即进行。工作结束,应立即将遮栏 恢复原位。
第 247 条 使用钳形电流表时,应注意钳形电流表的电压等级。测量时戴绝缘手套,站 在绝缘垫上,不得触及其他设备,以防短路或接地。
观测表计时,要特别注意保持头部与带电部分的安全距离。
第 248 条 测量低压熔断器(保险)和水平排列低压母线电流时,测量前应将各相熔断 器(保险)和母线用绝缘材料加以包护隔离,以免引起相间短路,同时应注意不得触及其他 带电部分。
第 249 条 在测量高压电缆各相电流时,电缆头线间距离应在 300mm 以上,且绝缘良好,测量方便者,方可进行。当有一相接地时,严禁测量。
第 250 条 钳形电流表应保存在干燥的室内,使用前要擦拭干净。第四节 使用摇表测量绝缘的工作
第 251 条 使用摇表测量高压设备绝缘,应由两人担任。
第 252 条 测量用的导线,应使用绝缘导线,其端部应有绝缘套。
第 253 条 测量绝缘时,必须将被测设备从各方面断开,验明无电压,确实证明设备无 人工作后,方可进行。在测量中禁止他人接近设备。在测量绝缘前后,必须将被试设备对地放电。测量线路绝缘时,应取得对方允许后方可进行。
第 254 条 在有感应电压的线路上(同杆架设的双回线路或单回路与另一线路有平行 段)测量绝缘时,必须将另一回线路同时停电,方可进行。雷电时,严禁测量线路绝缘。
第 255 条 在带电设备附近测量绝缘电阻时,测量人员和摇表安放位置,必须选择适当,保持安全距离,以免摇表引线或引线支持物触碰带电部分。移动引线时,必须注意监护,防 止工作人员触电。
第十二章 电力电缆工作
第 256 条 电力电缆停电工作应填用第一种工作票,不需停电的工作应填用第二种工作 票。工作前必须详细核对电缆名称,标示牌是否与工作票所写的符合,安全措施正确可靠后,方可开始工作。
第 257 条 挖掘电缆工作,应由有经验人员交待清楚后才能进行。挖到电缆保护板后,应由有经验的人员在场指导,方可继续工作。
挖掘电缆沟前,应做好防止交通事故的安全措施。在挖出的土堆起的斜坡上,不得放置 工具、材料等杂物。沟边应留有走道。
第 258 条 挖掘出的电缆或接头盒,如下面需要挖空时,必须将其悬吊保护,悬吊电缆 应每隔约 1.0~1.5m 吊一道。悬吊接头盒应平放,不得使接头受到拉力。
第 259 条 敷设电缆时,应有专人统一指挥。电缆走动时,严禁用手搬动滑轮,以防压 伤。
移动电缆接头盒一般应停电进行。如带电移动时,应先调查该电缆的历史记录,由敷设 电缆有经验的人员,在专人统一指挥下,平正移动,防止绝缘损伤爆炸。
第 260 条 锯电缆以前,必须与电缆图纸核对是否相符,并确切证实电缆无电后,用接 地的带木柄的铁钎钉入电缆芯后,方可工作。扶木柄的人应戴绝缘手套并站在绝缘垫上。第 261 条 熬电缆胶工作应有专人看管。熬胶人员,应戴帆布手套及鞋盖。搅拌或掐取 溶化的电缆胶或焊锡时,必须使用预先加热的金属棒或金属勺子,防止落入水分而发生爆溅 烫伤。
第 262 条 进电缆井前,应排除井内浊气。电缆井内工作,应戴安全帽,并做好防火、防水及防止高空落物等措施,电缆井口应有专人看守。
第 263 条 水底电缆提起放在船上工作时,应使船体保持平衡。船上应具备足够的救生 圈,工作人员应穿救生衣。
第 264 条 制做环氧树脂电缆头和调配环氧树脂工作过程中,应采取有效的防毒和防火 措施。
第十三章 其他安全措施
第 265 条 使用携带型火炉或喷灯时,火焰与带电部分的距离:电压在 10kV 及以下者,不得小于 1.5m;电压在 10kV 以上者,不得小于 3m。不得在带电导线、带电设备、变压器、油开关附近将火炉或喷灯点火。
第 266 条 在屋外变电所和高压室内搬动梯子、管子等长物,应两人放倒搬运,并与带 电部分保持足够的安全距离。
第 267 条 工作地点应有充足的照明。
第 268 条 进入高空作业现场,应戴安全帽。高处作业人员必须使用安全带。高处工作传递物件,不得上下抛掷。
第 269 条 雷电时,禁止在室外变电所或室内的架空引入线上进行检修和试验。
第 270 条 遇有电气设备着火时,应立即将有关设备的电源切断,然后进行救火。对带 电设备应使用干式灭火器、二氧化碳灭火器等灭火,不得使用泡沫灭火器灭火。对注油设备 应使用泡沫灭火器或干燥的砂子等灭火。发电厂和变电所控制室内应备有防毒面具,防毒面 具要按规定使用并定期进行试验,使其经常处于良好状态。
第 271 条 在带电设备周围严禁使用钢卷尺、皮卷尺和线尺(夹有金属丝者)进行测 量工作。
第 272 条 在电容器组上或进入其围栏内工作时,应将电容器逐个多次放电并接地后,方可进行。附录一
倒闸操作票格式 附录二
第一种工作票格式 附录三
第二种工作票格式
发电厂(变电所)第二种工作票 编号: 1.工作负责人(监护人):_________________________班组__________________ 工作班人员:_________________________ 2.工作任务:___________________________________________________________ _______________________________________________________________________ 3.计划工作时间:自__________年_______月______日______时______分 至__________年_______月______日______时______分 4.工作条件(停电或不停电):
______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ 5.注意事项(安全措施):_________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ 工作票签发人签名:__________________ 6.许可开始工作时间:___________年________月_____日______时________分
工作许可人(值班员)签名:________________工作负责人签名:_______________ 7.工作结束时间:_______________年________月_____日_______时________分 工作负责人签名:_____________工作许可人(值班员)签名:_______________ 8.备注:_______________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ 附录四 标示牌式样 附录五
常用电气绝缘工具试验一览表 附录六
登高安全工具试验标准表 附录七 紧急救护法 1 通则
1.1 紧急救护的基本原则是在现场采取积极措施保护伤员生命,减轻伤情,减少痛苦,并根据伤情需要,迅速联系医疗部门救治。急救的成功条件是动作快,操作正确。任何拖延 和操作错误都会导致伤员伤情加重或死亡。
1.2 要认真观察伤员全身情况,防止伤情恶化。发现呼吸、心跳停止时,应立即在现场 就地抢救,用心肺复苏法支持呼吸和循环,对脑、心重要脏器供氧。应当记住只有在心脏停 止跳动后分秒必争地迅速抢救,救活的可能才较大。
1.3 现场工作人员都应定期进行培训,学会紧急救护法。会正确解脱电源、会心肺复苏 法、会止血、会包扎、会转移搬运伤员、会处理急救外伤或中毒等。
1.4 生产现场和经常有人工作的场所应配备急救箱,存放急救用品,并应指定专人经常 检查、补充或更换。2 触电急救
2.1 触电急救必须分秒必争,立即就地迅速用心肺复苏法进行抢救,并坚持不断地进行,同时及早与医疗部门联系,争取医务人员接替救治。在医务人员未接替救治前,不应放弃现 场抢救,更不能只根据没有呼吸或脉搏擅自判定伤员死亡,放弃抢救。只有医生有权做出伤 员死亡的诊断。2.2 脱离电源:
2.2.1 触电急救,首先要使触电者迅速脱离电源,越快越好。因为电流作用的时间越长,伤害越重。
2.2.2 脱离电源就是要把触电者接触的那一部分带电设备的开关、刀闸或其他断路设备 断开;或设法将触电者与带电设备脱离。在脱离电源中,救护人员既要救人,也要注意保护 自己。
2.2.3 触电者未脱离电源前,救护人员不准直接用手触及伤员,因为有触电的危险。2.2.4 如触电者处于高处,触脱电源后会自高处坠落,因此,要采取预防措施。
2.2.5 触电者触及低压带电设备,救护人员应设法迅速切断电源,如拉开电源开关或刀 闸,拔除电源插头等;或使用绝缘工具、干燥的木棒、木板、绳索等不导电的东西解脱触电 者;也可抓住触电者干燥而不贴身的衣服,将其拖开,切记要避免碰到金属物体和触电者的 裸露身躯;也可戴绝缘手套或将手用干燥衣物等包起绝缘后解脱触电者;救护人员也可站在 绝缘垫上或干木板上,绝缘自己进行救 护。为使触电者与导电体解脱,最好用一只手进行。
如果电流通过触电者入地,并且触电者紧握电线,可设法用干木板塞到身下,与地隔离,也可用干木把斧子或有绝缘柄的钳子等将电线剪断。剪断电线要分相,一根一根地剪断,并 尽可能站在绝缘物体或干木板上。
2.2.6 触电者触及高压带电设备,救护人员应迅速切断电源,或用适合该电压等级的绝 缘工具(戴绝缘手套、穿绝缘靴并用绝缘棒)解脱触电者。救护人员在抢救过程中应注意保 持自身与周围带电部分必要的安全距离。
2.2.7 如果触电发生在架空线杆塔上,如系低压带电线路,若可能立即切断线路电源的,应迅速切断电源,或者由救护人员迅速登杆,束好自己的安全皮带后,用带绝缘胶柄的钢丝 钳、干燥的不导电物体或绝缘物体将触电者拉离电源;如系高压带电线路,又不可能迅速切 断电源开关的,可采用抛挂足够截面的适当长度的金属短路线方法,使电源开关跳闸。抛挂 前,将短路线一端固定在铁塔或接地引下线上,另一端系重物,但抛掷短路线时,应注意防 止电弧伤人或断线危及人员安全。不论是何级电压线路上触电,救护人员在使触电者脱离电 源时要注意防止发生高处坠落的可能和再次触及其它有电线路的可能。
2.2.8 如果触电者触及断落在地上的带电高压导线,且尚未确证线路无电,救护人员在 未做好安全措施(如穿绝缘靴或临时双脚并紧跳跃地接近触电者)前,不能接近断线点至 8~ 10m 范围内,防止跨步电压伤人。触电者脱离带电导线后亦应迅速带至 8~10m 以外后立即
开始触电急救。只有在确证线路已经无电,才可在触电者离开触电导线后,立即就地进行急 救。
2.2.9 救护触电伤员切除电源时,有时会同时使照明失电,因此应考虑事故照明、应急 灯等临时照明。新的照明要符合使用场所防火、防爆的要求。但不能因此延误切除电源和进 行急救。
2.3 伤员脱离电源后的处理:
2.3.1 触电伤员如神志清醒者,应使其就地躺平,严密观察,暂时不要站立或走动。2.3.2 触电伤员如神志不清者,应就地仰面躺平,且确保气道通畅,并用 5s 时间,呼 叫伤员或轻拍其肩部,以判定伤员是否意识丧失。禁止摇动伤员头部呼叫伤员。2.3.3 需要抢救的伤员,应立即就地坚持正确抢救,并设法联系医疗部门接替救治。2.4 呼吸、心跳情况的判定:
2.4.1 触电伤员如意识丧失,应在 10s 内,用看、听、试的方法(见图 1),判定伤员 呼吸心跳情况。图 1 看、听、试
2.4.1.1 看—看伤员的胸部、腹部有无起伏动作;
2.4.1.2 听—用耳贴近伤员的口鼻处,听有无呼气声音;
2.4.1.3 试—试测口鼻有无呼气的气流。再用两手指轻试一侧(左或右)喉结旁凹陷处 的颈动脉有无搏动。
2.4.2 若看、听、试结果,既无呼吸又无颈动脉搏动,可判定呼吸心跳停止。2.5 心肺复苏法:
2.5.1 触电伤员呼吸和心跳均停止时,应立即按心肺复苏法支持生命的三项基本措施,正确进行就地抢救。a.通畅气道; b.口对口(鼻)人工呼吸; c.胸外按压(人工循环)。2.5.2 通畅气道:
2.5.2.1 触电伤员呼吸停止,重要的是始终确保气道通畅。如发现伤员口内有异物,可
将其身体及头部同时侧转,迅速用一个手指或用两手指交叉从口角处插入,取出异物;操作 中要注意防止将异物推到咽喉深部。
2.5.2.2 通畅气道可采用仰头抬颏法(见图 2)。用一只手放在触电者前额,另一只手 的手指将其下颌骨向上抬起,两手协同将头部推向后仰,舌根随之抬起,气道即可通畅(判 断气道是否通畅可参见图 3)。严禁用枕头或其它物品垫在伤员头下,头部抬高前倾,会更 加重气道阻塞,且使胸外按压时流向脑部的血流减少,甚至消失。图 2 仰头抬颏法 图 3 气道状况(a)气道通畅;(b)气道阻塞
2.5.3 口对口(鼻)人工呼吸(见图 4): 图 4 口对口人工呼吸
2.5.3.1 在保持伤员气道通畅的同时,救护人员用放在伤员额上的手的手指捏住伤员鼻
翼,救护人员深吸气后,与伤员口对口紧合,在不漏气的情况下,先连续大口吹气两次,每 次 1~1.5s。如两次吹气后试测颈动脉仍无搏动,可判断心跳已经停止,要立即同时进行胸 外按压。
2.5.3.2 除开始时大口吹气两次外,正常口对口(鼻)呼吸的吹气量不需过大,以免引
起胃膨胀。吹气和放松时要注意伤员胸部应有起伏的呼吸动作。吹气时如有较大阻力,可能 是头部后仰不够,应及时纠正。
2.5.3.3 触电伤员如牙关紧闭,可口对鼻人工呼吸。口对鼻人工呼吸吹气时,要将伤员 嘴唇紧闭,防止漏气。2.5.4 胸外按压:
2.5.4.1 正确的按压位置是保证胸外按压效果的重要前提。确定正确按压位置的步骤: a.右手的食指和中指沿触电伤员的右侧肋弓下缘向上,找到肋骨和胸骨接合处的中点; b.两手指并齐,中指放在切迹中点(剑突底部),食指平放在胸骨下部;
c.另一只手的掌根紧挨食指上缘,置于胸骨上,即为正确按压位置(见图 5)。图 5 正确的按压位置
2.5.4.2 正确的按压姿势是达到胸外按压效果的基本保证。正确的按压姿势:
a.使触电伤员仰面躺在平硬的地方,救护人员立或跪在伤员一侧肩旁,救护人员的两肩 位于伤员胸骨正上方,两臂伸直,肘关节固定不屈,两手掌根相叠,手指翘起,不接触伤员 胸壁;
b.以髋关节为支点,利用上身的重力,垂直将正常成人胸骨压陷 3~5cm(儿童和瘦弱 者酌减);
c.压至要求程度后,立即全部放松,但放松时救护人员的掌根不得离开胸壁(见图 6)。按压必须有效,有效的标志是按压过程中可以触及颈动脉搏动。图 6 按压姿势与用力方法 2.5.4.3 操作频率:
a.胸外按压要以均匀速度进行,每分钟 80 次左右,每次按压和放松的时间相等;
b.胸外按压与口对口(鼻)人工呼吸同时进行,其节奏为:单人抢救时,每按压 15 次 后吹气 2 次(15∶2),反复进行;双人抢救时,每按压 5 次后由另一人吹气 1 次(5∶1),反复进行。2.6 抢救过程中的再判定:
2.6.1 按压吹气 1min 后(相当于单人抢救时做了 4 个 15∶2 压吹循环),应用看、听、试方法在 5~7s 时间内完成对伤员呼吸和心跳是否恢复的再判定。
2.6.2 若判定颈动脉已有搏动但无呼吸,则暂停胸外按压,而再进行 2 次口对口人工呼 吸,接着每 5s 吹气一次(即每分钟 12 次)。如脉搏和呼吸均未恢复,则继续坚持心肺复苏
法抢救。
2.6.3 在抢救过程中,要每隔数分钟再判定一次,每次判定时间均不得超过 5~7s。在 医务人员未接替抢救前,现场抢救人员不得放弃现场抢救。2.7 抢救过程中伤员的移动与转院(见图 7): 图 7 搬运伤员(a)正常担架;(b)临时担架及木板;(c)错误搬运
2.7.1 心肺复苏应在现场就地坚持进行,不要为方便而随意移动伤员,如确有需要移动 时,抢救中断时间不应超过 30s。
2.7.2 移动伤员或将伤员送医院时,除应使伤员平躺在担架上并在其背部垫以平硬阔木 板,移动或送医院过程中应继续抢救,心跳呼吸停止者要继续心肺复苏法抢救,在医务人员 未接替救治前不能中止。
2.7.3 应创造条件,用塑料袋装入砸碎冰屑作成帽状包绕在伤员头部,露出眼睛,使脑 部温度降低,争取心肺脑完全复苏。2.8 伤员好转后的处理:
如伤员的心跳和呼吸经抢救后均已恢复,可暂停心肺复苏法操作。但心跳呼吸恢复的早 期有可能再次骤停,应严密监护,不能麻痹,要随时准备再次抢救。初期恢复后,神志不清或精神恍惚、躁动,应设法使伤员安静。2.9 杆上或高处触电急救:
2.9.1 发现杆上或高处有人触电,应争取时间及早在杆上或高处开始进行抢救。救护人 员登高时应随身携带必要的工具和绝缘工具以及牢固的绳索等,并紧急呼 救。
2.9.2 救护人员应在确认触电者已与电源隔离,且救护人员本身所涉环境安全距离内无 危险电源时,方能接触伤员进行抢救,并应注意防止发生高空坠落的可能性。2.9.3 高处抢救:
2.9.3.1 触电伤员脱离电源后,应将伤员扶卧在自己的安全带上(或在适当地方躺平),并注意保持伤员气道通畅。
2.9.3.2 救护人员迅速按 2.3 和 2.4 条规定判定反应、呼吸和循环情况。
2.9.3.3 如伤员呼吸停止,立即口对口(鼻)吹气 2 次,再测试颈动脉,如有搏动,则 每 5s 继续吹气一次,如颈动脉无搏动时,可用空心拳头叩击心前区 2 次,促使心脏复跳。2.9.3.4 高处发生触电,为使抢救更为有效,应及早设法将伤员送至地面。在完成上述
措施后,应立即用绳索参照图 8 所示方法迅速将伤员送至地面,或采取可能的迅速有效措施
送至平台上。
图 8 杆上或高处触电下放方法
2.9.3.5 在将伤员由高处送至地面前,应再口对口(鼻)吹气 4 次。2.9.3.6 触电伤员送至地面后,应立即继续按心肺复苏法坚持抢救。
2.10 现场触电抢救,对采用肾上腺素等药物应持慎重态度。如没有必要的诊断设备条
件和足够的把握,不得乱用。在医院内抢救触电者时,由医务人员经医疗仪器设备诊断,根 据诊断结果决定是否采用。3 创伤急救
3.1 创伤急救的基本要求。
3.1.1 创伤急救原则上是先抢救,后固定,再搬运,并注意采取措施,防止伤情加重或 污染。需要送医院救治的,应立即做好保护伤员措施后送医院救治。
3.1.2 抢救前先使伤员安静躺平,判断全身情况和受伤程度,如有无出血、骨折和休克 等。
3.1.3 外部出血立即采取止血措施,防止失血过多而休克。外观无伤,但呈休克状态,神志不清,或昏迷者,要考虑胸腹部内脏或脑部受伤的可能性。
3.1.4 为防止伤口感染,应用清洁布片覆盖。救护人员不得用手直接接触伤口,更不得 在伤口内填塞任何东西或随便用药。
3.1.5 搬运时应使伤员平躺在担架上,腰部束在担架上,防止跌下。平地搬运时伤员头 部在后,上楼、下楼、下坡时头部在上,搬运中应严密观察伤员,防止伤情突变。3.2 止血
3.2.1 伤口渗血:
用较伤口稍大的消毒纱布数层覆盖伤口,然后进行包扎。若包扎后仍有较多渗血,可 再加绷带适当加压止血。
3.2.2 伤口出血呈喷射状或鲜红血液涌出时,立即用清洁手指压迫出血点上方(近心 端),使血流中断,并将出血肢体抬高或举高,以减少出血量。3.2.3 用止血带或弹性较好的布带等止血时(图 9),应先用柔软布片或伤员的衣袖等
数层垫在止血带下面,再扎紧止血带以刚使肢端动脉搏动消失为度。上肢每 60min,下肢每
80min 放松一次,每次放松 1~2min。开始扎紧与每次放松的时间均应书面标明在止血带旁。
扎紧时间不宜超过 4h。不要在上臂中三分之一处和窝下使用止血带,以免损伤神经。若 放松时观察已无大出血可暂停使用。
严禁用电线、铁丝、细绳等作止血带使用。图 9 止血带
3.2.4 高处坠落、撞击、挤压可能有胸腹内脏破裂出血。受伤者外观无出血但常表现面 色苍白,脉搏细弱,气促,冷汗淋漓,四肢厥冷,烦躁不安,甚至神志不清等休克状态,应 迅速躺平,抬高下肢(图 10),保持温暖,速送医院救治。若送院途中时间较长,可给伤 员饮用少量糖盐水。图 10 抬高下肢 3.3 骨折急救
3.3.1 肢体骨折可用夹板或木棍、竹竿等将断骨上、下方两个关节固定(图 11),也 可利用伤员身体进行固定,避免骨折部位移动,以减少疼痛,防止伤势恶化。图 11 骨折固定方法(a)上肢骨折固定;(b)下肢骨折固定
开放性骨折,伴有大出血者,先止血,再固定,并用干净布片覆盖伤口,然后速送医院 救治。切勿将外露的断骨推回伤口内。
3.3.2 疑有颈椎损伤,在使伤员平卧后,用沙土袋(或其它代替物)放置头部两侧(图 12)使颈部固定不动。必须进行口对口呼吸时,只能采用抬颏使气道通畅,不能再将头部后 仰移动或转动头部,以免引起截瘫或死亡。图 12 颈椎骨折固定
3.3.3 腰椎骨折应将伤员平卧在平硬木板上,并将腰椎躯干及二侧下肢一同进行固定预 防瘫痪(图 13)。搬动时应数人合作,保持平稳,不能扭曲。图 13 腰椎骨折固定 3.4 颅脑外伤
3.4.1 应使伤员采取平卧位,保持气道通畅,若有呕吐,应扶好头部和身体,使头部和 身体同时侧转,防止呕吐物造成窒息。
3.4.2 耳鼻有液体流出时,不要用棉花堵塞,只可轻轻拭去,以利降低颅内压力。也不 可用力擤鼻,排除鼻内液体,或将液体再吸入鼻内。
3.4.3 颅脑外伤时,病情可能复杂多变,禁止给予饮食,速送医院诊治。3.5 烧伤急救
3.5.1 电灼伤、火焰烧伤或高温气、水烫伤均应保持伤口清洁。伤员的衣服鞋袜用剪刀 剪开后除去。伤口全部用清洁布片覆盖,防止污染。四肢烧伤时,先用清洁冷水冲洗,然后 用清洁布片或消毒纱布覆盖送医院。
3.5.2 强酸或碱灼伤应立即用大量清水彻底冲洗,迅速将被侵蚀的衣物剪去。为防止酸、碱残留在伤口内,冲洗时间一般不少于 10min。
3.5.3 未经医务人员同意,灼伤部位不宜敷搽任何东西和药物。3.5.4 送医院途中,可给伤员多次少量口服糖盐水。3.6 冻伤急救
3.6.1 冻伤使肌肉僵直,严重者深及骨骼,在救护搬运过程中动作要轻柔,不要强使其 肢体弯曲活动,以免加重损伤,应使用担架,将伤员平卧并抬至温暖室内救治。3.6.2 将伤员身上潮湿的衣服剪去后用干燥柔软的衣服覆盖,不得烤火或搓雪。3.6.3 全身冻伤者呼吸和心跳有时十分微弱,不应误认为死亡,应努力抢救。3.7 动物咬伤急救
3.7.1 毒蛇咬伤后,不要惊慌、奔跑、饮酒,以免加速蛇毒在人体内扩散。
3.7.1.1 咬伤大多在四肢,应迅速从伤口上端向下方反复挤出毒液,然后在伤口上方(近心端)用布带扎紧,将伤肢固定,避免活动,以减少毒液的吸收。3.7.1.2 有蛇药时可先服用,再送往医院救治。3.7.2 犬咬伤
3.7.2.1 犬咬伤后应立即用浓肥皂水冲洗伤口,同时用挤压法自上而下将残留伤口内唾 液挤出,然后再用碘酒涂搽伤口。
3.7.2.2 少量出血时,不要急于止血,也不要包扎或缝合伤口。3.7.2.3 尽量设法查明该犬是否为“疯狗”,对医院制订治疗计划有较大帮助。3.8 溺水急救
3.8.1 发现有人溺水应设法迅速将其从水中救出,呼吸心跳停止者用心肺复苏法坚持抢 救。曾受水中抢救训练者在水中即可抢救。
3.8.2 口对口人工呼吸因异物阻塞发生困难,而又无法用手指除去时,可用两手相叠,置于脐部稍上正中线上(远离剑突)迅速向上猛压数次,使异物退出,但也不可用力太大。3.8.3 溺水死亡的主要原因是窒息缺氧。由于淡水在人体内能很快经循环吸收,而气管
能容纳的水量很少,因此在抢救溺水者时不应“倒水”而延误抢救时间,更不应仅“倒水” 而不用心肺复苏法进行抢救。3.9 高温中暑急救
3.9.1 烈日直射头部,环境温度过高,饮水过少或出汗过多等可以引起中暑现象,其症 状一般为恶心、呕吐、胸闷、眩晕、嗜睡、虚脱,严重时抽搐、惊厥甚至昏迷。
3.9.2 应立即将病员从高温或日晒环境转移到阴凉通风处休息。用冷水擦浴,湿毛巾覆 盖身体,电扇吹风,或在头部置冰袋等方法降温,并及时给病人口服盐水。严重者送医院治 疗。
3.10 有害气体中毒急救
3.10.1 气体中毒开始时有流泪、眼痛、呛咳、咽部干燥等症状,应引起警惕。稍重时 头痛、气促、胸闷、眩晕。严重时会引起惊厥昏迷。
3.10.2 怀疑可能存在有害气体时,应即将人员撤离现场,转移到通风良好处休息。抢 救人员进入险区必须带防毒面具。
3.10.3 已昏迷病员应保持气道通畅,有条件时给予氧气吸入。呼吸心跳停止者,按心 肺复苏法抢救,并联系医院救治。
3.10.4 迅速查明有害气体的名称,供医院及早对症治疗。附录八
SF6 新气质量暂行标准 附加说明:
本标准由能源部安全环保司提出。本标准由能源部安全环保司归口。
本标准由能源部安全环保司负责起草,全国有关电管局、电力局等参加。本标准主要起草人:徐余文、蔡树人、陈祖嘉、陈其祥、柏克寒。
第三篇:电业安全工作规程(发电厂和变电所电气部分)
中华人民共和国行业标准
电业安全工作规程
DL 408—91
(发电厂和变电所电气部分)
能源部 1991-3-18批准 1991-09-01 实施 总则
1.1 为了切实保证职工在生产中的安全和健康、电力系统、发供配电设备的安全运 行,结合电力生产多年来的实践经验,制定本规程。
各单位的领导干部和电气工作人员,必须严格执行本规程。
1.2 安全生产,人人有责。各级领导必须以身作则,要充分发动群众,依靠群众; 要发挥安全监察机构和群众性的安全组织的作用,严格监督本规程的贯彻执行。
1.3 本规程适用于运用中的发、变、送、配、农电和用户电气设备上工作的一切人 员(包括基建安装人员)。
各单位可根据现场情况制定补充条文,经厂(局)主管生产的领导(总工程师)批 准后执行。
所谓运用中的电气设备,系指全部带有电压或一部分带有电压及一经操作即带 有电压的电气设备。
1.4 电气设备分为高压和低压两种:
高压:设备对地电压在250V以上者:
低压:设备对地电压在250V及以下者。
1.5 电气工作人员必须具备下列条件:
1.5.1 经医师鉴定,无妨碍工作的病症(体格检查约两年一次)。
1.5.2 具备必要的电气知识,且按其职务和工作性质,熟悉《电业安全工作规程》(发电厂和变电所电气部分、电力线路部分、热力和机械部分)的有关部分,并经考 试合格。
1.5.3 学会紧急救护法(附录G),特别要学会触电急救。
1.6 电气工作人员对本规程应每年考试一次。因故间断电气工作连续三个月以上 者,必须重新温习本规程,并经考试合格后,方能恢复工作。
参加带电作业人员,应经专门培训,并经考试合格、领导批准后,方能参加工 作。
新参加电气工作的人员、实习人员和临时参加劳动的人员(干部、临时工等),必须经过安全知识教育后,方可下现场随同参加指定的工作,但不得单独工作。
对外单位派来支援的电气工作人员,工作前应介绍现场电气设备接线情况和有 关安全措施。
1.7 任何工作人员发现有违反本规程,并足以危及人身和设备安全者,应立即制 止。
1.8 对认真遵守本规程者,应给予表扬和奖励。对违反本规程者,应认真分析,加 强教育,分别情况,严肃处理。对造成严重事故者,应按情节轻重,予以行政或刑 事处分。
1.9 本规程所指的安全用具必须符合附录E、附录F的要求。高压设备工作的基本要求 2.1 发电厂和变电所的值班工作
2.1.1 值班人员必须熟悉电气设备。单独值班人员或值班负责人还应有实际工作经 验。
表1 设备不停电时的安全距离
2.1.2 高压设备符合下列条件者,可由单人值班:
a.室内高压设备的隔离室设有遮栏,遮栏的高度在1.7m以上,安装牢固并加锁 者;
b.室内高压开关的操作机构用墙或金属板与该开关隔离,或装有远方操作机构 者。
单人值班不得单独从事修理工作。
2.1.3 不论高压设备带电与否,值班人员不得单独移开或越过遮栏进行工作;若有 必要移开遮栏时,必须有监护人在场,并符合表1的安全距离。
2.2 高压设备的巡视
2.2.1 经企业领导批准允许单独巡视高压设备的值班员和非值班员,巡视高压设备 时,不得进行其他工作,不得移开或越过遮栏。
2.2.2 雷雨天气,需要巡视室外高压设备时,应穿绝缘靴,并不得靠近避雷器和避 雷针。
2.2.3 高压设备发生接地时,室内不得接近故障点4m以内,室外不得接近故障点 8m以内。进入上述范围人员必须穿绝缘靴,接触设备的外壳和架构时,应戴绝缘 手套。2.2.4 巡视配电装置,进出高压室,必须随手将门锁好。
2.2.5 高压室的钥匙至少应有三把,由配电值班人员负责保管,按值移交。一把专 供紧急时使用,一把专供值班员使用,其他可以借给许可单独巡视高压设备的人员和 工作负责人使用,但必须登记签名,当日交回。
2.3 倒闸操作
2.3.1 倒闸操作必须根据值班调度员或值班负责人命令,受令人复诵无误后执行。发布命令应准确、清晰、使用正规操作术语和设备双重名称,即设备名称和编 号。发令人使用电话发布命令前,应先和受令人互报姓名。值班调度员发布命令的 全过程(包括对方复诵命令)和听取命令的报告时,都要录音并作好记录。倒闸操 作由操作人填写操作票(见附录A)。单人值班,操作票由发令人用电话向值班员传 达,值班员应根据传达,填写操作票,复诵无误,并在“监护人”签名处填入发 令人的姓名。
每张操作票只能填写一个操作任务。
2.3.2 停电拉闸操作必须按照断路器(开关)——负荷侧隔离开关(刀闸)——母线侧 隔离开关(刀闸)的顺序依次操作,送电合闸操作应按与上述相反的顺序进行。严防 带负荷拉合刀闸。
为防止误操作,高压电气设备都应加装防误操作的闭锁装置(少数特殊情况下 经上级主管部门批准,可加机械锁)。闭锁装置的解锁用具(包括钥匙)应妥善保管,按规定使用,不许乱用。机械锁要一把钥匙开一把锁,钥匙要编号并妥善保管,方 便使用。所有投运的闭锁装置(包括机械锁)不经值班调度员或值长同意不得退出或 解锁。
2.3.3 下列项目应填入操作票内:
应拉合的断路器(开关)和隔离开关(刀闸),检查断路器(开关)和隔离开关(刀闸)的位置,检查接地线是否拆除,检查负荷分配,装拆接地线,安装或拆除控制回路 或电压互感器回路的熔断器(保险),切换保护回路和检验是否确无电压等。
操作票应填写设备的双重名称,即设备名称和编号。
2.3.4 操作票应用钢笔或圆珠笔填写,票面应清楚整洁,不得任意涂改。操作人和 监护人应根据模拟图板或接线图核对所填写的操作项目,并分别签名,然后经值班负 责人审核签名。特别重要和复杂的操作还应由值长审核签名。
2.3.5 开始操作前,应先在模拟图板上进行核对性模拟预演,无误后,再进行设备 操作。操作前应核对设备名称、编号和位置,操作中应认真执行监护复诵制。发布操 作命令和复诵操作命令都应严肃认真,声音宏亮清晰。必须按操作票填写的顺序逐 项操作。每操作完一项,应检查无误后做一个“√”记号,全部操作完毕后进行复 查。
2.3.6 倒闸操作必须由两人执行,其中一人对设备较为熟悉者作监护。单人值班的 变电所倒闸操作可由一人执行。
特别重要和复杂的倒闸操作,由熟练的值班员操作,值班负责人或值长监护。
2.3.7 操作中发生疑问时,应立即停止操作并向值班调度员或值班负责人报告,弄 清问题后,再进行操作。不准擅自更改操作票,不准随意解除闭锁装置。
2.3.8 用绝缘棒拉合隔离开关(刀闸)或经传动机构拉合隔离开关(刀闸)和断路器(开 关),均应戴绝缘手套。雨天操作室外高压设备时,绝缘棒应有防雨罩,还应穿绝 缘靴。接地网电阻不符合要求的,晴天也应穿绝缘靴。雷电时,禁止进行倒闸操 作。
2.3.9 装卸高压熔断器(保险),应戴护目眼镜和绝缘手套,必要时使用绝缘夹钳,并 站在绝缘垫或绝缘台上。
2.3.10 断路器(开关)遮断容量应满足电网要求。如遮断容量不够,必须将操作机构 用墙或金属板与该断路器(开关)隔开,并设远方控制,重合闸装置必须停用。
2.3.11 电气设备停电后,即使是事故停电,在未拉开有关隔离开关(刀闸)和做好安 全措施以前,不得触及设备或进入遮栏,以防突然来电。
2.3.12 在发生人身触电事故时,为了解救触电人,可以不经许可,即行断开有关设 备的电源,但事后必须立即报告上级。
2.3.13 下列各项工作可以不用操作票:
a.事故处理;
b.拉合断路器(开关)的单一操作;
c.拉开接地刀闸或拆除全厂(所)仅有的一组接地线。
上述操作应记入操作记录簿内。
2.3.14 操作票应先编号,按照编号顺序使用。作废的操作票,应注明“作废”字样,已操作的注明“已执行”的字样。上述操作票保存三个月。
2.4 高压设备上工作的安全措施分类
2.4.1 在运用中的高压设备上工作,分为三类:
2.4.1.1 全部停电的工作,系指室内高压设备全部停电(包括架空线路与电缆引入线 在内),通至邻接高压室的门全部闭锁,以及室外高压设备全部停电(包括架空线路 与电缆引入线在内)。
2.4.1.2 部分停电的工作,系指高压设备部分停电,或室内虽全部停电,而通至邻 接高压室的门并未全部闭锁。
2.4.1.3 不停电工作系指:
a.工作本身不需要停电和没有偶然触及导电部分的危险者;
b.许可在带电设备外壳上或导电部分上进行的工作。
2.4.2 在高压设备上工作,必须遵守下列各项:
a.填用工作票或口头、电话命令;
b.至少应有两人在一起工作;
c.完成保证工作人员安全的组织措施和技术措施。保证安全的组织措施
3.1 在电气设备上工作,保证安全的组织措施
a.工作票制度;
b.工作许可制度;
c.工作监护制度;
d.工作间断、转移和终结制度。
3.2 工作票制度
3.2.1 在电气设备上工作,应填用工作票或按命令执行,其方式有下列三种:
a.填用第一种工作票(见附录B);
b.填用第二种工作票(见附录C);
c.口头或电话命令。3.2.2 填用第一种工作票的工作为:
a.高压设备上工作需要全部停电或部分停电者;
b.高压室内的二次接线和照明等回路上的工作,需要将高压设备停电或做安全 措施者。
3.2.3 填用第二种工作票的工作为:
a.带电作业和在带电设备外壳上的工作;
b.控制盘和低压配电盘、配电箱、电源干线上的工作;
c.二次接线回路上的工作,无需将高压设备停电者;
d.转动中的发电机、同期调相机的励磁回路或高压电动机转子电阻回路上的工 作;
e.非当值值班人员用绝缘棒和电压互感器定相或用钳形电流表测量高压回路的 电流。
3.2.4 其他工作用口头或电话命令。
口头或电话命令,必须清楚正确,值班员应将发令人、负责人及工作任务详细 记入操作记录簿中,并向发令人复诵核对一遍。
3.2.5 工作票要用钢笔或圆珠笔填写一式两份,应正确清楚,不得任意涂改,如有 个别错、漏字需要修改时,应字迹清楚。
两份工作票中的一份必须经常保存在工作地点,由工作负责人收执,另一份由 值班员收执,按值移交。值班员应将工作票号码、工作任务、许可工作时间及完工 时间记入操作记录簿中。
在无人值班的设备上工作时,第二份工作票由工作许可人收执。
3.2.6 一个工作负责人只能发给一张工作票。工作票上所列的工作地点,以一个电 气连接部分为限。
如施工设备属于同一电压、位于同一楼层、同时停送电,且不会触及带电导体 时,则允许在几个电气连接部分共用一张工作票。
开工前工作票内的全部安全措施应一次做完。
建筑工、油漆工等非电气人员进行工作时,工作票发给监护人。
3.2.7 在几个电气连接部分上依次进行不停电的同一类型的工作,可以发给一张第 二种工作票。
3.2.8 若一个电气连接部分或一个配电装置全部停电,则所有不同地点的工作,可 以发给一张工作票,但要详细填明主要工作内容。几个班同时进行工作时,工作票 可发给一个总的负责人,在工作班成员栏内只填明各班的负责人,不必填写全部工 作人员名单。
若至预定时间,一部分工作尚未完成,仍须继续工作而不妨碍送电者,在送电 前,应按照送电后现场设备带电情况,办理新的工作票,布置好安全措施后,方可 继续工作。
3.2.9 事故抢修工作可不用工作票,但应记入操作记录簿内,在开始工作前必须按 本规程第4章的规定做好安全措施,并应指定专人负责监护。
3.2.10 线路、用户检修班或基建施工单位在发电厂或变电所进行工作时,必须由所 在单位(发电厂、变电所或工区)签发工作票并履行工作许可手续。
3.2.11 第一种工作票应在工作前一日交给值班员。临时工作可在工作开始以前直接 交给值班员。
第二种工作票应在进行工作的当天预先交给值班员。
3.2.12 若变电所距离工区较远或因故更换新工作票不能在工作前一日将工作票送 到,工作票签发人可根据自己填好的工作票用电话全文传达给变电所值班员,传达 必须清楚,值班员应根据传达做好记录,并复诵核对。若电话联系有困难,也可在 进行工作的当天预先将工作票交给值班员。
3.2.13 第一、二种工作票的有效时间,以批准的检修期为限。第一种工作票至预定 时间,工作尚未完成,应由工作负责人办理延期手续。延期手续应由工作负责人向 值班负责人申请办理,主要设备检修延期要通过值长办理。工作票有破损不能继续 使用时,应补填新的工作票。
3.2.14 需要变更工作班中的成员时,须经工作负责人同意。需要变更工作负责人 时,应由工作票签发人将变动情况记录在工作票上。若扩大工作任务,必须由工作 负责人通过工作许可人,并在工作票上增填工作项目。若须变更或增设安全措施 者,必须填用新的工作票,并重新履行工作许可手续。
3.2.15 工作票签发人不得兼任该项工作的工作负责人。工作负责人可以填写工作 票。
工作许可人不得签发工作票。
3.2.16 工作票签发人应由分场、工区(所)熟悉人员技术水平、熟悉设备情况、熟悉 本规程的生产领导人、技术人员或经厂、局主管生产领导批准的人员担任。工作票签 发人员名单应书面公布。
工作负责人和允许办理工作票的值班员(工作许可人)应由分场或工区主管生产 的领导书面批准。
3.2.17 工作票中所列人员的安全责任:
3.2.17.1 工作票签发人:
a.工作必要性;
b.工作是否安全;
c.工作票上所填安全措施是否正确完备;
d.所派工作负责人和工作班人员是否适当和足够,精神状态是否良好。
3.2.17.2 工作负责人(监护人):
a.正确安全地组织工作;
b.结合实际进行安全思想教育;
c.督促、监护工作人员遵守本规程;
d.负责检查工作票所载安全措施是否正确完备和值班员所做的安全措施是否 符合现场实际条件;
e.工作前对工作人员交待安全事项;
f.工作班人员变动是否合适。
3.2.17.3 工作许可人:
a.负责审查工作票所列安全措施是否正确完备,是否符合现场条件;
b.工作现场布置的安全措施是否完善;
c.负责检查停电设备有无突然来电的危险;
d.对工作票中所列内容即使发生很小疑问,也必须向工作票签发人询问清楚,必要时应要求作详细补充。
3.2.17.4 值长:
负责审查工作的必要性和检修工期是否与批准期限相符以及工作票所列安全 措施是否正确完备。
3.2.17.5 工作班成员:
认真执行本规程和现场安全措施,互相关心施工安全,并监督本规程和现场安 全措施的实施。
3.3 工作许可制度
3.3.1 工作许可人(值班员)在完成施工现场的安全措施后,还应:
a.会同工作负责人到现场再次检查所做的安全措施,以手触试,证明检修设备 确无电压;
b.对工作负责人指明带电设备的位置和注意事项;
c.和工作负责人在工作票上分别签名。
完成上述许可手续后,工作班方可开始工作。
3.3.2 工作负责人、工作许可人任何一方不得擅自变更安全措施,值班人员不得变 更有关检修设备的运行接线方式。工作中如有特殊情况需要变更时,应事先取得对 方的同意。
3.4 工作监护制度
3.4.1 完成工作许可手续后,工作负责人(监护人)应向工作班人员交待现场安全措 施、带电部位和其他注意事项。工作负责人(监护人)必须始终在工作现场,对工作 班人员的安全认真监护,及时纠正违反安全的动作。
3.4.2 所有工作人员(包括工作负责人),不许单独留在高压室内和室外变电所高压设 备区内。
若工作需要(如测量极性、回路导通试验等),且现场设备具体情况允许时,可 以准许工作班中有实际经验的一人或几人同时在他室进行工作,但工作负责人应在事 前将有关安全注意事项予以详尽的指示。
3.4.3 工作负责人(监护人)在全部停电时,可以参加工作班工作。在部分停电时,只 有在安全措施可靠,人员集中在一个工作地点,不致误碰导电部分的情况下,方能 参加工作。
工作票签发人或工作负责人,应根据现场的安全条件、施工范围、工作需要等 具体情况,增设专人监护和批准被监护的人数。
专责监护人不得兼做其他工作。
3.4.4 工作期间,工作负责人若因故必须离开工作地点时,应指定能胜任的人员临 时代替,离开前应将工作现场交待清楚,并告知工作班人员。原工作负责人返回工 作地点时,也应履行同样的交接手续。
若工作负责人需要长时间离开现场,应由原工作票签发人变更新工作负责人,两工作负责人应做好必要的交接。
3.4.5 值班员如发现工作人员违反安全规程或任何危及工作人员安全的情况,应向 工作负责人提出改正意见,必要时可暂时停止工作,并立即报告上级。
3.5 工作间断、转移和终结制度
3.5.1 工作间断时,工作班人员应从工作现场撤出,所有安全措施保持不动,工作 票仍由工作负责人执存。间断后继续工作,无需通过工作许可人。每日收工,应清扫 工作地点,开放已封闭的通路,并将工作票交回值班员。次日复工时,应得值班员 许可,取回工作票,工作负责人必须事前重新认真检查安全措施是否符合工作票的 要求后,方可工作。若无工作负责人或监护人带领,工作人员不得进入工作地点。
3.5.2 在未办理工作票终结手续以前,值班员不准将施工设备合闸送电。
在工作间断期间,若有紧急需要,值班员可在工作票未交回的情况下合闸送 电,但应先将工作班全班人员已经离开工作地点的确切根据通知工作负责人或电气 分场负责人,在得到他们可以送电的答复后方可执行,并应采取下列措施:
a.拆除临时遮栏、接地线和标示牌,恢复常设遮栏,换挂“止步,高压危险!” 的标示牌;
b.必须在所有通路派专人守候,以便告诉工作班人员“设备已经合闸送电,不 得继续工作”,守候人员在工作票未交回以前,不得离开守候地点。
3.5.3 检修工作结束以前,若需将设备试加工作电压,可按下列条件进行:
a.全体工作人员撤离工作地点;
b.将该系统的所有工作票收回,拆除临时遮栏、接地线和标示牌,恢复常设遮 栏;
c.应在工作负责人和值班员进行全面检查无误后,由值班员进行加压试验。
工作班若需继续工作时,应重新履行工作许可手续。
3.5.4 在同一电气连接部分用同一工作票依次在几个工作地点转移工作时,全部安 全措施由值班员在开工前一次做完,不需再办理转移手续,但工作负责人在转移工 作地点时,应向工作人员交待带电范围、安全措施和注意事项。
3.5.5 全部工作完毕后,工作班应清扫、整理现场。工作负责人应先周密的检查,待全体工作人员撤离工作地点后,再向值班人员讲清所修项目、发现的问题、试验结 果和存在问题等,并与值班人员共同检查设备状况,有无遗留物件,是否清洁等,然后在工作票上填明工作终结时间,经双方签名后,工作票方告终结。
3.5.6 只有在同一停电系统的所有工作票结束,拆除所有接地线、临时遮栏和标示 牌,恢复常设遮栏,并得到值班调度员或值班负责人的许可命令后,方可合闸送 电。
3.5.7 已结束的工作票,保存三个月。保证安全的技术措施
表2 工作人员工作中正常活动范围与带电设备 的安全距离
4.1 在全部停电或部分停电的电气设备上工作,必须完成下列措施:
a.停电;
b.验电;
c.装设接地线;
d.悬挂标示牌和装设遮栏。
上述措施由值班员执行。对于无经常值班人员的电气设备,由断开电源人执 行,并应有监护人在场[两线一地制系统验电、装设接地线措施,由局(厂)自行规 定]。
4.2 停电
4.2.1 工作地点,必须停电的设备如下:
a.检修的设备;
b.与工作人员在进行工作中正常活动范围的距离小于表2规定的设备;
c.在44kV以下的设备上进行工作,上述安全距离虽大于表2规定,但小于表1 规定,同时又无安全遮栏措施的设备;
d.带电部分在工作人员后面或两侧无可靠安全措施的设备。
4.2.2 将检修设备停电,必须把各方面的电源完全断开(任何运用中的星形接线设备 的中性点,必须视为带电设备)。禁止在只经断路器(开关)断开电源的设备上工作。必须拉开隔离开关(刀闸),使各方面至少有一个明显的断开点。与停电设备有关的 变压器和电压互感器,必须从高、低压两侧断开,防止向停电检修设备反送电。
4.2.3 断开断路器(开关)和隔离开关(刀闸)的操作能源。隔离开关(刀闸)操作把手必 须锁住。
4.3 验电
4.3.1 验电时,必须用电压等级合适而且合格的验电器,在检修设备进出线两侧各 相分别验电。验电前,应先在有电设备上进行试验,确证验电器良好。如果在木杆、木梯或木架构上验电,不接地线不能指示者,可在验电器上接地线,但必须经值班 负责人许可。
4.3.2 高压验电必须戴绝缘手套。验电时应使用相应电压等级的专用验电器。
330kV及以上的电气设备,在没有相应电压等级的专用验电器的情况下,可使 用绝缘棒代替验电器,根据绝缘棒端有无火花和放电噼啪声来判断有无电压。
4.3.3 表示设备断开和允许进入间隔的信号、经常接入的电压表等,不得作为设备 无电压的根据。但如果指示有电,则禁止在该设备上工作。
4.4 装设接地线
4.4.1 当验明设备确已无电压后,应立即将检修设备接地并三相短路。这是保护工 作人员在工作地点防止突然来电的可靠安全措施,同时设备断开部分的剩余电荷,亦可因接地而放尽。
4.4.2 对于可能送电至停电设备的各方面或停电设备可能产生感应电压的都要装设 接地线,所装接地线与带电部分应符合安全距离的规定。
4.4.3 检修母线时,应根据母线的长短和有无感应电压等实际情况确定地线数量。检修10m及以下的母线,可以只装设一组接地线。在门型架构的线路侧进行停电 检修,如工作地点与所装接地线的距离小于10m,工作地点虽在接地线外侧,也可 不另装接地线。
4.4.4 检修部分若分为几个在电气上不相连接的部分〔如分段母线以隔离开关(刀闸)或断路器(开关)隔开分成几段〕,则各段应分别验电接地短路。接地线与检修部分 之间不得连有断路器(开关)或熔断器(保险)。降压变电所全部停电时,应将各个可能 来电侧的部分接地短路,其余部分不必每段都装设接地线。
4.4.5 在室内配电装置上,接地线应装在该装置导电部分的规定地点,这些地点的 油漆应刮去,并划下黑色记号。
所有配电装置的适当地点,均应设有接地网的接头。接地电阻必须合格。
4.4.6 装设接地线必须由两人进行。若为单人值班,只允许使用接地刀闸接地,或 使用绝缘棒合接地刀闸。
4.4.7 装设接地线必须先接接地端,后接导体端,且必须接触良好。拆接地线的顺 序与此相反。装、拆接地线均应使用绝缘棒和戴绝缘手套。
4.4.8 接地线应用多股软裸铜线,其截面应符合短路电流的要求,但不得小于 25mm2。接地线在每次装设以前应经过详细检查。损坏的接地线应及时修理或更 换。禁止使用不符合规定的导线作接地或短路之用。
接地线必须使用专用的线夹固定在导体上,严禁用缠绕的方法进行接地或短 路。
4.4.9 高压回路上的工作,需要拆除全部或一部分接地线后始能进行工作者〔如测 量母线和电缆的绝缘电阻,检查断路器(开关)触头是否同时接触〕,如:
a.拆除一相接地线;
b.拆除接地线,保留短路线;
c.将接地线全部拆除或拉开接地刀闸。
必须征得值班员的许可(根据调度员命令装设的接地线,必须征得调度员的许 可),方可进行。工作完毕后立即恢复。
4.4.10 每组接地线均应编号,并存放在固定地点。存放位置亦应编号,接地线号码 与存放位置号码必须一致。4.4.11 装、拆接地线,应做好记录,交接班时应交待清楚。
4.5 悬挂标示牌和装设遮栏
4.5.1 在一经合闸即可送电到工作地点的断路器(开关)和隔离开关(刀闸)的操作把 手上,均应悬挂“禁止合闸,有人工作!”的标示牌(见附录D)。
如果线路上有人工作,应在线路断路器(开关)和隔离开关(刀闸)操作把手上悬 挂“禁止合闸,线路有人工作!”的标示牌,标示牌的悬挂和拆除,应按调度员的 命令执行。
4.5.2 部分停电的工作,安全距离小于表1规定距离以内的未停电设备,应装设临 时遮栏。临时遮栏与带电部分的距离,不得小于表2的规定数值。临时遮栏可用干 燥木材、橡胶或其他坚韧绝缘材料制成,装设应牢固,并悬挂“止步,高压危险!” 的标示牌。
35kV及以下设备的临时遮栏,如因工作特殊需要,可用绝缘挡板与带电部分 直接接触。但此种挡板必须具有高度的绝缘性能,并符合附录E的要求。
4.5.3 在室内高压设备上工作,应在工作地点两旁间隔和对面间隔的遮栏上和禁止 通行的过道上悬挂“止步,高压危险!”的标示牌。
4.5.4 在室外地面高压设备上工作,应在工作地点四周用绳子做好围栏,围栏上悬 挂适当数量的“止步,高压危险!”标示牌,标示牌必须朝向围栏里面。
4.5.5 在工作地点悬挂“在此工作!”的标示牌。
4.5.6 在室外架构上工作,则应在工作地点邻近带电部分的横梁上,悬挂“止步,高压危险!”的标示牌。此项标示牌在值班人员的监护下,由工作人员悬挂。在工作 人员上下铁架和梯子上应悬挂“从此上下!”的标示牌。在邻近其他可能误登的带电 架构上,应悬挂“禁止攀登,高压危险!”的标示牌。
4.5.7 严禁工作人员在工作中移动或拆除遮栏、接地线和标示牌。线路作业时发电厂和变电所的安全措施
5.1 线路的停送电均应按照值班调度员或有关单位书面指定的人员的命令执行。严 禁约时停、送电。停电时,必须先将该线路可能来电的所有断路器(开关)、线路隔 离开关(刀闸)、母线隔离开关(刀闸)全部拉开,用验电器验明确无电压后,在所有线 路上可能来电的各端装接地线,线路隔离开关(刀闸)操作把手上挂“禁止合闸,线路 有人工作!”的标示牌。
5.2 值班调度员必须将线路停电检修的工作班组数目、工作负责人姓名、工作地点 和工作任务记入记录簿。
工作结束时,应得到工作负责人(包括用户)的竣工报告,确认所有工作班组均 已竣工,接地线已拆除,工作人员已全部撤离线路,并与记录簿核对无误后,方可 下令拆除发电厂或变电所内的安全措施,向线路送电。
5.3 当用户管辖的线路要求停电时,必须得到用户工作负责人的书面申请方可停 电,并做好安全措施,恢复送电,必须接到原申请人的通知后方可进行。带电作业
6.1 一般规定
6.1.1 本章的规定适用于在海拔1000m及以下交流10~500kV的高压架空电力线 路、变电所(发电厂)电气设备上采用等电位、中间电位和地电位方式进行的带电作 业,以及低压带电作业。两线一地的线路及其电气设备上不宜进行带电作业。
6.1.2 带电作业应在良好天气下进行。如遇雷、雨、雪、雾不得进行带电作业,风 力大于5级时,一般不宜进行带电作业。
在特殊情况下,必须在恶劣天气进行带电抢修时,应组织有关人员充分讨论并 采取必要的安全措施,经厂(局)主管生产领导(总工程师)批准后方可进行。
6.1.3 对于比较复杂,难度较大的带电作业新项目和研制的新工具必须进行科学试 验,确认安全可靠,编出操作工艺方案和安全措施,并经厂(局)主管生产领导(总工 程师)批准后方可进行和使用。
6.1.4 带电作业工作票签发人和工作负责人应具有带电作业实践经验。工作票签发 人必须经厂(局)领导批准,工作负责人也可经工区领导批准。
6.1.5 带电作业必须设专人监护。监护人应由有带电作业实践经验的人员担任。监 护人不得直接操作。监护的范围不得超过一个作业点。复杂的或高杆塔上的作业应 增设(塔上)监护人。
6.1.6 带电作业工作票签发人和工作负责人对带电作业现场情况不熟悉时,应组织 有经验的人员到现场查勘。根据查勘结果作出能否进行带电作业的判断,并确定作 业方法和所需工具以及应采取的措施。
6.1.7 带电作业工作负责人在带电作业工作开始前应与调度联系,工作结束后向调 度汇报。
6.1.8 带电作业有下列情况之一者应停用重合闸,并不得强送电:
a.中性点有效接地的系统中有可能引起单相接地的作业。
b.中性点非有效接地的系统中有可能引起相间短路的作业。
c.工作票签发人或工作负责人认为需要停用重合闸的作业。
严禁约时停用或恢复重合闸。
6.1.9 在带电作业过程中如设备突然停电,作业人员应视设备仍然带电。工作负责 人应尽快与调度联系,调度未与工作负责人取得联系前不得强送电。
6.2 一般技术措施
6.2.1 进行地电位带电作业时,人身与带电体间的安全距离不得小于表3的规定。
35kV及以下的带电设备,不能满足表3规定的最小安全距离时,必须采取可 靠的绝缘隔离措施。
表3 人身与带电体的安全距离
注:1)因受设备限制达不到1.8m时,经厂(局)主管生产领导(总工程师)批 准,并采取必要的措施后,可采用括号内(1.6m)的数值。2)由于500kV带电作业经验不多,此数据为暂定数据。
6.2.2 绝缘操作杆,绝缘承力工具和绝缘绳索的有效长度不得小于表4的规定。
6.2.3 更换绝缘子或在绝缘子串上作业时,良好绝缘子片数不得少于表5的规定。
6.2.4 更换直线绝缘子串或移动导线的作业,当采用单吊线装置时,应采取防止导 线脱落时的后备保护措施。
6.2.5 在绝缘子串未脱离导线前,拆、装靠近横担的第一片绝缘子时,必须采用专 用短接线或穿屏蔽服方可直接进行操作。
6.2.6 在市区或人口稠密的地区进行带电作业时,工作现场应设置围栏,严禁非工 作人员入内。
表4 绝缘工具最小有效绝缘长度
表5 良好绝缘子最少片数
6.3 等电位作业
6.3.1 等电位作业一般在63(66)kV及以上电压等级的电力线路和电气设备上进行。若须在35kV及以下电压等级采用等电位作业时,应采取可靠的绝缘隔离措施。
6.3.2 等电位作业人员必须在衣服外面穿合格的全套屏蔽服(包括帽、衣、裤、手套、袜和鞋),且各部分应连接好,屏蔽服内还应穿阻燃内衣。
严禁通过屏蔽服断、接接地电流、空载线路和耦合电容器的电容电流。
6.3.3 等电位作业人员对地距离应不小于表3的规定,对邻相导线的距离应不小于 表6的规定。
表6 等电位作业人员对邻相导线的最小距离
6.3.4 等电位作业人员在绝缘梯上作业或沿绝缘梯进入强电场时,其与接地体和带 电体两部分间所组成的组合间隙不得小于表7的规定。
表7 组 合 间 隙 最 小 距 离
6.3.5 等电位作业人员沿绝缘子串进入强电场的作业,只能在220kV及以上电压等 级的绝缘子串上进行。扣除人体短接的和零值的绝缘子片后,良好绝缘子片数不得 小于表5的规定,其组合间隙不得小于表7的规定。若组合间隙不满足表7的规定,应加装保护间隙。
6.3.6 等电位作业人员在电位转移前,应得到工作负责人的许可,并系好安全带。转移电位时人体裸露部分与带电体的距离不应小于表8的规定。
表8 转移电位时人体裸露部分与带电体的最小距离
6.3.7 等电位作业人员与地面作业人员传递工具和材料时,必须使用绝缘工具或绝 缘绳索进行,其有效长度不得小于表4的规定。
6.3.8 沿导、地线上悬挂的软、硬梯或飞车进入强电场的作业应遵守下列规定:
6.3.8.1 在连接档距的导、地线上挂梯(或飞车)时,其导、地线的截面不得小于:
钢芯铝绞线
铜 绞 线
钢 绞 线
mmmmmm22
26.3.8.2 有下列情况之一者,应经验算合格,并经厂(局)主管生产领导(总工程师)批 准后才能进行:
a.在孤立档距的导、地线上的作业; b.在有断股的导、地线上的作业;
c.在有锈蚀的地线上的作业;
d.在其它型号导、地线上的作业;
e.二人以上在导、地线上的作业。
6.3.8.3 在导、地线上悬挂梯子前,必须检查本档两端杆塔处导、地线的紧固情况。挂梯载荷后地线及人体对导线的最小间距应比表3中的数值增大0.5m,导线及人 体对被跨越的电力线路、通信线路和其他建筑物的最小距离应比表3的安全距离增 大1m。
6.3.8.4 在瓷横担线路上严禁挂梯作业,在转动横担的线路上挂梯前应将横担固定。
6.3.9 等电位作业人员在作业中严禁用酒精、汽油等易燃品擦拭带电体及绝缘部 分,防止起火。
6.4 带电断、接引线
6.4.1 带电断、接空载线路,必须遵守下列规定:
6.4.1.1 带电断接空载线路时,必须确认线路的终端断路器(开关)[或隔离开关(刀 闸)]确已断开,接入线路侧的变压器、电压互感器确已退出运行后,方可进行。
严禁带负荷断、接引线。
6.4.1.2 带电断、接空载线路时,作业人员应戴护目镜,并应采取消弧措施,消弧 工具的断流能力应与被断、接的空载线路电压等级及电容电流相适应。如使用消弧 绳,则其断、接的空载线路的长度不应大于表9的规定,且作业人员与断开点应保 持4m以上的距离。
表9 使用消弧绳断、接空载线路的最大长度
注:线路长度包括分支在内,但不包括电缆线路。
6.4.1.3 在查明线路确无接地,绝缘良好,线路上无人工作且相位确定无误后才可 进行带电断、接引线。
6.4.1.4 带电接引时,未接通相的导线及带电断引时,已断开相的导线将因感应而 带电。为防止电击,应采取措施后才能触及。
6.4.1.5 严禁同时接触未接通的或已断开的导线两个断头,以防人体串入电路。
6.4.2 严禁用断、接空载线路的方法使两电源解列或并列。
6.4.3 带电断、接耦合电容器时,应将其信号、接地刀闸合上并应停用高频保护。被断开的电容器应立即对地放电。
6.4.4 带电断、接空载线路、耦合电容器、避雷器等设备时,应采取防止引流线摆 动的措施。
6.5 带电短接设备
6.5.1 用分流线短接断路器(开关)、隔离开关(刀闸)等载流设备时,必须遵守下列规 定:
6.5.1.1 短接前一定要核对相位。
6.5.1.2 组装分流线的导线处必须清除氧化层,且线夹接触应牢固可靠。
6.5.1.3 35kV及以下设备使用的绝缘分流线的绝缘水平应符合表17的规定。
6.5.1.4 断路器(开关)必须处于合闸位置,并取下跳闸回路熔断器(保险),锁死跳闸 机构后,方可短接。
6.5.1.5 分流线应支撑好,以防摆动造成接地或短路。
6.5.2 阻波器被短路前,严防等电位作业人员人体短接阻波器。
6.5.3 短接开关设备或阻波器的分流线截面和两端线夹的载流容量,应满足最大负 荷电流的要求。
6.6 带电水冲洗
6.6.1 带电水冲洗一般应在良好天气时进行,风力大于四级,气温低于零下3℃,雨天、雪天、雾天及雷电天气不宜进行。
6.6.2 带电水冲洗作业前应掌握绝缘子的脏污情况,当盐密值大于表10临界盐密值 的规定时,一般不宜进行水冲洗,否则,应增大水电阻率来补救。避雷器及密封不 良的设备不宜进行带电水冲洗。
6.6.3 带电水冲洗用水的电阻率一般不低于1500Ω·cm,冲洗220kV变电设备时 水电阻率不应低于3000Ω·cm,并应符合表10的要求。每次冲洗前都应用合格 的水阻表测量水电阻率,应从水枪出口处取水样进行测量。如用水车等容器盛水,每 车水都应测量水电阻率。
表10 带电水冲洗临界盐密值1)
(仅适用于220kV及以下)
注:1)330kV及500kV等级的临界盐密值尚不成熟,暂不列入。
2)爬电比距指电力设备外绝缘的爬电距离与设备最高工作电压之比。
6.6.4 以水柱为主绝缘的大、中、小型水冲(喷嘴直径为3mm及以下者称小水冲; 直径为4~8mm者称中水冲;直径为9mm及以上者称大水冲),其水枪喷嘴与带电 体之间的水柱长度不得小于表11的规定。大、中型水冲水枪喷嘴均应可靠接地。
表11 喷嘴与带电体之间的水柱长度(m)
6.6.5 由水柱、绝缘杆、引水管(指有效绝缘部分)组成的小水冲工具,其组合绝缘应 满足如下要求:
6.6.5.1 在工作状态下应能耐受表17规定的试验电压。
6.6.5.2 在最大工频过电压下流经操作人员人体的电流应不超过1mA,试验时间不 小于5min。
6.6.6 利用组合绝缘的小水冲工具进行冲洗时,冲洗工具严禁触及带电体。引水管 的有效绝缘部分不得触及接地体。
操作杆的使用及保管均按带电作业工具的有关规定执行。
6.6.7 带电冲洗前应注意调整好水泵压强,使水柱射程远且水流密集。当水压不足 时,不得将水枪对准被冲的带电设备。冲洗用水泵应良好接地。
6.6.8 带电水冲洗应注意选择合适的冲洗方法。直径较大的绝缘子宜采用双枪跟踪 法或其它方法,并应防止被冲洗设备表面出现污水线。当被冲绝缘子未冲洗干净 时,水枪切勿强行离开,以免造成闪络。
6.6.9 带电水冲洗前要确知设备绝缘是否良好。有零值及低值的绝缘子及瓷质有裂 纹时,一般不可冲洗。
6.6.10 冲洗悬垂绝缘子串、瓷横担、耐张绝缘子串时,应从导线侧向横担侧依次冲 洗。冲洗支柱绝缘子及绝缘瓷套时,应从下向上冲洗。
6.6.11 冲洗绝缘子时应注意风向,必须先冲下风侧,后冲下风侧,对于上、下层布 置的绝缘子应先冲下层,后冲上层,还要注意冲洗角度,严防临近绝缘子在溅射的 水雾中发生闪络。
6.7 带电爆炸压接
6.7.1 带电爆炸压接应使用工业8号纸壳火雷管。
6.7.2 为防止雷管在电场中自行起爆,引爆系统(包括雷管、导火索、拉火管)必须全 部屏蔽。
引爆方式可采用地面引爆和等电位引爆。当采用等电位引爆时,应做到:引爆 系统与导线连接牢固;安装引爆系统时,作业人员应始终与导线保持等电位;导火 索应有足够的长度,以保证作业人员安全撤离。
6.7.3 炸药爆炸会降低空气绝缘。为保证安全,应遵守下列规定:
6.7.3.1 爆炸时对地及相间的安全距离应满足表12的规定。表12 爆炸点对地及相间的安全距离
6.7.3.2 如不能满足表12的规定,可在药包外包食盐或聚胺脂泡沫塑料,以减小由 于爆炸时造成的空气绝缘降低。
6.7.4 爆炸压接时所有工作人员均应撤到爆炸点30m以外雷管开口端反向的安全区。
6.7.5 爆炸压接时,爆炸点距绝缘子、分流线、金属承力工具、绝缘工具的距离应 大于表13的规定,否则,应采取保护措施。
表13 爆炸点距邻近物的最小距离
6.7.6 若分裂导线间距小于0.4m,应设法加大距离或采取保护措施。
6.7.7 出现瞎炮时,应按《电业安全工作规程》(热力和机械部分)的有关规定处理。爆炸压接使用的炸药、雷管、导火索、拉火管均为易燃易爆物品,均应按上述规程 有关规定加以管理。
6.8 感应电压防护
6.8.1 在220~500kV电压等级的线路杆塔上及变电所构架上作业,必须采取防静 电感应措施,例如,穿着静电感应防护服或导电鞋等。
6.8.2 带电更换架空地线或架设耦合地线时,应通过放线滑车可靠接地。
6.8.3 绝缘架空地线应视为带电体。作业人员与绝缘架空地线之间的距离不应小于 0.4m。如需在绝缘架空地线上作业应用接地线将其可靠接地或采用等电位方式进 行。
6.8.4 用绝缘绳索传递大件金属物品(包括工具、材料等)时,杆塔或地面上作业人员 应将金属物品接地后再接触,以防电击。
6.9 高架绝缘斗臂车
6.9.1 使用前应认真检查,并在预定位置空斗试操作一次,确认液压传动、回转、升降、伸缩系统工作正常,操作灵活,制动装置可靠,方可使用。
6.9.2 绝缘臂的有效绝缘长度应大于表14的规定,并应在其下端装设泄漏电流监视 装置。
6.9.3 绝缘臂下节的金属部分,在仰起回转过程中,对带电体的距离应按表3的规 定值增加0.5m。工作中车体应良好接地。
表14 绝缘臂的最小长度
6.9.4 绝缘斗用于10~35kV带电作业时,其壁厚及层间绝缘水平应满足表17耐受 电压的规定。
6.9.5 操作绝缘斗臂车人员应熟悉带电作业的有关规定,并经专门培训,在工作过 程中不得离开操作台,且斗臂车的发动机不得熄火。
6.10 带电气吹清扫
6.10.1 用于气吹的操作杆和出气软管,应按表17相应电压等级要求耐压试验合 格。储气风包、出气软管及辅助罐等压力容器应作水压试验(108N/cm2)。
6.10.2 喷嘴宜用硬质绝缘材料制成。若用金属材料制作时,其长度不宜超过 100mm。喷嘴内径以3.5~6mm为宜。
6.10.3 用作辅料的锯末,须经16~30目筛网筛选和干燥。装入辅料罐前,应用 2500V摇表测量,其绝缘电阻应大于9000MΩ。
6.10.4 现场作业前,应认真检查空气压缩机是否正常,风包安全阀门是否动作可 靠,风包内有余水时,应先放完。空气压缩机的排气压力以59~98N/cm2为宜。
6.10.5 带电气吹操作人员工作中,必须戴护目镜、口罩和防尘帽。
操作人员宜站在上风侧位置作业,且须保持表3规定的安全距离。
6.10.6 在带电气吹作业时,作业人员应注意喷嘴不得垂直电瓷表面及定点气吹,以 免损坏电瓷和釉质表面层。
6.10.7 带电气吹清扫时,如遇喷嘴锯末阻塞,应先减压,再行消除障碍。
6.11 保护间隙
6.11.1 保护间隙的接地线应用多股软铜线。其截面应满足接地短路容量的要求,但 最小不得小于25mm2。
6.11.2 圆弧形保护间隙的距离应按表15的规定进行整定。
6.11.3 使用保护间隙时,应遵守下列规定:
6.11.3.1 悬挂保护间隙前,应与调度联系停用重合闸。
6.11.3.2 悬挂保护间隙应先将其与接地网可靠接地,再将保护间隙挂在导线上,并 使其接触良好。拆除程序相反。
表15 圆弧形保护间隙定值
6.11.3.3 保护间隙应挂在相邻杆塔的导线上,悬挂后,须派专人看守,在有人畜通 过的地区,还应增设围栏。
6.11.3.4 装拆保护间隙的人员应穿全套屏蔽服。
6.12 带电检测绝缘子
6.12.1 使用火花间隙检测器检测绝缘子时,应遵守下列规定:
6.12.1.1 检测前应对检测器进行检测,保证操作灵活,测量准确。
6.12.1.2 针式及少于3片的悬式绝缘子不得使用火花间隙检测器进行检测。
6.12.1.3 当检测35kV及以上电压等级的绝缘子串时,发现同一串中的零值绝缘子 片数达到表16的规定,应立即停止。
如绝缘子串的总片数超过表16规定时,零值绝缘子片数可相应增加。
6.12.1.4 应在干燥天气进行。
6.13 低压带电作业
表16 一串中允许零值绝缘子片数
6.13.1 低压带电作业应设专人监护,使用有绝缘柄的工具,工作时站在干燥的绝缘 物上进行,并戴手套和安全帽,必须穿长袖衣工作,严禁使用锉刀、金属尺和带有 金属物的毛刷、毛掸等工具。
6.13.2 高低压同杆架设,在低压带电线路上工作时,应先检查与高压线的距离,采 取防止误碰带电高压设备的措施。在低压带电导线未采取绝缘措施时,工作人员不 得穿越。在带电的低压配电装置上工作时,应采取防止相间短路和单相接地的绝缘 隔离措施。
6.13.3 上杆前应先分清火、地线,选好工作位置。断开导线时,应先断开火线,后 断开地线。搭接导线时,顺序应相反。
人体不得同时接触两根线头。
6.14 带电作业工具的保管与试验
6.14.1 带电作业工具应置于通风良好、备有红外线灯泡或去湿设施的清洁干燥的专 用房间存放。
6.14.2 高架绝缘斗臂车的绝缘部分应有防潮保护罩,并应存放在通风、干燥的车库 内。
6.14.3 在运输过程中,带电绝缘工具应装在专用工具袋、工具箱或专用工具车内,以防受潮和损伤。
6.14.4 不合格的带电作业工具应及时检修或报废,不得继续使用。
6.14.5 发现绝缘工具受潮或表面损伤、脏污时,应及时处理并经试验合格后方可使 用。
6.14.6 使用工具前应仔细检查其是否损坏、变形、失灵,并使用2500V绝缘摇表 或绝缘检测仪进行分段绝缘检测(电极宽2cm,极间宽2cm),阻值应不低于700MΩ。操作绝缘工具时应戴清洁、干燥的手套,并应防止绝缘工具在使用中脏污和受潮。
6.14.7 带电作业工具应设专人保管,登记造册,并建立每件工具的试验记录。
6.14.8 带电作业工具应定期进行电气试验及机械试验。其试验周期为:
电气试验:预防性试验每年一次,检查性试验每年一次,两次试验间隔半年。
机械试验:绝缘工具每年一次,金属工具两年一次。
6.14.9 绝缘工具电气试验项目及标准见表17。
表17 绝缘工具的试验项目及标准
操作冲击耐压试验宜采用250/2500μs的标准波,以无一次击穿、闪络为合格。
工频耐压试验以无击穿、无闪络及过热为合格。
高压电极应使用直径不小于30mm的金属管,被试品应垂直悬挂。接地极的对 地距离为1.0~1.2m。接地极及接高压的电极(无金具时)处以50mm宽金属泊缠绕。试品间距不小于500mm,单导线两侧均压球直径不小于200mm,均压球距试品不 小于1.5m。
试品应整根进行试验,不得分段。
6.14.10 绝缘工具的检查性试验条件是:将绝缘工具分成若干段进行工频耐压,每 300mm耐压75kV,时间为1min,以无击穿、闪络及过热为合格。
6.14.11 组合绝缘的水冲洗工具应在工作状态下进行电气试验。除按表17的项目和 标准试验外(指220kV及以下电压等级),还应增加工频泄漏试验,试验电压见表 18。泄漏电流以不超过1mA为合格,试验时间5min。
试验时的水电阻率为1500Ω·cm(适用于220kV及以下电压等级)。
表18 组合绝缘水冲洗工具工频泄漏试验电压值
6.14.12 带电作业工具的机械试验标准:
静荷重试验:2.5倍允许工作负荷下持续5min,工具无变形及损伤者为合格。
动荷重试验:1.5倍允许工作负荷下实际操作3次,工具灵活、轻便,无卡住 现象者为合格。
6.14.13 屏蔽服衣裤最远端点之间的电阻值均不得大于20Ω。发电机、同期调相机和高压电动机的维护工作
7.1 检修发电机、同期调相机和高压电动机应填用第一种工作票。
7.2 发电厂主要机组(锅炉、汽机、发电机)停电检修,只需第一天办理开工手续,以后每天开工时,应由工作负责人检查现场,核对安全措施。检修期间工作票始终 由工作负责人保存。工作全部结束,再办理工作票结束手续。
在同一机组的几个电动机上依次工作时,可填用一张工作票。
7.3 检修发电机、同期调相机必须做好下列安全措施:
a.断开发电机、同期调相机的断路器(开关)和隔离开关(刀闸);
b.待发电机和同期调相机完全停止后,在操作把手、按钮、机组的启动装置、并车装置插座和盘车装置的操作把手上悬挂“禁止合闸,有人工作!”的标示牌;
c.若本机尚可从其他电源获得励磁电流,则此项电源亦必须断开,并悬挂“禁 止合闸,有人工作!”的标示牌;
d.断开断路器(开关)、隔离开关(刀闸)的操作能源。如调相机有启动用的电动 机,还应断开此电动机的断路器(开关)和隔离开关(刀闸),并悬挂“禁止合闸,有 人工作!”的标示牌;
e.将电压互感器从高、低压两侧断开;
f.经验明无电压后,在发电机和断路器(开关)间装设接地线;
g.检修机组中性点与其他发电机的中性点连在一起的,则在工作前必须将检修 发电机的中性点分开;
h.检修机组装有二氧化碳或蒸汽灭火装置的,则在风道内工作前,应采取防止 灭火装置误动的必要措施;
i.检修机组装有可以堵塞机内空气流通的自动闸板风门的,应采取措施保证使 风门不能关闭,以防窒息。
7.4 转动着的发电机、同期调相机,即使未加励磁,亦应认为有电压。
禁止在转动着的发电机、同期调相机的回路上工作,或用手触摸高压绕组。必 须不停机进行紧急修理时,应先将励磁回路切断,投入自动灭磁装置,然后将定子 引出线与中性点短路接地。在拆装短路接地线时,应戴绝缘手套,穿绝缘靴或站在 绝缘垫上,并戴护目眼镜。
7.5 测量轴电压和在转动着的发电机上用电压表测量转子绝缘的工作,应使用专用 电刷,电刷上应装有 300mm 以上的绝缘柄。7.6 在转动着的电机上调整、清扫电刷及滑环时,应由有经验的电工担任,并遵守 下列规定:
a.工作人员必须特别小心,不使衣服及擦拭材料被机器挂住,扣紧袖口,发辫 应放在帽内;
b.工作时站在绝缘垫上(该绝缘垫为常设固定型绝缘垫),不得同时接触两极或 一极与接地部分,也不能两人同时进行工作。
7.7 检修高压电动机和启动装置时,应做好下列安全措施:
a.断开电源断路器(开关)、隔离开关(刀闸),经验明确无电压后装设接地线或在 隔离开关(刀闸)间装绝缘隔板,小车开关应从成套配电装置内拉出并关门上锁;
b.在断路器(开关)、隔离开关(刀闸)把手上悬挂“禁止合闸,有人工作!”的标 示牌;
c.拆开后的电缆头须三相短路接地;
d.做好防止被其带动的机械(如水泵、空气压缩机、引风机等)引起电动机转 动的措施,并在阀门上悬挂“禁止合闸,有人工作!”的标示牌。
7.8 禁止在转动着的高压电动机及其附属装置回路上进行工作。必须在转动着的电 动机转子电阻回路上进行工作时,应先提起碳刷或将电阻完全切除。工作时要戴手 套或使用有绝缘把手的工具,穿绝缘靴或站在绝缘垫上。
7.9 电动机的引出线和电缆头以及外露的转动部分均应装设牢固的遮栏或护罩。
7.10 电动机及起动装置的外壳均应接地。禁止在运转中的电动机的接地线上进行 工作。
7.11 工作尚未全部终结,而需送电试验电动机或起动装置时,应收回全部工作票 并通知有关机械部分检修人员后,方可送电。在六氟化硫电气设备上的工作
8.1 装有SF6设备的配电装置室和SF6气体实验室,必须装设强力通风装置。风口 应设置在室内底部。
8.2 在室内,设备充装SF6气体时,周围环境相对湿度应≤80%,同时必须开启通 风系统,并避免SF6气体漏泄到工作区。工作区空气中SF6气体含量不得超过 1000ppm。
8.3 SF6新气应具有厂家名称、装灌日期、批号及质量检验单。SF6新气到货后应按 有关规定进行复核、检验,合格后方准使用。SF6新气标准见附录H。
在气瓶内存放半年以上的SF6气体,使用前应先检验其水份和空气含量,符合 标准后方准使用。
8.4 SF6电气设备投运前,应检验设备气室内SF6气体水份和空气含量。
设备运行后每三个月检查一次SF6气体含水量,直至稳定后,方可每年检测 一次含水量。SF6气体有明显变化时,应请上级复核。
8.5 主控制室与SF6配电装置室间要采取气密性隔离措施。
8.6 工作人员进入SF6配电装置室,必须先通风15min,并用检漏仪测量SF6气体含 量。尽量避免一人进入SF6配电装置室进行巡视,不准一人进入从事检修工作。
8.7 工作人员不准在SF6设备防爆膜附近停留,若在巡视中发现异常情况,应立即 报告,查明原因,采取有效措施进行处理。
8.8 进入SF6配电装置低位区或电缆沟进行工作应先检测含氧量(不低于18%)和SF6 气体含量是否合格。
8.9 在SF6配电装置室低位区应安装能报警的氧量仪和SF6气体泄漏警报仪。这些仪 器应定期试验,保证完好。
8.10 设备解体检修前,必须对SF6气体进行检验。根据有毒气体的含量,采取安全 防护措施。检修人员需着防护服并根据需要配戴防毒面具。打开设备封盖后,检修 人员应暂离现场30min。取出吸附剂和清除粉尘时,检修人员应戴防毒面具和防护 手套。
8.11 设备内的SF6气体不得向大气排放,应采用净化装置回收,经处理合格后方准 使用。
设备抽真空后,用高纯氮气冲洗3次[压力为9.8×104Pa(1个大气压)]。将 清出的吸附剂、金属粉末等废物放入20%氢氧化钠水溶液中浸泡12h后深埋。
8.12 从SF6气体钢瓶引出气体时,必须使用减压阀降压。当瓶内压力降至9.8× 104Pa(1个大气压)时,即停止引出气体,并关紧气瓶阀门,戴上瓶帽,防止气体 泄漏。
8.13 发生紧急事故应立即开启全部通风系统进行通风。发生设备防爆膜破裂事故 时,应停电处理,并用汽油或丙酮擦拭干净。
8.14 进行气体采样和处理一般渗漏时,要戴防毒面具并进行通风。
8.15 检修结束后,检修人员应洗澡,把用过的工器具、防护用具清洗干净。
8.16 SF6气瓶应放置在阴凉干燥、通风良好、敞开的专门场所,直立保存,并应远 离热源和油污的地方,防潮、防阳光曝晒,并不得有水份或油污粘在阀门上。
搬运时,应轻装轻卸。
8.17 未经检验的SF6新气气瓶和已检验合格的气体气瓶应分别存放,不得混淆。在停电的低压配电装置和低压导线上的工作
9.1 低压配电盘、配电箱和电源干线上的工作,应填用第二种工作票。
在低压电动机和照明回路上工作,可用口头联系。
上述工作至少由两人进行。
9.2 低压回路停电的安全措施:
9.2.1 将检修设备的各方面电源断开,取下熔断器(保险),在刀闸操作把手上挂“禁 止合闸,有人工作!”的标示牌。
9.2.2 工作前必须验电。
9.2.3 根据需要采取其他安全措施。
9.3 停电更换保险器后,恢复操作时,应戴手套和护目眼镜。在继电保护、仪表第二次回路上的工作
10.1 下列情况应填用第一种工作票:
10.1.1 在高压室遮栏内或与导电部分小于表1规定的安全距离进行继电器和仪表 等的检查试验时,需将高压设备停电的。
10.1.2 检查高压电动机和起动装置的继电器和仪表需将高压设备停电的。
10.2 下列情况应填用第二种工作票:
10.2.1 一次电流继电器有特殊装置可以在运行中改变定值的。
10.2.2 对于连于电流互感器或电压互感器二次绕组并装在通道上或配电盘上的继 电器和保护装置,可以不断开所保护的高压设备的。上述工作至少由两人进行。
10.3 继电保护人员在现场工作过程中,凡遇到异常情况(如直流系统接地等)或开 关跳闸时,不论与本身工作是否有关,应立即停止工作,保持现状,待查明原因,确定与本工作无关时方可继续工作;若异常情况是本身工作所引起,应保留现场并 立即通知值班人员,以便及时处理。
10.4 工作前应做好准备,了解工作地点一次及二次设备运行情况和上次的检验记 录、图纸是否符合实际。
10.5 现场工作开始前,应查对已做的安全措施是否符合要求,运行设备与检修设 备是否明确分开,还应看清设备名称,严防走错位置。
10.6 在全部或部分带电的盘上进行工作时,应将检修设备与运行设备前后以明显 的标志隔开(如盘后用红布帘,盘前用“在此工作”标志牌等)。
10.7 在保护盘上或附近进行打眼等振动较大的工作时,应采取防止运行中设备掉 闸的措施,必要时经值班调度员或值班负责人同意,将保护暂时停用。
10.8 在继电保护屏间的通道上搬运或安放试验设备时,要与运行设备保持一定距 离,防止误碰运行设备,造成保护误动作。清扫运行设备和二次回路时,要防止振 动,防止误碰,要使用绝缘工具。
10.9 继电保护装置做传动试验或一次通电时,应通知值班员和有关人员,并由工 作负责人或由他派人到现场监视,方可进行。
10.10 所有电流互感器和电压互感器的二次绕组应有永久性的、可靠的保护接地。
10.11 在带电的电流互感器二次回路上工作时,应采取下列安全措施:
10.11.1 严禁将变流器二次侧开路;
10.11.2 短路变流器二次绕组,必须使用短路片或短路线,短路应妥善可靠,严禁 用导线缠绕;
10.11.3 严禁在电流互感器与短路端子之间的回路和导线上进行任何工作;
10.11.4 工作必须认真、谨慎,不得将回路的永久接地点断开;
10.11.5 工作时,必须有专人监护,使用绝缘工具,并站在绝缘垫上。
10.12 在带电的电压互感器二次回路上工作时,应采取下列安全措施:
10.12.1 严格防止短路或接地。应使用绝缘工具,戴手套。必要时,工作前停用有 关保护装置;
10.12.2 接临时负载,必须装有专用的刀闸和熔断器(保险)。
10.13 二次回路通电或耐压试验前,应通知值班员和有关人员,并派人到各现场看 守,检查回路上确无人工作后,方可加压。
电压互感器的二次回路通电试验时,为防止由二次侧向一次侧反充电,除应将 二次回路断开外,还应取下一次熔断器(保险)或断开隔离开关(刀闸)。
10.14 检验继电保护和仪表的工作人员,不准对运行中的设备、信号系统、保护 压板进行操作,但在取得值班人员许可并在检修工作盘两侧开关把手上采取防误操作 措施后,可拉合检修开关。
10.15 试验用刀闸必须带罩,禁止从运行设备上直接取试验电源,熔丝配合要适 当,要防止越级熔断总电源熔丝。试验结线要经第二人复查后,方可通电。
10.16 保护装置二次回路变动时,严防寄生回路存在,没用的线应拆除,临时所垫 纸片应取出,接好已拆下的线头。11 电气试验
11.1 高压试验
11.1.1 高压试验应填写第一种工作票。
在一个电气连接部分同时有检修和试验时,可填写一张工作票,但在试验前应 得到检修工作负责人的许可。
在同一电气连接部分,高压试验的工作票发出后,禁止再发出第二张工作票。
如加压部分与检修部分之间的断开点,按试验电压有足够的安全距离,并在另 一侧有接地短路线时,可在断开点的一侧进行试验,另一侧可继续工作。但此时在 断开点应挂有“止步,高压危险!”的标示牌,并设专人监护。
11.1.2 高压试验工作不得少于两人。试验负责人应由有经验的人员担任,开始试验 前,试验负责人应对全体试验人员详细布置试验中的安全注意事项。
11.1.3 因试验需要断开设备接头时,拆前应做好标记,接后应进行检查。
11.1.4 试验装置的金属外壳应可靠接地;高压引线应尽量缩短,必要时用绝缘物支 持牢固。
试验装置的电源开关,应使用明显断开的双极刀闸。为了防止误合刀闸,可在 刀刃上加绝缘罩。
试验装置的低压回路中应有两个串联电源开关,并加装过载自动掉闸装置。
11.1.5 试验现场应装设遮栏或围栏,向外悬挂“止步,高压危险!”的标示牌,并 派人看守。被试设备两端不在同一地点时,另一端还应派人看守。
11.1.6 加压前必须认真检查试验结线,表计倍率、量程,调压器零位及仪表的开始 状态,均正确无误,通知有关人员离开被试设备,并取得试验负责人许可,方可加 压。加压过程中应有人监护并呼唱。
高压试验工作人员在全部加压过程中,应精力集中,不得与他人闲谈,随时警 戒异常现象发生,操作人应站在绝缘垫上。
11.1.7 变更结线或试验结束时,应首先断开试验电源,放电,并将升压设备的高 压部分短路接地。
11.1.8 未装地线的大电容被试设备,应先行放电再做试验。高压直流试验时,每告 一段落或试验结束时,应将设备对地放电数次并短路接地。
11.1.9 试验结束时,试验人员应拆除自装的接地短路线,并对被试设备进行检查和 清理现场。
11.1.10 特殊的重要电气试验,应有详细的试验措施,并经厂(局)主管生产的领导(总 工程师)批准。
11.2 使用携带型仪器的测量工作
11.2.1 使用携带型仪器在高压回路上进行工作,需要高压设备停电或做安全措施 的,应填用第一种工作票,并至少由两人进行。
11.2.2 除使用特殊仪器外,所有使用携带型仪器的测量工作,均应在电流互感器和 电压互感器的低压侧进行。
11.2.3 电流表、电流互感器及其他测量仪表的接线和拆卸,需要断开高压回路者,应将此回路所连接的设备和仪器全部停电后,始能进行。
11.2.4 电压表、携带型电压互感器和其他高压测量仪器的接线和拆卸无需断开高压 回路者,可以带电工作。但应使用耐高压的绝缘导线,导线长度应尽可能缩短,不 准有接头,并应连接牢固,以防接地和短路。必要时用绝缘物加以固定。
使用电压互感器进行工作时,先应将低压侧所有接线接好,然后用绝缘工具将 电压互感器接到高压侧。工作时应带手套和护目眼镜,站在绝缘垫上,并应有专人 监护。
11.2.5 连接电流回路的导线截面,应适合所测电流数值。连接电压回路的导线截面 不得小于1.5mm2。
11.2.6 非金属外壳的仪器,应与地绝缘,金属外壳的仪器和变压器外壳应接地。
11.2.7 所有测量用装置均应设遮栏和围栏,并悬挂“止步,高压危险!”的标示牌。仪器的布置应使工作人员距带电部分不小于表1规定的安全距离。
11.3 使用钳形电流表的测量工作
11.3.1 值班人员在高压回路上使用钳形电流表的测量工作,应由两人进行。非值班 人员测量时,应填第二种工作票。
11.3.2 在高压回路上测量时,严禁用导线从钳形电流表另接表计测量。
11.3.3 测量时若需拆除遮栏,应在拆除遮栏后立即进行。工作结束,应立即将遮栏 恢复原位。
11.3.4 使用钳形电流表时,应注意钳形电流表的电压等级。测量时戴绝缘手套,站 在绝缘垫上,不得触及其他设备,以防短路或接地。
观测表计时,要特别注意保持头部与带电部分的安全距离。
11.3.5 测量低压熔断器(保险)和水平排列低压母线电流时,测量前应将各相熔断器(保险)和母线用绝缘材料加以包护隔离,以免引起相间短路,同时应注意不得触及 其他带电部分。
11.3.6 在测量高压电缆各相电流时,电缆头线间距离应在300mm以上,且绝缘良 好,测量方便者,方可进行。
当有一相接地时,严禁测量。
11.3.7 钳形电流表应保存在干燥的室内,使用前要擦拭干净。
11.4 使用摇表测量绝缘的工作
11.4.1 使用摇表测量高压设备绝缘,应由两人担任。
11.4.2 测量用的导线,应使用绝缘导线,其端部应有绝缘套。
11.4.3 测量绝缘时,必须将被测设备从各方面断开,验明无电压,确实证明设备无 人工作后,方可进行。在测量中禁止他人接近设备。
在测量绝缘前后,必须将被试设备对地放电。
测量线路绝缘时,应取得对方允许后方可进行。
11.4.4 在有感应电压的线路上(同杆架设的双回线路或单回路与另一线路有平行 段)测量绝缘时,必须将另一回线路同时停电,方可进行。
雷电时,严禁测量线路绝缘。
11.4.5 在带电设备附近测量绝缘电阻时,测量人员和摇表安放位置,必须选择适 当,保持安全距离,以免摇表引线或引线支持物触碰带电部分。移动引线时,必 须注意监护,防止工作人员触电。
电力电缆工作
12.1 电力电缆停电工作应填用第一种工作票,不需停电的工作应填用第二种工作 票。工作前必须详细核对电缆名称,标示牌是否与工作票所写的符合,安全措施正 确可靠后,方可开始工作。
12.2 挖掘电缆工作,应由有经验人员交待清楚后才能进行。挖到电缆保护板后,应由有经验的人员在场指导,方可继续工作。
挖掘电缆沟前,应做好防止交通事故的安全措施。在挖出的土堆起的斜坡上,不得放置工具、材料等杂物。沟边应留有走道。
12.3 挖掘出的电缆或接头盒,如下面需要挖空时,必须将其悬吊保护,悬吊电缆 应每隔约1.0~1.5m吊一道。悬吊接头盒应平放,不得使接头受到拉力。
12.4 敷设电缆时,应有专人统一指挥。电缆走动时,严禁用手搬动滑轮,以防压 伤。
移动电缆接头盒一般应停电进行。如带电移动时,应先调查该电缆的历史记 录,由敷设电缆有经验的人员,在专人统一指挥下,平正移动,防止绝缘损伤爆炸。
12.5 锯电缆以前,必须与电缆图纸核对是否相符,并确切证实电缆无电后,用接 地的带木柄的铁钎钉入电缆芯后,方可工作。扶木柄的人应戴绝缘手套并站在绝缘垫 上。
12.6 熬电缆胶工作应有专人看管。熬胶人员,应戴帆布手套及鞋盖。搅拌或掐取 溶化的电缆胶或焊锡时,必须使用预先加热的金属棒或金属勺子,防止落入水分而发 生爆溅烫伤。
12.7 进电缆井前,应排除井内浊气。电缆井内工作,应戴安全帽,并做好防火、防水及防止高空落物等措施,电缆井口应有专人看守。
12.8 水底电缆提起放在船上工作时,应使船体保持平衡。船上应具备足够的救生 圈,工作人员应穿救生衣。
12.9 制做环氧树脂电缆头和调配环氧树脂工作过程中,应采取有效的防毒和防火 措施。其他安全措施
13.1 使用携带型火炉或喷灯时,火焰与带电部分的距离:电压在10kV及以下者,不得小于1.5m;电压在10kV以上者,不得小于3m。不得在带电导线、带电设备、变压器、油开关附近将火炉或喷灯点火。
13.2 在屋外变电所和高压室内搬动梯子、管子等长物,应两人放倒搬运,并与带 电部分保持足够的安全距离。
13.3 工作地点应有充足的照明。
13.4 进入高空作业现场,应戴安全帽。高处作业人员必须使用安全带。
高处工作传递物件,不得上下抛掷。
13.5 雷电时,禁止在室外变电所或室内的架空引入线上进行检修和试验。
13.6 遇有电气设备着火时,应立即将有关设备的电源切断,然后进行救火。对带 电设备应使用干式灭火器、二氧化碳灭火器等灭火,不得使用泡沫灭火器灭火。对注 油设备应使用泡沫灭火器或干燥的砂子等灭火。发电厂和变电所控制室内应备有防 毒面具,防毒面具要按规定使用并定期进行试验,使其经常处于良好状态。
13.7 在带电设备周围严禁使用钢卷尺、皮卷尺和线尺(夹有金属丝者)进行测量工 作。
13.8 在电容器组上或进入其围栏内工作时,应将电容器逐个多次放电并接地后,方可进行。
附 录 A
倒闸操作票格式
(补充件)
发电厂(变电所)倒闸操作票
编号:
操作人:
监护人:
值班负责人:
值长:
附 录 B
第一种工作票格式
(补充件)
发电厂(变电所)第一种工作票
第____号
1.工作负责人(监护人):_________________班组:______________________ 2.工作班人员:______________________共__________________________人 3.工作内容和工作地点:____________________________________________ ______________________________________________________________________ 4.计划工作时间:
自
****年**月**日
时
分
至
****年**月**日
时
分
5.安全措施:
下列由工作票签发人填写
下列由工作许可人(值班员)填写
(发电厂值长签名:)
6.许可开始工作时间:____________年______月______日_______时______分
工作许可人签名:___________工作负责人签名:_____________________ 7.工作负责人变动:
原工作负责人____________离去,变更______________为工作负责人。
变动时间:_____________年_______月______日_______时________分,工作票签发人签名:___________________
8.工作票延期,有效期延长到:__________年____月____日______时____分
工作负责人签名:__________值长或值班负责人签名:________________ 9.工作终结:
工作班人员已全部撤离,现场已清理完毕。
全部工作于____________年______月_____日______时_______分结束。
工作负责人签名:工作许可人签名:
接地线共_____________组已拆除。
值班负责人签名:____________
10.备注:__________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________
附 录 C
第二种工作票格式
(补充件)
发电厂(变电所)第二种工作票
编号:
1.工作负责人(监护人):_________________________班组__________________ 工作班人员:_________________________
2.工作任务:___________________________________________________________ _______________________________________________________________________ 3.计划工作时间:自__________年_______月______日______时______分
至__________年_______月______日______时______分
4.工作条件(停电或不停电):
______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ 5.注意事项(安全措施):_________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________
工作票签发人签名:__________________
6.许可开始工作时间:___________年________月_____日______时________分
工作许可人(值班员)签名:________________工作负责人签名:_______________ 7.工作结束时间:_______________年________月_____日_______时________分
工作负责人签名:_____________工作许可人(值班员)签名:_______________ 8.备注:_______________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________
附 录 D 标示牌式样
(补充件)
附 录 E
常用电气绝缘工具试验一览表
(补充件)
附 录 F
登高安全工具试验标准表
(补充件)
附 录 G 紧急救护法
(补充件)
G1 通则
G1.1 紧急救护的基本原则是在现场采取积极措施保护伤员生命,减轻伤情,减少 痛苦,并根据伤情需要,迅速联系医疗部门救治。急救的成功条件是动作快,操 作正确。任何拖延和操作错误都会导致伤员伤情加重或死亡。
G1.2 要认真观察伤员全身情况,防止伤情恶化。发现呼吸、心跳停止时,应立即 在现场就地抢救,用心肺复苏法支持呼吸和循环,对脑、心重要脏器供氧。应当 记住只有在心脏停止跳动后分秒必争地迅速抢救,救活的可能才较大。
G1.3 现场工作人员都应定期进行培训,学会紧急救护法。会正确解脱电源、会心 肺复苏法、会止血、会包扎、会转移搬运伤员、会处理急救外伤或中毒等。
G1.4 生产现场和经常有人工作的场所应配备急救箱,存放急救用品,并应指定专 人经常检查、补充或更换。
G2 触电急救
G2.1 触电急救必须分秒必争,立即就地迅速用心肺复苏法进行抢救,并坚持不断 地进行,同时及早与医疗部门联系,争取医务人员接替救治。在医务人员未接替 救治前,不应放弃现场抢救,更不能只根据没有呼吸或脉搏擅自判定伤员死亡,放弃抢救。只有医生有权做出伤员死亡的诊断。
G2.2 脱离电源:
G2.2.1 触电急救,首先要使触电者迅速脱离电源,越快越好。因为电流作用的时 间越长,伤害越重。G2.2.2 脱离电源就是要把触电者接触的那一部分带电设备的开关、刀闸或其他断 路设备断开;或设法将触电者与带电设备脱离。在脱离电源中,救护人员既要救 人,也要注意保护自己。
G2.2.3 触电者未脱离电源前,救护人员不准直接用手触及伤员,因为有触电的危 险。
G2.2.4 如触电者处于高处,触脱电源后会自高处坠落,因此,要采取预防措施。
G2.2.5 触电者触及低压带电设备,救护人员应设法迅速切断电源,如拉开电源开 关或刀闸,拔除电源插头等;或使用绝缘工具、干燥的木棒、木板、绳索等不导 电的东西解脱触电者;也可抓住触电者干燥而不贴身的衣服,将其拖开,切记要 避免碰到金属物体和触电者的裸露身躯;也可戴绝缘手套或将手用干燥衣物等包 起绝缘后解脱触电者;救护人员也可站在绝缘垫上或干木板上,绝缘自己进行救 护。
为使触电者与导电体解脱,最好用一只手进行。
如果电流通过触电者入地,并且触电者紧握电线,可设法用干木板塞到身下,与地隔离,也可用干木把斧子或有绝缘柄的钳子等将电线剪断。剪断电线要分相,一根一根地剪断,并尽可能站在绝缘物体或干木板上。
G2.2.6 触电者触及高压带电设备,救护人员应迅速切断电源,或用适合该电压等 级的绝缘工具(戴绝缘手套、穿绝缘靴并用绝缘棒)解脱触电者。救护人员在抢救过 程中应注意保持自身与周围带电部分必要的安全距离。
G2.2.7 如果触电发生在架空线杆塔上,如系低压带电线路,若可能立即切断线路 电源的,应迅速切断电源,或者由救护人员迅速登杆,束好自己的安全皮带后,用 带绝缘胶柄的钢丝钳、干燥的不导电物体或绝缘物体将触电者拉离电源;如系高压 带电线路,又不可能迅速切断电源开关的,可采用抛挂足够截面的适当长度的金属 短路线方法,使电源开关跳闸。抛挂前,将短路线一端固定在铁塔或接地引下线上,另一端系重物,但抛掷短路线时,应注意防止电弧伤人或断线危及人员安全。不论 是何级电压线路上触电,救护人员在使触电者脱离电源时要注意防止发生高处坠落 的可能和再次触及其它有电线路的可能。
G2.2.8 如果触电者触及断落在地上的带电高压导线,且尚未确证线路无电,救护 人员在未做好安全措施(如穿绝缘靴或临时双脚并紧跳跃地接近触电者)前,不能接近断线点至8~10m范围内,防止跨步电压伤人。触电者脱离带电导线后亦应迅 速带至8~10m以外后立即开始触电急救。只有在确证线路已经无电,才可在触电 者离开触电导线后,立即就地进行急救。
G2.2.9 救护触电伤员切除电源时,有时会同时使照明失电,因此应考虑事故照明、应急灯等临时照明。新的照明要符合使用场所防火、防爆的要求。但不能因此延误 切除电源和进行急救。
G2.3 伤员脱离电源后的处理:
G2.3.1 触电伤员如神志清醒者,应使其就地躺平,严密观察,暂时不要站立或走 动。
G2.3.2 触电伤员如神志不清者,应就地仰面躺平,且确保气道通畅,并用5s时间,呼叫伤员或轻拍其肩部,以判定伤员是否意识丧失。禁止摇动伤员头部呼叫伤员。
G2.3.3 需要抢救的伤员,应立即就地坚持正确抢救,并设法联系医疗部门接替救 治。
图G1 看、听、试
G2.4 呼吸、心跳情况的判定:
G2.4.1 触电伤员如意识丧失,应在10s内,用看、听、试的方法(见图G1),判定 伤员呼吸心跳情况。
G2.4.1.1 看—看伤员的胸部、腹部有无起伏动作;
G2.4.1.2 听—用耳贴近伤员的口鼻处,听有无呼气声音;
G2.4.1.3 试—试测口鼻有无呼气的气流。再用两手指轻试一侧(左或右)喉结旁凹陷 处的颈动脉有无搏动。
G2.4.2 若看、听、试结果,既无呼吸又无颈动脉搏动,可判定呼吸心跳停止。
G2.5 心肺复苏法:
G2.5.1 触电伤员呼吸和心跳均停止时,应立即按心肺复苏法支持生命的三项基本 措施,正确进行就地抢救。
a.通畅气道;
b.口对口(鼻)人工呼吸;
c.胸外接压(人工循环)。
G2.5.2 通畅气道:
G2.5.2.1 触电伤员呼吸停止,重要的是始终确保气道通畅。如发现伤员口内有异 物,可将其身体及头部同时侧转,迅速用一个手指或用两手指交叉从口角处插入,取出异物;操作中要注意防止将异物推到咽喉深部。
G2.5.2.2 通畅气道可采用仰头抬颏法(见图G2)。用一只手放在触电者前额,另一 只手的手指将其下颌骨向上抬起,两手协同将头部推向后仰,舌根随之抬起,气道 即可通畅(判断气道是否通畅可参见图G3)。严禁用枕头或其它物品垫在伤员头下,头部抬高前倾,会更加重气道阻塞,且使胸外按压时流向脑部的血流减少,甚至消 失。
图G2 仰头抬颏法
图G3 气道状况
(a)气道通畅;(b)气道阻塞 G2.5.3 口对口(鼻)人工呼吸(见图G4):
图G4 口对口人工呼吸
G2.5.3.1 在保持伤员气道通畅的同时,救护人员用放在伤员额上的手的手指捏住 伤员鼻翼,救护人员深吸气后,与伤员口对口紧合,在不漏气的情况下,先连续大 口吹气两次,每次1~1.5s。如两次吹气后试测颈动脉仍无搏动,可判断心跳已经 停止,要立即同时进行胸外按压。
G2.5.3.2 除开始时大口吹气两次外,正常口对口(鼻)呼吸的吹气量不需过大,以免 引起胃膨胀。吹气和放松时要注意伤员胸部应有起伏的呼吸动作。吹气时如有较大 阻力,可能是头部后仰不够,应及时纠正。
G2.5.3.3 触电伤员如牙关紧闭,可口对鼻人工呼吸。口对鼻人工呼吸吹气时,要 将伤员嘴唇紧闭,防止漏气。
G2.5.4 胸外按压:
G2.5.4.1 正确的按压位置是保证胸外按压效果的重要前提。确定正确按压位置的 步骤:
a.右手的食指和中指沿触电伤员的右侧肋弓下缘向上,找到肋骨和胸骨接合处 的中点;
b.两手指并齐,中指放在切迹中点(剑突底部),食指平放在胸骨下部;
c.另一只手的掌根紧挨食指上缘,置于胸骨上,即为正确按压位置(见图G5)。
G2.5.4.2 正确的按压姿势是达到胸外按压效果的基本保证。正确的按压姿势:
a.使触电伤员仰面躺在平硬的地方,救护人员立或跪在伤员一侧肩旁,救护人 员的两肩位于伤员胸骨正上方,两臂伸直,肘关节固定不屈,两手掌根相叠,手指 翘起,不接触伤员胸壁; b.以髋关节为支点,利用上身的重力,垂直将正常成人胸骨压陷3~5cm(儿童 和瘦弱者酌减);
c.压至要求程度后,立即全部放松,但放松时救护人员的掌根不得离开胸壁(见 图G6)。
图G5 正确的按压位置
图G6 按压姿势与用力方法
图G7 搬运伤员
(a)正常担架;(b)临时担架及木板;(c)错误搬运
按压必须有效,有效的标志是按压过程中可以触及颈动脉搏动。
G2.5.4.3 操作频率:
a.胸外按压要以均匀速度进行,每分钟80次左右,每次按压和放松的时间相 等;
b.胸外按压与口对口(鼻)人工呼吸同时进行,其节奏为:单人抢救时,每按压 15次后吹气2次(15∶2),反复进行;双人抢救时,每按压5次后由另一人吹气1次(5∶1),反复进行。
G2.6 抢救过程中的再判定:
G2.6.1 按压吹气1min后(相当于单人抢救时做了4个15∶2压吹循环),应用看、听、试方法在5~7s时间内完成对伤员呼吸和心跳是否恢复的再判定。
G2.6.2 若判定颈动脉已有搏动但无呼吸,则暂停胸外按压,而再进行2次口对口 人工呼吸,接着每5s吹气一次(即每分钟12次)。如脉搏和呼吸均未恢复,则继续 坚持心肺复苏法抢救。
G2.6.3 在抢救过程中,要每隔数分钟再判定一次,每次判定时间均不得超过5~ 7s。在医务人员未接替抢救前,现场抢救人员不得放弃现场抢救。
G2.7 抢救过程中伤员的移动与转院(见图G7):
G2.7.1 心肺复苏应在现场就地坚持进行,不要为方便而随意移动伤员,如确有需 要移动时,抢救中断时间不应超过30s。
G2.7.2 移动伤员或将伤员送医院时,除应使伤员平躺在担架上并在其背部垫以平硬阔木板,移动或送医院过程中应继续抢救,心跳呼吸停止者要继续心肺复苏法抢 救,在医务人员未接替救治前不能中止。
G2.7.3 应创造条件,用塑料袋装入砸碎冰屑作成帽状包绕在伤员头部,露出眼睛,使脑部温度降低,争取心肺脑完全复苏。
G2.8 伤员好转后的处理:
如伤员的心跳和呼吸经抢救后均已恢复,可暂停心肺复苏法操作。但心跳呼吸 恢复的早期有可能再次骤停,应严密监护,不能麻痹,要随时准备再次抢救。
初期恢复后,神志不清或精神恍惚、躁动,应设法使伤员安静。
G2.9 杆上或高处触电急救:
G2.9.1 发现杆上或高处有人触电,应争取时间及早在杆上或高处开始进行抢救。救护人员登高时应随身携带必要的工具和绝缘工具以及牢固的绳索等,并紧急呼 救。
G2.9.2 救护人员应在确认触电者已与电源隔离,且救护人员本身所涉环境安全距 离内无危险电源时,方能接触伤员进行抢救,并应注意防止发生高空坠落的可能 性。
图G8 杆上或高处触电下放方法
G2.9.3 高处抢救:
G2.9.3.1 触电伤员脱离电源后,应将伤员扶卧在自己的安全带上(或在适当地方躺平),并注意保持伤员气道通畅。
G2.9.3.2 救护人员迅速按G2.3和G2.4条规定判定反应、呼吸和循环情况。
G2.9.3.3 如伤员呼吸停止,立即口对口(鼻)吹气2次,再测试颈动脉,如有搏动,则每5s继续吹气一次,如颈动脉无搏动时,可用空心拳头叩击心前区2次,促使 心脏复跳。
G2.9.3.4 高处发生触电,为使抢救更为有效,应及早设法将伤员送至地面。在完 成上述措施后,应立即用绳索参照图G8所示方法迅速将伤员送至地面,或采取可能 的迅速有效措施送至平台上。
G2.9.3.5 在将伤员由高处送至地面前,应再口对口(鼻)吹气4次。
G2.9.3.6 触电伤员送至地面后,应立即继续按心肺复苏法坚持抢救。
G2.10 现场触电抢救,对采用肾上腺素等药物应持慎重态度。如没有必要的诊断 设备条件和足够的把握,不得乱用。在医院内抢救触电者时,由医务人员经医疗仪 器设备诊断,根据诊断结果决定是否采用。
G3 创伤急救
G3.1 创伤急救的基本要求。
G3.1.1 创伤急救原则上是先抢救,后固定,再搬运,并注意采取措施,防止伤情 加重或污染。需要送医院救治的,应立即做好保护伤员措施后送医院救治。
G3.1.2 抢救前先使伤员安静躺平,判断全身情况和受伤程度,如有无出血、骨折 和休克等。
G3.1.3 外部出血立即采取止血措施,防止失血过多而休克。外观无伤,但呈休克 状态,神志不清,或昏迷者,要考虑胸腹部内脏或脑部受伤的可能性。
G3.1.4 为防止伤口感染,应用清洁布片覆盖。救护人员不得用手直接接触伤口,更不得在伤口内填塞任何东西或随便用药。
图G9 止血带
G3.1.5 搬运时应使伤员平躺在担架上,腰部束在担架上,防止跌下。平地搬运时 伤员头部在后,上楼、下楼、下坡时头部在上,搬运中应严密观察伤员,防止伤情突 变。
G3.2 止血
G3.2.1 伤口渗血:
用较伤口稍大的消毒纱布数层覆盖伤口,然后进行包扎。若包扎后仍有较多渗 血,可再加绷带适当加压止血。
G3.2.2 伤口出血呈喷射状或鲜红血液涌出时,立即用清洁手指压迫出血点上方(近心端),使血流中断,并将出血肢体抬高或举高,以减少出血量。
G3.2.3 用止血带或弹性较好的布带等止血时(图G9),应先用柔软布片或伤员的衣 袖等数层垫在止血带下面,再扎紧止血带以刚使肢端动脉搏动消失为度。上肢每 60min,下肢每80min放松一次,每次放松1~2min。开始扎紧与每次放松的时 间均应书面标明在止血带旁。扎紧时间不宜超过4h。不要在上臂中三分之一处和 窝下使用止血带,以免损伤神经。若放松时观察已无大出血可暂停使用。
严禁用电线、铁丝、细绳等作止血带使用。
G3.2.4 高处坠落、撞击、挤压可能有胸腹内脏破裂出血。受伤者外观无出血但常 表现面色苍白,脉搏细弱,气促,冷汗淋漓,四肢厥冷,烦躁不安,甚至神志不清等 休克状态,应迅速躺平,抬高下肢(图G10),保持温暖,速送医院救治。若送院途 中时间较长,可给伤员饮用少量糖盐水。
G3.3 骨折急救
G3.3.1 肢体骨折可用夹板或木棍、竹竿等将断骨上、下方两个关节固定(图G11),也可利用伤员身体进行固定,避免骨折部位移动,以减少疼痛,防止伤势恶化。
图G10 抬高下肢
图G11 骨折固定方法
(a)上肢骨折固定;(b)下肢骨折固定
开放性骨折,伴有大出血者,先止血,再固定,并用干净布片覆盖伤口,然后 速送医院救治。切勿将外露的断骨推回伤口内。
G3.3.2 疑有颈椎损伤,在使伤员平卧后,用沙土袋(或其它代替物)放置头部两侧(图 G12)使颈部固定不动。必须进行口对口呼吸时,只能采用抬颏使气道通畅,不能再 将头部后仰移动或转动头部,以免引起截瘫或死亡。
G3.3.3 腰椎骨折应将伤员平卧在平硬木板上,并将腰椎躯干及二侧下肢一同进行 固定预防瘫痪(图G13)。搬动时应数人合作,保持平稳,不能扭曲。
图G12 颈椎骨折固定
图G13 腰椎骨折固定
G3.4 颅脑外伤
G3.4.1 应使伤员采取平卧位,保持气道通畅,若有呕吐,应扶好头部和身体,使 头部和身体同时侧转,防止呕吐物造成窒息。
G3.4.2 耳鼻有液体流出时,不要用棉花堵塞,只可轻轻拭去,以利降低颅内压力。也不可用力擤鼻,排除鼻内液体,或将液体再吸入鼻内。
G3.4.3 颅脑外伤时,病情可能复杂多变,禁止给予饮食,速送医院诊治。
G3.5 烧伤急救 G3.5.1 电灼伤、火焰烧伤或高温气、水烫伤均应保持伤口清洁。伤员的衣服鞋袜 用剪刀剪开后除去。伤口全部用清洁布片覆盖,防止污染。四肢烧伤时,先用清洁冷 水冲洗,然后用清洁布片或消毒纱布覆盖送医院。
G3.5.2 强酸或碱灼伤应立即用大量清水彻底冲洗,迅速将被侵蚀的衣物剪去。为 防止酸、碱残留在伤口内,冲洗时间一般不少于10min。
G3.5.3 未经医务人员同意,灼伤部位不宜敷搽任何东西和药物。
G3.5.4 送医院途中,可给伤员多次少量口服糖盐水。
G3.6 冻伤急救
G3.6.1 冻伤使肌肉僵直,严重者深及骨骼,在救护搬运过程中动作要轻柔,不要 强使其肢体弯曲活动,以免加重损伤,应使用担架,将伤员平卧并抬至温暖室内 救治。
G3.6.2 将伤员身上潮湿的衣服剪去后用干燥柔软的衣服覆盖,不得烤火或搓雪。
G3.6.3 全身冻伤者呼吸和心跳有时十分微弱,不应误认为死亡,应努力抢救。
G3.7 动物咬伤急救
G3.7.1 毒蛇咬伤后,不要惊慌、奔跑、饮酒,以免加速蛇毒在人体内扩散。
G3.7.1.1 咬伤大多在四肢,应迅速从伤口上端向下方反复挤出毒液,然后在伤口 上方(近心端)用布带扎紧,将伤肢固定,避免活动,以减少毒液的吸收。
G3.7.1.2 有蛇药时可先服用,再送往医院救治。
G3.7.2 犬咬伤
G3.7.2.1 犬咬伤后应立即用浓肥皂水冲洗伤口,同时用挤压法自上而下将残留伤 口内唾液挤出,然后再用碘酒涂搽伤口。
G3.7.2.2 少量出血时,不要急于止血,也不要包扎或缝合伤口。
G3.7.2.3 尽量设法查明该犬是否为“疯狗”,对医院制订治疗计划有较大帮助。
G3.8 溺水急救
G3.8.1 发现有人溺水应设法迅速将其从水中救出,呼吸心跳停止者用心肺复苏法 坚持抢救。曾受水中抢救训练者在水中即可抢救。
G3.8.2 口对口人工呼吸因异物阻塞发生困难,而又无法用手指除去时,可用两手 相叠,置于脐部稍上正中线上(远离剑突)迅速向上猛压数次,使异物退出,但也不 可用力太大。
G3.8.3 溺水死亡的主要原因是窒息缺氧。由于淡水在人体内能很快经循环吸收,而气管能容纳的水量很少,因此在抢救溺水者时不应“倒水”而延误抢救时间,更 不应仅“倒水”而不用心肺复苏法进行抢救。
G3.9 高温中暑急救
G3.9.1 烈日直射头部,环境温度过高,饮水过少或出汗过多等可以引起中暑现 象,其症状一般为恶心、呕吐、胸闷、眩晕、嗜睡、虚脱,严重时抽搐、惊厥甚 至昏迷。
G3.9.2 应立即将病员从高温或日晒环境转移到阴凉通风处休息。用冷水擦浴,湿 毛巾覆盖身体,电扇吹风,或在头部置冰袋等方法降温,并及时给病人口服盐水。严重者送医院治疗。
G3.10 有害气体中毒急救
G3.10.1 气体中毒开始时有流泪、眼痛、呛咳、咽部干燥等症状,应引起警惕。稍重时头痛、气促、胸闷、眩晕。严重时会引起惊厥昏迷。
G3.10.2 怀疑可能存在有害气体时,应即将人员撤离现场,转移到通风良好处休 息。抢救人员进入险区必须带防毒面具。
G3.10.3 已昏迷病员应保持气道通畅,有条件时给予氧气吸入。呼吸心跳停止者,按心肺复苏法抢救,并联系医院救治。
G3.10.4 迅速查明有害气体的名称,供医院及早对症治疗。
附 录 H
SF6新所暂行标准
(补充件)
_______________________
附加说明:
本标准由能源部安全环保司提出。
本标准由能源部安全环保司归口。
本标准由能源部安全环保司负责起草,全国有关电管局、电力局等参加。
本标准主要起草人:徐余文、蔡树人、陈祖嘉、陈其祥、柏克寒。
第四篇:新电业安全工作规程(发电厂、变电所电气部分)
《新电业安全工作规程》(发电厂、变电所电气部分)
《新电业安全工作规程》(发电厂、变电所电气部分)
目
录 总
则 高压设备工作的基本要求 2.1一般安全要求 2.2 高压设备的巡视 2.3 倒闸操作 2.4 高压设备上工作 3 保证安全的组织措施
3.1 在电气设备上工作,保证安全的组织措施 3.2 工作票制度 3.3 工作许可制度 3.4 工作监护制度
3.5 工作间断、转移和终结制度 4 保证安全的技术措施
4.1 在电气设备上工作,保证安全的技术措施 4.2 停电 4.3 验电 4.4接地
4.5 悬挂标示牌和装设遮栏(围栏)5 线路作业时变电站和发电厂的安全措施 6 带电作业 6.1 一般规定
6.2 一般安全技术措施 6.3 等电位作业 6.4 带电断、接引线 6.5 带电短接设备 6.6 带电水冲洗 6.7 带电清扫机械作业 6.8 感应电压防护 6.9 高架绝缘斗臂车作业 6.10 保护间隙 6.11 带电检测绝缘子 6.12 低压带电作业
6.13 带电作业工具的保管、使用和试验 发电机、同期调相机和高压电动机的检修、维护工作 8 在六氟化硫电气设备上的工作 在停电的低压配电装置和低压导线上的工作 10二次系统上的工作 11 电气试验 11.1 高压试验
11.2 使用携带型仪器的测量工作 11.3 用钳形电流表的测量工作 11.4 使用摇表测量绝缘的工作 12 电力电缆工作
12.1 电力电缆工作的基本要求 12.2 电力电缆作业时的安全措施 13 一般安全措施
附录1 变电站(发电厂)倒闸操作票格式 附录2 变电站(发电厂)第一种工作票格式 附录3 电力电缆第一种工作票格式 附录4 变电站(发电厂)第二种工作票格式 附录5 电力电缆第二种工作票格式
附录6 变电站(发电厂)带电作业工作票格式 附录7 变电站(发电厂)事故应急抢修单格式 附录8 二次工作安全措施票格式 附录9 标示牌式样
附录10 绝缘安全工器具试验项目、周期和要求 附录11 带电作业高架绝缘斗臂车电气试验标准表 附录12 登高工器具试验项目、周期和要求 附录13 紧急救护法
《新电业安全工作规程》(发电厂、变电所电气部分)总则
1.1 为加强电力生产现场管理,规范各类工作人员的行为,保证人身、电网和设备安全,依据国家有关法律、法规,结合电力生产的实际,制定本规程。1.2 作业现场的基本条件
1.2.1作业现场的生产条件和安全设施等应符合有关标准、规范的要求,工作人员的劳动防护用品应合格、齐备。
1.2.2 经常有人工作的场所及施工车辆上宜配备急救箱,存放急救用品,并应指定专人经常检查、补充或更换。
1.2.3 现场使用的安全工器具应合格并符合有关要求。
1.2.4 各类作业人员应被告知其作业现场和工作岗位存在的危险因素、防范措施及事故紧急处理措施。1.3 作业人员的基本条件
1.3.1经医师鉴定,无妨碍工作的病症(体格检查每两年至少一次)。1.3.2 具备必要的电气知识和业务技能,且按工作性质,熟悉本规程的相关部分,并经考试合格。
1.3.3 具备必要的安全生产知识,学会紧急救护法,特别要学会触电急救。1.4 教育和培训
1.4.1 各类作业人员应接受相应的安全生产教育和岗位技能培训,经考试合格上岗。
1.4.2 作业人员对本规程应每年考试一次。因故间断电气工作连续三个月以上者,应重新学习本规程,并经考试合格后,方能恢复工作。
1.4.3 新参加电气工作的人员、实习人员和临时参加劳动的人员(管理人员、临时工等),应经过安全知识教育后,方可下现场参加指定的工作,并且不得单独工作。
1.4.4外单位承担或外来人员参与公司系统电气工作的工作人员应熟悉本规程、并经考试合格,方可参加工作。工作前,设备运行管理单位应告知现场电气设备接线情况、危险点和安全注意事项。
1.5任何人发现有违反本规程的情况,应立即制止,经纠正后才能恢复作业。各类作业人员有权拒绝违章指挥和强令冒险作业;在发现直接危及人身、电网和设备安全的紧急情况时,有权停止作业或者在采取可能的紧急措施后撤离作业场所,并立即报告。
1.6 在试验和推广新技术、新工艺、新设备、新材料的同时,应制定相应的安全措施,经本单位总工程师批准后执行。1.7 电气设备分为高压和低压两种:
高压电气设备:对地电压在1000V及以上者; 低压电气设备:对地电压在1000V以下者。
1.8 本规程适用于运用中的发、输、变、配电和用户电气设备上的工作人员(包括基建安装、农电人员),其他单位和相关人员参照执行。所谓运用中的电气设备,系指全部带有电压、一部分带有电压或一经操作即带有电压的电气设备。
各单位可根据现场情况制定本规程补充条款和实施细则,经本单位主管生产的领导(总工程师)批准后执行。
高压设备工作的基本要求 2.1 一般安全要求
2.1.1 运行人员应熟悉电气设备。单独值班人员或运行值班负责人还应有实际工作经验。
2.1.2 高压设备符合下列条件者,可由单人值班或单人操作:
1)室内高压设备的隔离室设有遮栏,遮栏的高度在1.7m以上,安装牢固并加锁者;
2)室内高压断路器(开关)的操作机构用墙或金属板与该断路器(开关)隔离或装有远方操作机构者。
2.1.3 无论高压设备是否带电,工作人员不得单独移开或越过遮栏进行工作;若有必要移开遮栏时,必须有监护人在场,并符合表2-1的安全距离。表2-1 设备不停电时的安全距离 电压等级(kV)
安全距离(m)10及以下(13.8)
0.70 20、35
1.00 63(66)、110
1.50 220
3.00 330
4.00 500
5.00 注:表2-1中未列电压按高一档电压等级的安全距离
2.1.4 10 kV、20kV、35 kV配电装置的裸露部分在跨越人行过道或作业区时,若导电部分对地高度分别小于2.7m、2.8m、2.9m,该裸露部分两侧和底部须装设护网。
2.1.5 户外35kV及以上高压配电装置场所的行车通道上,应根据表2-2设置行车安全限高标志。
表2-2 车辆(包括装载物)外廓至无遮栏带电部分之间的安全距离 电压等级(kV)安全距离(m)
1.15 63(66)
1.40 110
1.65(1.75 注)220
2.55 330
3.25 500
4.55 注:括号内数字为110kV中性点不接地系统所使用。2.1.6 室内母线分段部分、母线交*部分及部分停电检修易误碰有电设备的,应设有明显标志的永久性隔离挡板(护网)。
2.1.7 待用间隔(母线连接排、引线已接上母线的备用间隔)应有名称、编号,并列入调度管辖范围。其隔离开关(刀闸)操作手柄、网门必须加锁。2.1.8 在手车开关拉出后,必须观察隔离挡板是否可*封闭。封闭式组合电器引出电缆备用孔或母线的终端备用孔必须用专用器具封闭。
2.1.9 运行中的高压设备其中性点接地系统的中性点应视作带电体。2.2 高压设备的巡视
2.2.1 经本单位批准允许单独巡视高压设备的人员巡视高压设备时,不得进行其他工作,不得移开或越过遮栏。
2.2.2 雷雨天气,需要巡视室外高压设备时,应穿绝缘靴,并不得*近避雷器和避雷针。
2.2.3 火灾、地震、台风、洪水等灾害发生时,如要对设备进行巡视时,应得到设备运行管理单位有关领导批准,巡视人员应与派出部门之间保持通讯联络。2.2.4 高压设备发生接地时,室内不得接近故障点4m以内,室外不得接近故障点8m以内。进入上述范围人员必须穿绝缘靴,接触设备的外壳和构架时,应戴绝缘手套。
2.2.5 巡视配电装置,进出高压室,必须随手关门。
2.2.6 高压室的钥匙至少应有三把,由运行人员负责保管,按值移交。一把专供紧急时使用,一把专供运行人员使用,其它可以借给经批准的巡视高压设备人员和经批准的检修、施工队伍的工作负责人使用,但应登记签名,巡视或当日工作结束后交还。2.3 倒闸操作
2.3.1 倒闸操作必须根据值班调度员或运行值班负责人的指令,受令人复诵无误后执行。发布指令应准确、清晰,使用规范的调度术语和设备双重名称,即设备名称和编号。发令人和受令人应先互报单位和姓名,发布指令的全过程(包括对方复诵指令)和听取指令的报告时双方都要录音并作好记录。操作人员(包括监护人)应了解操作目的和操作顺序。对指令有疑问时应向发令人询问清楚无误后执行。
2.3.2 倒闸操作可以通过就地操作、遥控操作、程序操作完成。遥控操作、程序操作的设备必须满足有关技术条件。2.3.3 倒闸操作的分类
2.3.3.1 监护操作:由两人进行同一项的操作。
监护操作时,其中一人对设备较为熟悉者作监护。特别重要和复杂的倒闸操作,由熟练的运行人员操作,运行值班负责人监护。2.3.3.2 单人操作:由一人完成的操作。
1)单人值班的变电站操作时,运行人员根据发令人用电话传达的操作指令填用操作票,复诵无误。
2)实行单人操作的设备、项目及运行人员需经设备运行管理单位批准,人员应通过专项考核。
2.3.3.3检修人员操作:由检修人员完成的操作。
1)经设备运行管理单位考试合格、批准的本企业的检修人员,可进行 220kV及以下的电气设备由热备用至检修或由检修至热备用的监护操作,监护人应是同一单位的检修人员或设备运行人员。
2)检修人员进行操作的接、发令程序及安全要求应由设备运行管理单位总工程师(技术负责人)审定,并报相关部门和调度机构备案。2.3.4 操作票
2.3.4.1 倒闸操作由操作人员填用操作票(见附录1)。
2.3.4.2 操作票应用钢笔或圆珠笔逐项填写。用计算机开出的操作票应与手写格式一致;操作票票面应清楚整洁,不得任意涂改。操作人和监护人应根据模拟图或接线图核对所填写的操作项目,并分别签名,然后经运行值班负责人(检修人员操作时由工作负责人)审核签名。每张操作票只能填写一个操作任务。2.3.4.3 下列项目必须填入操作票内:
1)应拉合的设备[断路器(开关)、隔离开关(刀闸)、接地刀闸等],验电,装拆接地线,安装或拆除控制回路或电压互感器回路的保险器,切换保护回路和自动化装置及检验是否确无电压等;
2)拉合设备[断路器(开关)、隔离开关(刀闸)、接地刀闸等]后检查设备的位置; 3)进行停、送电操作时,在拉、合隔离开关(刀闸)、手车式开关拉出、推入前,检查断路器(开关)确在分闸位置;
4)在进行倒负荷或解、并列操作前后,检查相关电源运行及负荷分配情况; 5)设备检修后合闸送电前,检查送电范围内接地刀闸已拉开,接地线已拆除。2.3.4.4 操作票应填写设备的双重名称。2.3.5 倒闸操作的基本条件
2.3.5.1 有与现场一次设备和实际运行方式相符的一次系统模拟图(包括各种电子接线图)。
2.3.5.2 操作设备应具有明显的标志,包括:命名、编号、分合指示,旋转方向、切换位置的指示及设备相色等。
2.3.5.3 高压电气设备都应安装完善的防误操作闭锁装置。防误闭锁装置不得随意退出运行,停用防误闭锁装置应经本单位总工程师批准;短时间退出防误闭锁装置时,应经变电站站长或发电厂当班值长批准,并应按程序尽快投入。2.3.5.4 有值班调度员、运行值班负责人正式发布的指令(规范的操作术语),并使用经事先审核合格的操作票。
2.3.5.5 下列三种情况必须加挂机械锁:
1)未装防误闭锁装置或闭锁装置失灵的刀闸手柄和网门;
2)当电气设备处于冷备用时,网门闭锁失去作用时的有电间隔网门; 3)设备检修时,回路中的各来电侧刀闸操作手柄和电动操作刀闸机构箱的箱门。机械锁要一把钥匙开一把锁,钥匙要编号并妥善保管。2.3.6 倒闸操作的基本要求
2.3.6.1停电拉闸操作必须按照断路器(开关)——负荷侧隔离开关(刀闸)——电源侧隔离开关(刀闸)的顺序依次进行,送电合闸操作应按与上述相反的顺序进行。严禁带负荷拉合隔离开关(刀闸)。
2.3.6.2 开始操作前,应先在模拟图(或微机防误装置、微机监控装置)上进行核对性模拟预演,无误后,再进行操作。操作前应先核对设备名称、编号和位置,操作中应认真执行监护复诵制度(单人操作时也必须高声唱票),宜全过程录音。操作过程中必须按操作票填写的顺序逐项操作。每操作完一步,应检查无误后做一个“√”记号,全部操作完毕后进行复查。
2.3.6.3 监护操作时,操作人在操作过程中不得有任何未经监护人同意的操作行为。
2.3.6.4 操作中发生疑问时,应立即停止操作并向发令人报告。待发令人再行许可后,方可进行操作。不准擅自更改操作票,不准随意解除闭锁装置。解锁工具(钥匙)必须封存保管,所有操作人员和检修人员严禁擅自使用解锁工具(钥匙)。若遇特殊情况,必须经值班调度员、值长或站长批准,方能使用解锁工具(钥匙)。单人操作、检修人员在倒闸操作过程中严禁解锁。如需解锁,必须待增派运行人员到现场后,履行批准手续后处理。解锁工具(钥匙)使用后应及时封存。2.3.6.5 用绝缘棒拉合隔离开关(刀闸)或经传动机构拉合断路器(开关)和隔离开关(刀闸),均应戴绝缘手套。雨天操作室外高压设备时,绝缘棒应有防雨罩,还应穿绝缘靴。接地网电阻不符合要求的,晴天也应穿绝缘靴。雷电时,一般不进行倒闸操作,禁止在就地进行倒闸操作。
2.3.6.6 装卸高压保险器,应戴护目眼镜和绝缘手套,必要时使用绝缘夹钳,并站在绝缘垫或绝缘台上。
2.3.6.7 断路器(开关)遮断容量应满足电网要求。如遮断容量不够,应将操作机构用墙或金属板与该断路器(开关)隔开,必须进行远方操作,重合闸装置必须停用。
2.3.6.8 电气设备停电后(包括事故停电),在未拉开有关隔离开关(刀闸)和做好安全措施前,不得触及设备或进入遮栏,以防突然来电。2.3.6.9 单人操作时不得进行登高或登杆操作。
2.3.6.10电气设备操作后的位置检查应以设备实际位置为准,无法看到实际位置时,可通过设备机械位置指示、电气指示、仪表及各种遥测、遥信信号的变化,且至少应有两个及以上指示已同时发生对应变化,才能确认该设备已操作到位。2.3.6.11 在发生人身触电事故时,为了抢救触电人,可以不经许可,即行断开有关设备的电源,但事后应立即报告调度和上级部门。2.3.7 下列各项工作可以不用操作票: 1)事故应急处理;
2)拉合断路器(开关)的单一操作;
3)拉开或拆除全站(厂)唯一的一组接地刀闸或接地线。
上述操作在完成后应作好记录,事故应急处理应保存原始记录。
2.3.8 同一变电站的操作票应事先连续编号,计算机生成的操作票应在正式出票前连续编号,操作票按编号顺序使用。作废的操作票,应注明“作废”字样,未执行的应注明“未执行”字样,已操作的应注明“已执行”字样。操作票应保存一年。
2.4 高压设备上工作
2.4.1 在运用中的高压设备上工作,分为三类:
2.4.1.1 全部停电的工作,系指室内高压设备全部停电(包括架空线路与电缆引入线在内),并且通至邻接高压室的门全部闭锁,以及室外高压设备全部停电(包括架空线路与电缆引入线在内)。
2.4.1.2 部分停电的工作,系指高压设备部分停电,或室内虽全部停电,而通至邻接高压室的门并未全部闭锁。2.4.1.3 不停电工作系指:
1)工作本身不需要停电并且没有偶然触及导电部分的危险; 2)许可在带电设备外壳上或导电部分上进行的工作。
2.4.2 在高压设备上工作,应至少由两人进行,并完成保证安全的组织措施和技术措施。保证安全的组织措施
3.1 在电气设备上工作,保证安全的组织措施 3.1.1 工作票制度; 3.1.2 工作许可制度; 3.1.3 工作监护制度;
3.1.4 工作间断、转移和终结制度。3.2 工作票制度
3.2.1 在电气设备上的工作,应填用工作票或事故应急抢修单,其方式有下列6种:
3.2.1.1 填用变电站(发电厂)第一种工作票(见附录2)。3.2.1.2 填用电力电缆第一种工作票(见附录3)。
3.2.1.3 填用变电站(发电厂)第二种工作票(见附录4)。3.2.1.4 填用电力电缆第二种工作票(见附录5)。
3.2.1.5 填用变电站(发电厂)带电作业工作票(见附录6)。3.2.1.6 填用变电站(发电厂)事故应急抢修单(见附录7)。3.2.2 填用第一种工作票的工作为:
3.2.2.1 高压设备上工作需要全部停电或部分停电者。
3.2.2.2 二次系统和照明等回路上的工作,需要将高压设备停电者或做安全措施者。
3.2.2.3 高压电力电缆需停电的工作。
3.2.2.4 其他工作需要将高压设备停电或要做安全措施者。3.2.3 填用第二种工作票的工作为:
3.2.3.1 控制盘和低压配电盘、配电箱、电源干线上的工作。
3.2.3.2 二次系统和照明等回路上的工作,无需将高压设备停电者或做安全措施者。
3.2.3.3 转动中的发电机、同期调相机的励磁回路或高压电动机转子电阻回路上的工作。
3.2.3.4 非运行人员用绝缘棒和电压互感器定相或用钳型电流表测量高压回路的电流。
3.2.3.5 大于表2-1距离的相关场所和带电设备外壳上的工作以及无可能触及带电设备导电部分的工作。
3.2.3.6 高压电力电缆不需停电的工作。3.2.4 填用带电作业工作票的工作为:
带电作业或与邻近带电设备距离小于表2-1规定的工作。3.2.5 填用事故应急抢修单的工作为:
事故应急抢修可不用工作票,但应使用事故应急抢修单。3.2.6 工作票的填写与签发
3.2.6.1 工作票应使用钢笔或圆珠笔填写与签发,一式两份,内容应正确、清楚,不得任意涂改。如有个别错、漏字需要修改,应使用规范的符号,字迹应清楚。3.2.6.2 用计算机生成或打印的工作票应使用统一的票面格式,由工作票签发人审核无误,手工或电子签名后方可执行。
工作票一份应保存在工作地点,由工作负责人收执;另一份由工作许可人收执,按值移交。工作许可人应将工作票的编号、工作任务、许可及终结时间记入登记簿。
3.2.6.3一张工作票中,工作票签发人、工作负责人和工作许可人三者不得互相兼任。工作负责人可以填写工作票。
3.2.6.4 工作票由设备运行管理单位签发,也可由经设备运行管理单位审核且经批准的修试及基建单位签发。修试及基建单位的工作票签发人及工作负责人名单应事先送有关设备运行管理单位备案。第一种工作票在工作票签发人认为必要时可采用总工作票、分工作票,并同时签发。总工作票、分工作票的填用、许可等有关规定由单位主管生产的领导(总工程师)批准后执行。3.2.6.5供电单位或施工单位到用户变电站内施工时,工作票应由有权签发工作票的供电单位、施工单位或用户单位签发。3.2.7工作票的使用
3.2.7.1 一个工作负责人只能发给一张工作票,工作票上所列的工作地点,以一个电气连接部分为限。
如施工设备属于同一电压、位于同一楼层,同时停、送电,且不会触及带电导体时,则允许在几个电气连接部分使用一张工作票。开工前工作票内的全部安全措施应一次完成。
3.2.7.2 若一个电气连接部分或一个配电装置全部停电,则所有不同地点的工作,可以发给一张工作票,但要详细填明主要工作内容。几个班同时进行工作时,工作票可发给一个总的负责人,在工作班成员栏内,只填明各班的负责人,不必填写全部工作人员名单。
若至预定时间,一部分工作尚未完成,需继续工作而不妨碍送电者,在送电前,应按照送电后现场设备带电情况,办理新的工作票,布置好安全措施后,方可继续工作。
3.2.7.3 在几个电气连接部分上依次进行不停电的同一类型的工作,可以使用一张第二种工作票。
3.2.7.4 在同一变电站或发电厂升压站内,依次进行的同一类型的带电作业可以使用一张带电作业工作票。
3.2.7.5持线路或电缆工作票进入变电站或发电厂升压站进行架空线路、电缆等工作,应增填工作票份数,工作负责人应将其中一份工作票交变电站或发电厂工作许可人许可工作。
上述单位的工作票签发人和工作负责人名单应事先送有关运行单位备案。
3.2.7.6 需要变更工作班成员时,须经工作负责人同意,在对新工作人员进行安全交底手续后,方可进行工作。非特殊情况不得变更工作负责人,如确需变更工作负责人应由工作票签发人同意并通知工作许可人,工作许可人将变动情况记录在工作票上。工作负责人允许变更一次。原、现工作负责人应对工作任务和安全措施进行交接。
3.2.7.7 在原工作票的停电范围内增加工作任务时,应由工作负责人征得工作票签发人和工作许可人同意,并在工作票上增填工作项目。若需变更或增设安全措施者必须填用新的工作票,并重新履行工作许可手续。
3.2.7.8 变更工作负责人或增加工作任务,如工作票签发人无法当面办理,应通过电话联系,并在工作票登记簿和工作票上注明。
3.2.7.9 第一种工作票应在工作前一日预先送达运行人员,可直接送达或通过传真、局域网传送,但传真的工作票许可应待正式工作票到达后履行。临时工作可在工作开始前直接交给工作许可人。
第二种工作票和带电作业工作票可在进行工作的当天预先交给工作许可人。3.2.7.10 工作票有破损不能继续使用时,应补填新的工作票。3.2.8 工作票的有效期与延期
3.2.8.1 第一、二种工作票和带电作业工作票的有效时间,以批准的检修期为限。3.2.8.2 第一、二种工作票需办理延期手续,应在工期尚未结束以前由工作负责人向运行值班负责人提出申请(属于调度管辖、许可的检修设备,还应通过值班调度员批准),由运行值班负责人通知工作许可人给予办理。第一、二种工作票只能延期一次。
3.2.9工作票所列人员的基本条件 工作票的签发人应是熟悉人员技术水平、熟悉设备情况、熟悉本规程,并具有相关工作经验的生产领导人、技术人员或经本单位主管生产领导批准的人员。工作票签发人员名单应书面公布。
工作负责人应是具有相关工作经验,熟悉设备情况、熟悉工作班人员工作能力和本规程,经工区(所、公司)生产领导书面批准的人员。
工作许可人应是经工区(所、公司)生产领导书面批准的有一定工作经验的运行人员或经批准的检修单位的操作人员(进行该工作任务操作及做安全措施的人员);用户变、配电站的工作许可人应是持有效证书的高压电工。专责监护人应是具有相关工作经验,熟悉设备情况和本规程的人员。3.2.10 工作票所列人员的安全责任 3.2.10.1 工作票签发人: 1)工作必要性和安全性;
2)工作票上所填安全措施是否正确完备;
3)所派工作负责人和工作班人员是否适当和充足。3.2.10.2 工作负责人(监护人): 1)正确安全地组织工作;
2)负责检查工作票所列安全措施是否正确完备和工作许可人所做的安全措施是否符合现场实际条件,必要时予以补充;
3)工作前对工作班成员进行危险点告知,交待安全措施和技术措施,并确认每一个工作班成员都已知晓;
4)严格执行工作票所列安全措施;
5)督促、监护工作班成员遵守本规程、正确使用劳动防护用品和执行现场安全措施;
6)工作班成员精神状态是否良好,变动是否合适。3.2.10.3 工作许可人:
1)负责审查工作票所列安全措施是否正确、完备,是否符合现场条件; 2)工作现场布置的安全措施是否完善,必要时予以补充; 3)负责检查检修设备有无突然来电的危险;
4)对工作票所列内容即使发生很小疑问,也必须向工作票签发人询问清楚,必要时应要求作详细补充。3.2.10.4 专责监护人:
1)明确被监护人员和监护范围;
2)工作前对被监护人员交待安全措施,告知危险点和安全注意事项; 3)监督被监护人员遵守本规程和现场安全措施,及时纠正不安全行为。3.2.10.5 工作班成员:
1)熟悉工作内容、工作流程,掌握安全措施,明确工作中的危险点,并履行确认手续;
2)严格遵守安全规章制度、技术规程和劳动纪律,对自己在工作中的行为负责,互相关心工作安全,并监督本规程的执行和现场安全措施的实施; 3)正确使用安全工器具和劳动防护用品。3.3 工作许可制度
3.3.1 工作许可人在完成施工现场的安全措施后,还应完成以下手续,工作班方可开始工作:
3.3.1.1 会同工作负责人到现场再次检查所做的安全措施,对具体的设备指明实际的隔离措施,证明检修设备确无电压。
3.3.1.2 对工作负责人指明带电设备的位置和工作过程中的注意事项。3.3.1.3 和工作负责人在工作票上分别确认、签名。
3.3.2运行人员不得变更有关检修设备的运行接线方式。工作负责人、工作许可人任何一方不得擅自变更安全措施,工作中如有特殊情况需要变更时,应先取得对方的同意。变更情况及时记录在值班日志内。3.4 工作监护制度
3.4.1工作票许可手续完成后,工作负责人、专责监护人应向工作班成员交待工作内容、人员分工、带电部位和现场安全措施,进行危险点告知,并履行确认手续,工作班方可开始工作。工作负责人、专责监护人应始终在工作现场,对工作班人员的安全认真监护,及时纠正不安全的行为。
3.4.2 所有工作人员(包括工作负责人)不许单独进入、滞留在高压室内和室外高压设备区内。
若工作需要(如测量极性、回路导通试验等),而且现场设备允许时,可以准许工作班中有实际经验的一个人或几人同时在它室进行工作,但工作负责人应在事前将有关安全注意事项予以详尽的告知。
3.4.3 工作负责人在全部停电时,可以参加工作班工作。在部分停电时,只有在安全措施可*,人员集中在一个工作地点,不致误碰有电部分的情况下,方能参加工作。
工作票签发人或工作负责人,应根据现场的安全条件、施工范围、工作需要等具体情况,增设专责监护人和确定被监护的人员。专责监护人不得兼做其他工作。专责监护人临时离开时,必须通知被监护人员停止工作或离开工作现场,待专责监护人回来后方可恢复工作。
3.4.4 工作期间,工作负责人若因故暂时离开工作现场时,应指定能胜任的人员临时代替,离开前应将工作现场交待清楚,并告知工作班成员。原工作负责人返回工作现场时,也应履行同样的交接手续。若工作负责人必须长时间离开工作的现场时,应由原工作票签发人变更工作负责人,履行变更手续,并告知全体工作人员及工作许可人。原、现工作负责人应做好必要的交接。
3.5 工作间断、转移和终结制度
3.5.1 工作间断时,工作班人员应从工作现场撤出,所有安全措施保持不动,工作票仍由工作负责人执存,间断后继续工作,无需通过工作许可人。每日收工,应清扫工作地点,开放已封闭的通路,并将工作票交回运行人员。次日复工时,应得到工作许可人的许可,取回工作票,工作负责人必须重新认真检查安全措施是否符合工作票的要求,并召开现场站班会后,方可工作。若无工作负责人或专责监护人带领,工作人员不得进入工作地点。
3.5.2 在未办理工作票终结手续以前,任何人员不准将停电设备合闸送电。
在工作间断期间,若有紧急需要,运行人员可在工作票未交回的情况下合闸送电,但应先通知工作负责人,在得到工作班全体人员已经离开工作地点、可以送电的答复后方可执行,并应采取下列措施:
1)拆除临时遮栏、接地线和标示牌,恢复常设遮栏,换挂“止步,高压危险!”的标示牌;
2)必须在所有道路派专人守候,以便告诉工作班人员“设备已经合闸送电,不得继续工作”。守候人员在工作票未交回以前,不得离开守候地点。3.5.3 检修工作结束以前,若需将设备试加工作电压,应按下列条件进行: 1)全体工作人员撤离工作地点;
2)将该系统的所有工作票收回,拆除临时遮栏、接地线和标示牌,恢复常设遮栏; 3)应在工作负责人和运行人员进行全面检查无误后,由运行人员进行加压试验。工作班若需继续工作时,应重新履行工作许可手续。
3.5.4 在同一电气连接部分用同一工作票依次在几个工作地点转移工作时,全部安全措施由运行人员在开工前一次做完,不需再办理转移手续。但工作负责人在转移工作地点时,应向工作人员交待带电范围、安全措施和注意事项。
3.5.5 全部工作完毕后,工作班应清扫、整理现场。工作负责人应先周密地检查,待全体工作人员撤离工作地点后,再向运行人员交待所修项目、发现的问题、试验结果和存在问题等,并与运行人员共同检查设备状况、状态,有无遗留物件,是否清洁等,然后在工作票上填明工作结束时间。经双方签名后,表示工作终结。待工作票上的临时遮栏已拆除,标示牌已取下,已恢复常设遮栏,未拉开的接地线、接地刀闸已汇报调度,工作票方告终结。
3.5.6 只有在同一停电系统的所有工作票都已终结,并得到值班调度员或运行值班负责人的许可指令后,方可合闸送电。
3.5.7 已终结的工作票、事故应急抢修单应保存一年。4 保证安全的技术措施
4.1 在电气设备上工作,保证安全的技术措施 4.1.1 停电; 4.1.2 验电; 4.1.3 接地;
4.1.4 悬挂标示牌和装设遮栏(围栏)。
上述措施由运行人员或有权执行操作的人员执行。4.2 停电
4.2.1 工作地点,必须停电的设备如下: 4.2.1.1 检修的设备;
4.2.1.2 与工作人员在进行工作中正常活动范围的距离小于表4-1规定的设备; 4.2.1.3 在35kV及以下的设备处工作,安全距离虽大于表4-1规定,但小于表2-1规定,同时又无绝缘挡板、安全遮栏措施的设备;
4.2.1.4 带电部分在工作人员后面、两侧、上下,且无可*安全措施的设备; 4.2.1.5 其它需要停电的设备。
表4-1 工作人员工作中正常活动范围与带电设备的安全距离 电压等级(kV)
安全距离(m)10及以下(13.8)
0.35 20、35
0.60 63(66)、110
1.50 220
3.00 330
4.00 500
5.00 注:表4-1中未列电压按高一档电压等级的安全距离
4.2.2 检修设备停电,必须把各方面的电源完全断开(任何运用中的星形接线设备的中性点,必须视为带电设备)。禁止在只经断路器(开关)断开电源的设备上工作。必须拉开隔离开关(刀闸),手车开关必须拉至试验或检修位置,应使各方面有一个明显的断开点(对于有些设备无法观察到明显断开点的除外)。与停电设备有关的变压器和电压互感器,必须将设备各侧断开,防止向停电检修设备反送电。
4.2.3 检修设备和可能来电侧的断路器(开关)、隔离开关(刀闸)必须断开控制电源和合闸电源,隔离开关(刀闸)操作把手必须锁住,确保不会误送电。4.2.4 对难以做到与电源完全断开的检修设备,可以拆除设备与电源之间的电气连接。4.3 验电
4.3.1 验电时,应使用相应电压等级而且合格的接触式验电器,在装设接地线或合接地刀闸处对各相分别验电。验电前,应先在有电设备上进行试验,确证验电器良好;无法在有电设备上进行试验时可用高压发生器等确证验电器良好。如果在木杆、木梯或木架上验电,不接地线不能指示者,可在验电器绝缘杆尾部接上接地线,但应经运行值班负责人或工作负责人许可。
4.3.2 高压验电必须戴绝缘手套。验电器的伸缩式绝缘棒长度必须拉足,验电时手必须握在手柄处不得超过护环,人体必须与验电设备保持安全距离。雨雪天气时不得进行室外直接验电。
4.3.3 对无法进行直接验电的设备,可以进行间接验电。即检查隔离开关(刀闸)的机械指示位置、电气指示、仪表及带电显示装置指示的变化,且至少应有两个及以上指示已同时发生对应变化;若进行遥控操作,则必须同时检查隔离开关(刀闸)的状态指示、遥测、遥信信号及带电显示装置的指示进行间接验电。
330kV及以上的电气设备,可采用间接验电方法进行验电。
4.3.4 表示设备断开和允许进入间隔的信号、经常接入的电压表等,如果指示有电,则禁止在设备上工作。
4.4.1 装设接地线应由两人进行(经批准可以单人装设接地线的项目及运行人员除外)。
4.4.2 当验明设备确已无电压后,应立即将检修设备接地并三相短路。电缆及电容器接地前应逐相充分放电,星形接线电容器的中性点应接地,串联电容器及与整组电容器脱离的电容器应逐个放电,装在绝缘支架上的电容器外壳也应放电。4.4.3 对于可能送电至停电设备的各方面都必须装设接地线或合上接地刀闸,所装接地线与带电部分应考虑接地线摆动时仍符合安全距离的规定。
4.4.4 对于因平行或邻近带电设备导致检修设备可能产生感应电压时,必须加装接地线或工作人员使用个人保安线,加装的接地线应登录在工作票上,个人保安接地线由工作人员自装自拆。
4.4.5 在门型架构的线路侧进行停电检修,如工作地点与所装接地线的距离小于10m,工作地点虽在接地线外侧,也可不另装接地线。
4.4.6 检修部分若分为几个在电气上不相连接的部分[如分段母线以隔离开关(刀闸)或断路器(开关)隔开分成几段],则各段应分别验电接地短路。降压变电站全部停电时,应将各个可能来电侧的部分接地短路,其余部分不必每段都装设接地线或合上接地刀闸。
4.4.7 接地线、接地刀闸与检修设备之间不得连有断路器(开关)或熔断器。若由于设备原因,接地刀闸与检修设备之间连有断路器(开关),在接地刀闸和断路器(开关)合上后,必须有保证断路器(开关)不会分闸的措施。4.4.8 在配电装置上,接地线应装在该装置导电部分的规定地点,这些地点的油漆必须刮去,并划有黑色标记。所有配电装置的适当地点,均应设有与接地网相连的接地端,接地电阻必须合格。接地线应采用三相短路式接地线,若使用分相式接地线时,应设置三相合一的接地端。
4.4.9 装设接地线必须先接接地端,后接导体端,接地线必须接触良好,连接应可*。拆接地线的顺序与此相反。装、拆接地线均应使用绝缘棒和戴绝缘手套。人体不得碰触接地线或未接地的导线,以防止感应电触电。
4.4.10 成套接地线应用有透明护套的多股软铜线组成,其截面不得小于25mm2,同时应满足装设地点短路电流的要求。禁止使用其他导线作接地线或短路线。
接地线必须使用专用的线夹固定在导体上,严禁用缠绕的方法进行接地或短路。4.4.11 严禁工作人员擅自移动或拆除接地线。高压回路上的工作,需要拆除全部或一部分接地线后始能进行工作者[如测量母线和电缆的绝缘电阻,测量线路参数,检查断路器(开关)触头是否同时接触],如: 1)拆除一相接地线;
2)拆除接地线,保留短路线;
3)将接地线全部拆除或拉开接地刀闸。
上述工作必须征得运行人员的许可(根据调度员指令装设的接地线,必须征得调度员的许可),方可进行。工作完毕后立即恢复。
4.4.12 每组接地线均应编号,并存放在固定地点。存放位置亦应编号,接地线号码与存放位置号码应一致。
4.4.13 装、拆接地线,应做好记录,交接班时应交待清楚。4.5 悬挂标示牌和装设遮栏(围栏)
4.5.1 在一经合闸即可送电到工作地点的断路器(开关)和隔离开关(刀闸)的操作把手上,均应悬挂“禁止合闸,有人工作!”的标示牌(见附录9)。
如果线路上有人工作,应在线路断路器(开关)和隔离开关(刀闸)操作把手上悬挂“禁止合闸,线路有人工作!”的标示牌。
对由于设备原因,接地刀闸与检修设备之间连有断路器(开关),在接地刀闸和断路器(开关)合上后,在断路器(开关)操作把手上,应悬挂“禁止分闸!”的标示牌。
在显示屏上进行操作的断路器(开关)和隔离开关(刀闸)的操作处均应相应设置“禁止合闸,有人工作!”或“禁止合闸,线路有人工作!”以及“禁止分闸!”的标记。
4.5.2 部分停电的工作,安全距离小于表2-1规定距离以内的未停电设备,应装设临时遮栏,临时遮栏与带电部分的距离,不得小于表4-1的规定数值,临时遮栏可用干燥木材、橡胶或其他坚韧绝缘材料制成,装设应牢固,并悬挂“止步,高压危险!”的标示牌。
35kV及以下设备的临时遮栏,如因工作特殊需要,可用绝缘挡板与带电部分直接接触。但此种挡板必须具有高度的绝缘性能,并符合附录10要求。4.5.3 在室内高压设备上工作,应在工作地点两旁及对面运行设备间隔的遮栏(围栏)上和禁止通行的过道遮栏(围栏)上悬挂“止步,高压危险!”的标示牌。4.5.4 高压开关柜内手车开关拉出后,隔离带电部位的挡板封闭后禁止开启,并设置“止步,高压危险!”的标示牌。
4.5.5 在室外高压设备上工作,应在工作地点四周装设围栏,其出入口要围至临近道路旁边,并设有“从此进出!”的标示牌。工作地点四周围栏上悬挂适当数量的“止步,高压危险!”标示牌,标示牌必须朝向围栏里面。若室外配电装置的大部分设备停电,只有个别地点保留有带电设备而其他设备无触及带电导体的可能时,可以在带电设备四周装设全封闭围栏,围栏上悬挂适当数量的“止步,高压危险!”标示牌,标示牌必须朝向围栏外面。严禁越过围栏。
4.5.6 在工作地点设置“在此工作!”的标示牌。
4.5.7 在室外构架上工作,则应在工作地点邻近带电部分的横梁上,悬挂“止步,高压危险!”的标示牌。在工作人员上下铁架或梯子上,应悬挂“从此上下!”的标示牌。在邻近其他可能误登的带电架构上,应悬挂“禁止攀登,高压危险!”的标示牌。
4.5.8 严禁工作人员擅自移动或拆除遮栏(围栏)、标示牌。线路作业时变电站和发电厂的安全措施
5.1 线路的停、送电均应按照值班调度员或线路工作许可人的指令执行。严禁约时停、送电。停电时,必须先将该线路可能来电的所有断路器(开关)、线路隔离开关(刀闸)、母线隔离开关(刀闸)全部拉开,手车开关必须拉至试验或检修位置,验明确无电压后,在线路上所有可能来电的各端装设接地线或合上接地刀闸。在线路断路器(开关)和隔离开关(刀闸)操作把手上均应悬挂“禁止合闸,线路有人工作!”的标示牌,在显示屏上断路器(开关)和隔离开关(刀闸)的操作处均应设置“禁止合闸,线路有人工作!”的标记。
5.2 值班调度员或线路工作许可人必须将线路停电检修的工作班组数目、工作负责人姓名、工作地点和工作任务记入记录簿。
工作结束时,应得到工作负责人(包括用户)的工作结束报告,确认所有工作班组均已竣工,接地线已拆除,工作人员已全部撤离线路,并与记录簿核对无误后,方可下令拆除变电站或发电厂内的安全措施,向线路送电。
5.3 当用户管辖的线路要求停电时,应得到用户停送电联系人的书面申请经批准后方可停电,并做好安全措施。恢复送电,应接到原申请人的工作结束报告,作好录音并记录后方可进行。用户停送电联系人的名单应在调度和有关部门备案。6 带电作业 6.1 一般规定
6.1.1 本章的规定适用于在海拔1000m及以下交流10~500kV的高压架空电力线路、变电所(发电厂)电气设备上,采用等电位、中间电位和地电位方式进行的带电作业,以及低压带电作业。
在海拔1000m以上带电作业时,应根据作业区不同海拔高度,修正各类空气与固体绝缘的安全距离和长度、绝缘子片数等,编制带电作业现场安全规程,经本单位主管生产领导(总工程师)批准后执行。
6.1.2 带电作业应在良好天气下进行。如遇雷电(听见雷声、看见闪电)、雪雹、雨雾不得进行带电作业,风力大于5级时,一般不宜进行带电作业。在特殊情况下,必须在恶劣天气进行带电抢修时,应组织有关人员充分讨论并编制必要的安全措施,经本单位主管生产领导(总工程师)批准后方可进行。
6.1.3 对于比较复杂、难度较大的带电作业新项目和研制的新工具,应进行科学试验,确认安全可*,编制操作工艺方案和安全措施,并经本单位主管生产领导(总工程师)批准后,方可进行和使用。
6.1.4 参加带电作业的人员,应经专门培训,并经考试合格,企业书面批准后,方能参加相应的作业。带电作业工作票签发人和工作负责人、专责监护人应由具有带电作业实践经验的人员担任。
6.1.5 带电作业必须设专责监护人。监护人不得直接操作。监护的范围不得超过一个作业点。复杂或高杆塔作业必要时应增设(塔上)监护人。
6.1.6 带电作业工作票签发人或工作负责人认为有必要时,应组织有经验的人员到现场查勘,根据查勘结果作出能否进行带电作业的判断,并确定作业方法和所需工具以及应采取的措施。
6.1.7 带电作业有下列情况之一者应停用重合闸,并不得强送电: 6.1.7.1 中性点有效接地的系统中有可能引起单相接地的作业。6.1.7.2 中性点非有效接地的系统中有可能引起相间短路的作业。6.1.7.3 工作票签发人或工作负责人认为需要停用重合闸的作业。严禁约时停用或恢复重合闸。
6.1.8 带电作业工作负责人在带电作业工作开始前,应与值班调度员联系。需要停用重合闸的作业和带电断、接引线应由值班调度员履行许可手续。带电工作结束后应及时向值班调度员汇报。
6.1.9 在带电作业过程中如设备突然停电,作业人员应视设备仍然带电。工作负责人应尽快与调度联系,值班调度员未与工作负责人取得联系前不得强送电。6.2 一般安全技术措施
6.2.1 进行地电位带电作业时,人身与带电体间的安全距离不得小于表6-1的规定。35kV及以下的带电设备,不能满足表6-1规定的最小安全距离时,应采取可*的绝缘隔离措施。
表6-1 带电作业时人身与带电体的安全距离
电压等级(kV)
63(66)
220
330 500 距离
(m)
0.4 0.6 0.7
1.0 1.8(1.6)(1)2.2
3.4(3.2)(2)注:(1)因受设备限制达不到1.8m时,经单位主管生产领导(总工程师)批准,并采取必要的措施后,可采用括号内(1.6m)的数值。
(2)海拔500m以下,500kV取3.2 m值,但不适用于500kV紧凑型线路。海拔在500m~1000m时,500kV取3.4m值。
6.2.2 绝缘操作杆、绝缘承力工具和绝缘绳索的有效绝缘长度不得小于表6-2的规定。
表6-2 绝缘工具最小有效绝缘长度
电压等级(kV)有效绝缘长度(m)
绝缘操作杆
绝缘承力工具、绝缘绳索 10
0.7
0.4 35
0.9
0.6 63(66)
1.0
0.7 110
1.3
1.0 220
2.1
1.8 330
3.1
2.8 500
4.0
3.7 6.2.3带电作业不得使用非绝缘绳索(如棉纱绳、白棕绳、钢丝绳)。
6.2.4 带电更换绝缘子或在绝缘子串上作业,必须保证作业中良好绝缘子片数不得少于表6-3的规定。
表6-3
带电作业中良好绝缘子最少片数 电压等级(kV)35
63(66)
220
330
500 片数6.2.5 更换直线绝缘子串或移动导线的作业,当采用单吊线装置时,应采取防止导线脱落时的后备保护措施。
6.2.6 在绝缘子串未脱离导线前,拆、装*近横担的第一片绝缘子时,必须采用专用短接线或穿屏蔽服方可直接进行操作。
6.2.7 在市区或人口稠密的地区进行带电作业时,工作现场应设置围栏,派专人监护,严禁非工作人员入内。
6.2.8 非特殊需要,不应在跨越处下方或邻近有电力线路或其它弱电线路的档内进行带电架、拆线的工作。如需进行,则必须制订可*的安全技术措施,经本单位生产领导(总工程师)批准后,方可进行。6.3 等电位作业
6.3.1 等电位作业一般在63(66)kV及以上电压等级的电力线路和电气设备上进行。若须在35kV电压等级进行等电位作业时,应采取可*的绝缘隔离措施。10kV及以下电压等级的电力线路和电气设备上不得进行等电位作业。
6.3.2 等电位作业人员必须在衣服外面穿合格的全套屏蔽服(包括帽、衣裤、手套、袜和鞋),且各部分应连接良好。屏蔽服内还应穿着阻燃内衣。严禁通过屏蔽服断、接接地电流、空载线路和耦合电容器的电容电流。
6.3.3 等电位作业人员对地距离应不小于表6-1的规定,对相邻导线的距离应不小于表6-4的规定。
表6-4
等电位作业人员对邻相导线的最小距离
电压等级(kV)35 63(66)110 220 330 500 距离(m)
0.8 0.9
1.4 2.5
3.5 5.0 6.3.4 等电位作业人员在绝缘梯上作业或者沿绝缘梯进入强电场时,其与接地体和带电体两部分间隙所组成的组合间隙不得小于表6-5的规定。表6-5 等电位作业中的最小组合间隙
电压等级(kV)35 63(66)
220 330 500 距离(m)
0.7 0.8
1.2
2.1 3.1
4.0 6.3.5 等电位作业人员沿绝缘子串进入强电场的作业,一般在220 kV及以上电压等级的绝缘子串上进行。其组合间隙不得小于表6-5的规定。若不满足表6-5的规定,应加装保护间隙。扣除人体短接的和零值的绝缘子片数后,良好绝缘子片数不得小于表6-3的规定。
6.3.6 等电位作业人员在电位转移前,应得到工作负责人的许可。转移电位时,人体裸露部分与带电体的距离不应小于表6-6的规定。
表6-6 等电位作业转移电位时人体裸露部分与带电体的最小距离 电压等级(kV)
35、63(66)110、220330、500 距离(m)
0.2
0.3
0.4 6.3.7 等电位作业人员与地电位作业人员传递工具和材料时,必须使用绝缘工具或绝缘绳索进行,其有效长度不得小于表6-2的规定。
6.3.8 沿导、地线上悬挂的软、硬梯或飞车进入强电场的作业应遵守下列规定: 6.3.8.1 在连续档距的导、地线上挂梯(或飞车)时,其导、地线的截面不得小于:钢芯铝绞线和铝合金绞线120mm2;钢绞线50mm2(等同OPGW光缆和配套的LGJ-70/40导线)。
6.3.8.2 有下列情况之一者,应经验算合格,并经本单位主管生产领导(总工程师)批准后才能进行:
1)在孤立档的导、地线上的作业;
2)在有断股的导、地线和锈蚀的地线上的作业; 3)在6.3.8.1条以外的其它型号导、地线上的作业; 4)两人以上在同档同一根导、地线上的作业。
6.3.8.3 在导、地线上悬挂梯子、飞车进行等电位作业前,必须检查本档两端杆塔处导、地线的紧固情况。挂梯载荷后,应保持地线及人体对下方带电导线的安全间距比表6-1中的数值增大0.5m;带电导线及人体对被跨越的电力线路、通讯线路和其他建筑物的安全距离应比表6-1中的数值增大1m。
6.3.8.4 在瓷横担线路上严禁挂梯作业,在转动横担的线路上挂梯前应将横担固定。
6.3.9 等电位作业人员在作业中严禁用酒精、汽油等易燃品擦拭带电体及绝缘部分,防止起火。
6.4 带电断、接引线
6.4.1 带电断、接空载线路,必须遵守下列规定:
6.4.1.1 带电断、接空载线路时,必须确认线路的另一端断路器(开关)和隔离开关(刀闸)确已断开,接入线路侧的变压器、电压互感器确已退出运行后,方可进行。
严禁带负荷断、接引线。
6.4.1.2 带电断、接空载线路时,作业人员应戴护目镜,并应采取消弧措施。消弧工具的断流能力应与被断、接的空载线路电压等级及电容电流相适应。如使用消弧绳,则其断、接的空载线路的长度不应大于表6-7规定,且作业人员与断开点应保持4m以上的距离。
表6-7 使用消弧绳断、接空载线路的最大长度 电压等级(kV)35 63 110
220 长度(km)
30 20 10
注:线路长度包括分支在内,但不包括电缆线路。
6.4.1.3 在查明线路确无接地、绝缘良好、线路上无人工作且相位确定无误后,才可进行带电断、接引线。
6.4.1.4 带电接引线时未接通相的导线及带电断引线时,已断开相的导线将因感应而带电。为防止电击,应采取措施后人员才能触及。
6.4.1.5 严禁同时接触未接通的或已断开的导线两个断头,以防人体串入电路。6.4.2 严禁用断、接空载线路的方法使两电源解列或并列。
6.4.3 带电断、接耦合电容器时,应将其信号、接地刀闸合上并应停用高频保护。被断开的电容器应立即对地放电。
6.4.4 带电断、接空载线路、耦合电容器、避雷器、阻波器等设备引线时,应采取防止引流线摆动的措施。6.5 带电短接设备
6.5.1 用分流线短接断路器(开关)、隔离开关(刀闸)、跌落式熔断器(保险)等载流设备,必须遵守下列规定: 6.5.1.1 短接前一定要核对相位。
6.5.1.2 组装分流线的导线处必须清除氧化层,且线夹接触应牢固可*。
6.5.1.3 35kV及以下设备使用的绝缘分流线的绝缘水平应符合表6-13的规定。6.5.1.4 断路器(开关)必须处于合闸位置,并取下跳闸回路熔断器(保险),锁死跳闸机构后,方可短接。
6.5.1.5 分流线应支撑好,以防摆动造成接地或短路。
6.5.2 阻波器被短接前,严防等电位作业人员人体短接阻波器。
6.5.3 短接开关设备或阻波器的分流线截面和两端线夹的载流容量,应满足最大负荷电流的要求。6.6 带电水冲洗
6.6.1 带电水冲洗一般应在良好天气时进行。风力大于4级,气温低于-3℃,或雨天、雪天、沙尘暴、雾天及雷电天气时不宜进行。冲洗时,操作人员应戴绝缘手套、穿绝缘靴。
6.6.2 带电水冲洗作业前应掌握绝缘子的脏污情况,当盐密值大于表6-8最大临界盐密值的规定,一般不宜进行水冲洗,否则,应增大水电阻率来补救。避雷器及密封不良的设备不宜进行带电水冲洗。
表6-8 带电水冲洗临界盐密值1)(仅适用于220kV及以下)爬电比距2)(mm/kV)发电厂及变电所支柱绝缘子或密闭瓷套管 14.8~16(普通型)20~31(防污型)临界盐密值(mg/cm2)0.02 0.04 0.08 0.12 0.08 0.12 0.16 0.2 水电阻率(Ω·cm)1500 3000 10000 50000及以上 1500 3000 10000 50000及以上 爬电比距2)(mm/kV)线路悬式绝缘子 14.8~16(普通型)20~31(防污型)临界盐密值(mg/cm2)0.05 0.07 0.12 0.15 0.12 0.15 0.2 0.22 水电阻率(Ω·cm)1500 3000 10000 50000及以上 1500 3000 10000 50000及以上 注:1)330kV及以上等级的临界盐密值尚不成熟,暂不列入。
2)爬电比距指电力设备外绝缘的爬电距离与设备最高工作电压之比。6.6.3 带电水冲洗用水的电阻率一般不低于1500Ω·cm,冲洗220kV变电设备水电阻率不低于3000Ω·cm,并应符合表6-8的要求。每次冲洗前,都应用合格的水阻表测量水电阻率,应从水枪出口处取水样进行测量。如用水车等容器盛水,每车水都应测量水电阻率。
6.6.4 以水柱为主绝缘的大、中型水冲(喷嘴直径为4~8mm者称中水冲;直径为9mm及以上者称大水冲),其水枪喷嘴与带电体之间的水柱长度不得小于表6-9的规定。大、中型水枪喷嘴均应可*接地。
表6-9 喷嘴与带电体之间的水柱长度(m)喷嘴直径(mm)4~8 9~12 13~18 电压等级(kV)63(66)及以下 2 4 6 110 3 5 7 220 4 6 8 6.6.5 带电冲洗前应注意调整好水泵压强,使水柱射程远且水流密集。当水压不足时,不得将水枪对准被冲洗的带电设备。冲洗用水泵应良好接地。
6.6.6 带电水冲洗应注意选择合适的冲洗方法。直径较大的绝缘子宜采用双枪跟踪法或其它方法,并应防止被冲洗设备表面出现污水线。当被冲绝缘子未冲洗干净时,严禁中断冲洗,以免造成闪络。
6.6.7 带电水冲洗前要确知设备绝缘是否良好。有零值及低值的绝缘子及瓷质有裂纹时,一般不可冲洗。
6.6.8 冲洗悬垂、耐张绝缘子串、瓷横担时,应从导线侧向横担侧依次冲洗。冲洗支柱绝缘子及绝缘瓷套时,应从下向上冲洗。6.6.9 冲洗绝缘子时,应注意风向,必须先冲下风侧,后冲上风侧;对于上、下层布置的绝缘子应先冲下层,后冲上层。还要注意冲洗角度,严防临近绝缘子在溅射的水雾中发生闪络
6.7 带电清扫机械作业
6.7.1 进行带电清扫工作时,绝缘操作杆的有效长度不得小于表6-2的规定。6.7.2 在使用带电清扫机械进行清扫前,应确认:清扫机械工况(电机及控制部分、软轴及传动部分等)完好,绝缘部件无变形、脏污和损伤,毛刷转向正确,清扫机械已可*接地。
6.7.3 带电清扫作业人员应站在上风侧位置作业,应戴口罩、护目镜。
6.7.4 作业时,作业人的双手应始终握持绝缘杆保护环以下部位,并保持带电清扫有关绝缘部件的清洁和干燥。6.8 感应电压防护
6.8.1 在330kV及以上电压等级的线路杆塔上及变电所构架上作业,应采取防静电感应措施,例如,穿静电感应防护服、导电鞋等(220kV线路杆塔上作业时宜穿导电鞋)。
6.8.2 绝缘架空地线应视为带电体。在绝缘架空地线附近作业时,作业人员与绝缘架空地线之间的距离不应小于0.4m。如需在绝缘架空地线上作业应用接地线将其可*接地或采用等电位方式进行。
6.8.3 用绝缘绳索传递大件金属物品(包括工具、材料等)时,杆塔或地面上作业人员应将金属物品接地后再接触,以防电击。6.9 高架绝缘斗臂车作业
6.9.1 高架绝缘斗臂车应经检验合格。斗臂车操作人员应熟悉带电作业的有关规定,并经专门培训,考试合格、持证上岗。6.9.2 高架绝缘斗臂车的工作位置应选择适当,支撑应稳固可*,并有防倾覆措施。使用前应在预定位置空斗试操作一次,确认液压传动、回转、升降、伸缩系统工作正常、操作灵活,制动装置可*。
6.9.3 绝缘斗中的作业人员应正确使用安全带和绝缘工具。
6.9.4 高架绝缘斗臂车操作人员必须服从工作负责人的指挥,作业时应注意周围环境及操作速度。在工作过程中,高架绝缘斗臂车的发动机不应熄火。接近和离开带电部位时,应由斗臂中人员操作,但下部操作人员不得离开操作台。6.9.5 绝缘臂的有效绝缘长度应大于表6-10的规定,且应在下端装设泄漏电流监视装置。
表6-10 绝缘臂的最小有效绝缘长度
电压等级(kV)10 35、63(66)
220 长 度(m)
1.0
1.5
2.0
3.0 6.9.6 绝缘臂下节的金属部分,在仰起回转过程中,对带电体的距离应按表6-1的规定值增加0.5m。工作中车体应良好接地。6.10 保护间隙
6.10.1 保护间隙的接地线应用多股软铜线。其截面应满足接地短路容量的要求,但不得小于25 mm2。
6.10.2 圆弧形保护间隙的距离应按表6-11的规定进行整定。表6-11 圆弧形保护间隙整定值 电压等级(kV)
220
330 间隙距离(m)0.7~0.8 1.0~1.1 6.10.3 使用保护间隙时,应遵守下列规定:
6.10.3.1 悬挂保护间隙前,应与调度联系停用重合闸。
6.10.3.2 悬挂保护间隙应先将其与接地网可*接地,再将保护间隙挂在导线上,并使其接触良好。拆除的程序与其相反。
6.10.3.3 保护间隙应挂在相邻杆塔的导线上,悬挂后,应派专人看守,在有人、畜通过的地区,还应增设围栏。
6.10.3.4 装、拆保护间隙的人员应穿全套屏蔽服。6.11 带电检测绝缘子
6.11.1 使用火花间隙检测器检测绝缘子时,应遵守下列规定:
6.11.1.1 检测前应对检测器进行检测,保证操作灵活,测量准确。
6.11.1.2 针式及少于3片的悬式绝缘子不得使用火花间隙检测器进行检测。6.11.1.3 检测35kV及以上电压等级的绝缘子串时,当发现同一串中的零值绝缘子片数达到表6-12的规定时,应立即停止检测。表6-12
一串中允许零值绝缘子片数
电压等级(kV)35
63(66)110 220 330
500 绝缘子串片数
13 零值片数
如绝缘子串的片数超过表6-12的规定时,零值绝缘子允许片数可相应增加。6.11.1.4 应在干燥天气进行。6.12 低压带电作业
6.12.1 低压带电作业应设专人监护。6.12.2 使用有绝缘柄的工具,其外裸的导电部位应采取绝缘措施,防止操作时相间或相对地短路。工作时,应穿绝缘鞋和全棉长袖工作服,并戴手套、安全帽和护目镜,站在干燥的绝缘物上进行。严禁使用锉刀、金属尺和带有金属物的毛刷、毛掸等工具。
6.12.3 高低压同杆架设,在低压带电线路上工作时,应先检查与高压线的距离,采取防止误碰带电高压设备的措施。在低压带电导线未采取绝缘措施时,工作人员不得穿越。在带电的低压配电装置上工作时,应采取防止相间短路和单相接地的绝缘隔离措施。
6.12.4 上杆前,应先分清相、零线,选好工作位置。断开导线时,应先断开相线,后断开零线。搭接导线时,顺序应相反。人体不得同时接触两根线头。
6.13 带电作业工具的保管、使用和试验 6.13.1 带电作业工具的保管
6.13.1.1 带电作业工具应存放于通风良好,清洁干燥的专用工具房内。工具房门窗应密闭严实,地面、墙面及顶面应采用不起尘、阻燃材料制做。室内的相对湿度应保持在50%~70%。室内温度应略高于室外,且不宜低于0℃。
6.13.1.2 带电工具房进行室内通风时,必须在干燥的天气进行,并且室外的相对湿度不得高于75%。通风结束后,应立即检查室内的相对湿度,并加以调控。6.13.1.3 带电作业工具房应配备:湿度计、温度计,抽湿机(数量以满足要求为准),辐射均匀的加热器,足够的工具摆放架、吊架和灭火器等。
6.13.1.4 带电作业工具应统一编号、专人保管、登记造册,并建立试验、检修、使用记录。
6.13.1.5 有缺陷的带电作业工具应及时修复,不合格的应及时报废,严禁继续使用。
6.13.1.6 高架绝缘斗臂车应存放在干燥通风的车库内,其绝缘部分应有防潮措施。
6.13.2 带电作业工具的使用
6.13.2.1 带电作业工具应绝缘良好、联结牢固、转动灵活,并按厂家使用说明书、现场操作规程正确使用。
6.13.2.2 带电作业工具使用前应根据工作负荷校核满足规定安全系数。
6.13.2.3 带电作业工具在运输过程中,带电绝缘工具应装在专用工具袋、工具箱或专用工具车内,以防受潮和损伤。发现绝缘工具受潮或表面损伤、脏污时,应及时处理并经试验或检测合格后方可使用。
6.13.2.4 进入作业现场应将使用的带电作业工具放置在防潮的帆布或绝缘垫上,防止绝缘工具在使用中脏污和受潮。
6.13.2.5 带电作业工具使用前,仔细检查确认没有损坏、受潮、变形、失灵,否则禁止使用。并使用2500V及以上绝缘摇表或绝缘检测仪进行分段绝缘检测(电极宽2cm,极间宽2cm),阻值应不低于700MΩ。操作绝缘工具时应戴清洁、干燥的手套。
6.13.3 带电作业工具的试验
6.13.3.1 带电作业工具应定期进行电气试验及机械试验,其试验周期为:
电气试验:预防性试验每年一次,检查性试验每年一次,两次试验间隔半年。机械试验:绝缘工具每年一次,金属工具两年一次。6.13.3.2 绝缘工具电气预防性试验项目及标准见表6-13。表6-13 绝缘工具的试验项目及标准
额定电压(kV)试验长度(m)1min工频耐压(kV)5min工频耐压(kV)15次操作冲击耐压(kV)
出厂及型式试验 预防性试验 出厂及型式试验 预防性试验 出厂及型式试验 预防性试验 0.4 100 45 / / / / 35 0.6 150 95 / / / / 63(66)0.7 175 175 / / / / 110 1.0 250 220 / / / / 220 1.8 450 440 / / / / 330 2.8 / / 420 380 900 800 500 3.7 / / 640 580 1175 1050 操作冲击耐压试验宜采用250/2500μs的标准波,以无一次击穿、闪络为合格。工频耐压试验以无击穿、无闪络及过热为合格。高压电极应使用直径不小于30mm的金属管,被试品应垂直悬挂,接地极的对地距离为1.0~1.2m。接地极及接高压的电极(无金具时)处,以50mm宽金属铂缠绕。试品间距不小于500mm,单导线两侧均压球直径不小于200mm,均压球距试品不小于1.5m。
试品应整根进行试验,不得分段。
6.13.3.3 绝缘工具的检查性试验条件是:将绝缘工具分成若干段进行工频耐压试验,每300mm耐压75kV,时间为1min,以无击穿、闪络及过热为合格。6.13.3.4 带电作业高架绝缘斗臂车电气试验标准见附录11 6.13.3.5 组合绝缘的水冲洗工具应在工作状态下进行电气试验。除按表6-13的项目和标准试验外(指220 kV及以下电压等级),还应增加工频泄漏试验,试验电压见表6-14。泄漏电流以不超过1mA为合格。试验时间5min。
试验时的水电阻率为1500Ω·cm(适用于220 kV及以下的电压等级)。表6-14 组合绝缘的水冲洗工具工频泄漏试验电压值 额定电压(kV)10 35 63(66)110 220 试验电压(kV)15 46 80 110 220 6.13.3.6 屏蔽服衣裤任意两端点之间的电阻值均不得大于20Ω。6.13.3.7 带电作业工具的机械试验标准:
1)在工作负荷状态承担各类线夹和连接金具荷重时,应按有关金具标准进行试验;
2)在工作负荷状态承担其他静荷载时,应根据设计荷载,按SD165“《电力建设施工机具设计基本要求》(输电线路施工机具篇)”的规定进行试验; 3)在工作负荷状态承担人员操作荷载时:
静荷重试验:2.5倍允许工作负荷下持续5min,工具无变形及损伤者为合格。动荷重试验:1.5倍允许工作负荷下实际操作3次,工具灵活、轻便、无卡住现象为合格。发电机、同期调相机和高压电动机的检修、维护工作
7.1 检修发电机、同期调相机和高压电动机应填用变电站(发电厂)第一种工作票。
7.2 发电厂主要机组(锅炉、汽机、发电机、水轮机、水泵水轮机)停用检修,只需第一天办理开工手续,以后每天开工时,应由工作负责人检查现场,核对安全措施。检修期间工作票始终由工作负责人保存在工作地点。
在同一机组的几个电动机上依次工作时,可填用一张工作票。7.3 检修发电机、同期调相机必须做好下列安全措施: 7.3.1 断开发电机、励磁机(励磁变)、同期调相机的断路器(开关)和隔离开关(刀闸);
7.3.2 待发电机和同期调相机完全停止后,在其操作把手、按钮和机组的启动装置、励磁装置、同期并车装置、盘车装置的操作把手上悬挂“禁止合闸,有人工作!”的标示牌;
7.3.3 若本机尚可从其他电源获得励磁电流,则此项电源亦必须断开,并悬挂“禁止合闸,有人工作!”的标示牌; 7.3.4 断开断路器(开关)、隔离开关(刀闸)的操作能源。如调相机有启动用的电动机,还应断开此电动机的断路器(开关)和隔离开关(刀闸),并悬挂“禁止合闸,有人工作!”的标示牌;
7.3.5 将电压互感器从高、低压两侧断开;
7.3.6 在发电机和断路器(开关)间或发电机定子三相出口处(引出线)验明无电压后,装设接地线;
7.3.7 检修机组中性点与其他发电机的中性点连在一起的,则在工作前必须将检修发电机的中性点分开;
7.3.8 检修机组装有二氧化碳或蒸汽灭火装置的,则在风道内工作前,应采取防止灭火装置误动的必要措施;
7.3.9 检修机组装有可以堵塞机内空气流通的自动闸板风门的,应采取措施保证使风门不能关闭,以防窒息;
7.3.10 氢冷机组应关闭至氢气系统的相关阀门、加堵板等隔离措施。7.4 转动着的发电机、同期调相机,即使未加励磁,亦应认为有电压。
禁止在转动着的发电机、同期调相机的回路上工作,或用手触摸高压绕组。必须不停机进行紧急修理时,应先将励磁回路切断,投入自动灭磁装置,然后将定子引出线与中性点短路接地,在拆装短路接地线时,应戴缘绝手套,穿绝缘靴或站在绝缘垫上,并戴防护眼镜。
7.5 测量轴电压和在转动着的发电机上用电压表测量转子绝缘的工作,应使用专用电刷,电刷上应装有300mm以上的绝缘柄。
7.6 在转动着的电机上调整、清扫电刷及滑环时,应由有经验的电工担任,并遵守下列规定:
1)工作人员必须特别小心,不使衣服及擦拭材料被机器挂住,扣紧袖口,发辫应放在帽内;
2)工作时站在绝缘垫上(该绝缘垫为常设固定型绝缘垫),不得同时接触两极或一极与接地部分,也不能两人同时进行工作。
7.7 检修高压电动机和启动装置时,应做好下列安全措施: 7.7.1 断开电源断路器(开关)、隔离开关(刀闸),经验明确无电压后装设接地线或在隔离开关(刀闸)间装绝缘隔板,手车开关应从成套配电装置内拉出并关门上锁;
7.7.2 在断路器(开关)、隔离开关(刀闸)操作把手上悬挂“禁止合闸,有人工作!”的标示牌;
7.7.3 拆开后的电缆头须三相短路接地;
7.7.4 做好防止被其带动的机械(如水泵、空气压缩机、引风机等)引起电动机转动的措施,并在阀门(风门)上悬挂“禁止合闸,有人工作!”的标示牌.7.8 禁止在转动着的高压电动机及其附属装置回路上进行工作。必须在转动着的电动机转子电阻回路上进行工作时,应先提起碳刷或将电阻完全切除。工作时要戴绝缘手套或使用有绝缘把手的工具,穿绝缘靴或站在绝缘垫上。
7.9 电动机的引出线和电缆头以及外露的转动部分均应装设牢固的遮栏或护罩。7.10电动机及起动装置的外壳均应接地。禁止在转动中的电动机的接地线上进行工作。
7.11 工作尚未全部终结,而需送电试验电动机或起动装置时,应收回全部工作票并通知有关机械部分检修人员后,方可送电。在六氟化硫电气设备上的工作
8.1 装有SF6设备的配电装置室和SF6气体实验室,必须装设强力通风装置,风口应设置在室内底部,排风口不应朝向居民住宅或行人。
8.2 在室内,设备充装SF6气体时,周围环境相对湿度应≤80%,同时必须开启通风系统,并避免SF6气体泄漏到工作区。工作区空气中SF6气体含量不得超过1000ppm。
8.3 主控制室与SF6配电装置室间要采取气密性隔离措施。SF6配电装置室与其下方电缆层、电缆隧道相通的孔洞都应封堵。SF6配电装置室及下方电缆层隧道的门上,应设置“注意通风”的标志。
8.4 SF6配电装置室、电缆层(隧道)的排风机电源开关应设置在门外。
8.5 在SF6配电装置室低位区应安装能报警的氧量仪或SF6气体泄漏报警仪,在工作人员入口处也要装设显示器。这些仪器应定期试验,保证完好。
8.6 工作人员进入SF6配电装置室,入口处若无SF6气体含量显示器,必须先通风15min,并用检漏仪测量SF6气体含量合格。尽量避免一人进入SF6配电装置室进行巡视,不准一人进入从事检修工作。
8.7 工作人员不准在SF6设备防爆膜附近停留。若在巡视中发现异常情况,应立即报告,查明原因,采取有效措施进行处理。
8.8 进入SF6配电装置低位区或电缆沟进行工作应先检测含氧量(不低于18%)和SF6气体含量是否合格。
8.9 在打开的SF6电气设备上工作的人员,应经专门的安全技术知识培训,配置和使用必要的安全防护用具。
8.10设备解体检修前,应对SF6气体进行检验。根据有毒气体的含量,采取安全防护措施。检修人员需穿着防护服并根据需要配戴防毒面具。打开设备封盖后,现场所有人员应暂离现场30min。取出吸附剂和清除粉尘时,检修人员应戴防毒面具和防护手套。
8.11 设备内的SF6气体不得向大气排放,应采取净化装置回收,经处理合格后方准使用。回收时作业人员应站在上风侧。
设备抽真空后,用高纯度氮气冲洗3次[压力为9.8×104 pa(1个大气压)]。将清出的吸附剂、金属粉末等废物放入20%氢氧化钠水溶液中浸泡12小时后深埋。
8.12 从SF6气体钢瓶引出气体时,必须使用减压阀降压。当瓶内压力降至9.8×104 pa(1个大气压)时,即停止引出气体,并关紧气瓶阀门,戴上瓶帽。8.13 SF6配电装置发生大量泄漏等紧急情况时,人员应迅速撤出现场,开启所有排风机进行排风。未配戴隔离式防毒面具人员禁止入内。只有经过充分的自然排风或恢复排风后,人员才准进入。发生设备防爆膜破裂时,应停电处理,并用汽油或丙酮擦试干净。
8.14 进行气体采样和处理一般渗漏时,要戴防毒面具并进行通风。8.15 SF6开关进行操作时,禁止检修人员在其外壳上进行工作。
8.16 检修结束后,检修人员应洗澡,把用过的工器具、防护用具清洗干净。8.17 SF6气瓶应放置在阴凉干燥、通风良好、敞开的专门场所,直立保存,并应远离热源和油污的地方,防潮、防阳光曝晒,并不得有水份或油污粘在阀门上。搬运时,应轻装轻卸。在停电的低压配电装置和低压导线上的工作
9.1 低压配电盘、配电箱和电源干线上的工作,应填用变电站(发电厂)第二种工作票。
在低压电动机和在照明回路上的工作可不填用工作票,应做好相应记录,该工作至少由两人进行。
9.2 低压回路停电的安全措施
9.2.1 将检修设备的各方面电源断开取下可熔保险器,在开关或刀闸操作把手上挂 “禁止合闸,有人工作!”的标示牌; 9.2.2 工作前必须验电;
9.2.3 根据需要采取其他安全措施。
9.3 停电更换保险器后,恢复操作时,应戴手套和护目眼镜。10二次系统上的工作
10.1 下列情况应填用变电站(发电厂)第一种工作票:
10.1.1 在高压室遮栏内或与导电部分小于表2-1规定的安全距离进行继电保护、安全自动装置和仪表等及其二次回路的检查试验时,需将高压设备停电的; 10.1.2 在高压设备继电保护、安全自动装置和仪表、自动化监控系统等及其二次回路上工作需将高压设备停电或做安全措施者;
10.1.3 通信系统同继电保护、安全自动装置等复用通道(包括载波、微波、光纤通道等)的检修、联动试验需将高压设备停电或做安全措施者; 10.1.4 在经继电保护出口跳闸的发电机组热工保护、水车保护及其相关回路上工作需将高压设备停电或做安全措施者。
10.2 下列情况应填用变电站(发电厂)第二种工作票: 10.2.1 继电保护装置、安全自动装置、自动化监控系统在运行中改变装置原有定值时不影响一次设备正常运行的工作;
10.2.2 对于连接电流互感器或电压互感器二次绕组并装在屏柜上的继电保护、安全自动装置上的工作,可以不停用所保护的高压设备或不需做安全措施的; 10.2.3 在继电保护、安全自动装置、自动化监控系统等及其二次回路,以及在通信复用通道设备上检修及试验工作,可以不停用高压设备或不需做安全措施的; 10.2.4 在经继电保护出口的发电机组热工保护、水车保护及其相关回路上工作,可以不停用高压设备的或不需做安全措施的。
10.3 检修中遇有下列情况应填用二次工作安全措施票(见附录8)10.3.1 在运行设备的二次回路上进行拆、接线工作;
10.3.2 在对检修设备执行隔离措施时,需拆断、短接和恢复同运行设备有联系的二次回路工作;
10.4 二次工作安全措施票执行
10.4.1 二次工作安全措施票的工作内容及安全措施内容由工作负责人填写,由技术人员或班长审核并签发。
10.4.2 监护人由技术水平较高及有经验的人担任,执行人、恢复人由工作班成员担任,按二次工作安全措施票的顺序进行。上述工作至少由两人进行。
10.5 工作人员在现场工作过程中,凡遇到异常情况(如直流系统接地等)或断路器(开关)跳闸时,不论与本身工作是否有关,应立即停止工作,保持现状,待查明原因,确定与本工作无关时方可继续工作;若异常情况或断路器(开关)跳闸是本身工作所引起,应保留现场并立即通知运行人员,以便及时处理。10.6 工作前应做好准备,了解工作地点、工作范围、一次设备及二次设备运行情况、安全措施、试验方案、上次试验记录、图纸、整定值通知单是否齐备并符合实际,检查仪器、仪表等试验设备是否完好,核对微机保护及安全自动装置的软件版本号等是否符合实际。
10.7 现场工作开始前,应检查已做的安全措施是否符合要求,运行设备和检修设备之间的隔离措施是否正确完成,工作时还应仔细核对检修设备名称,严防走错位置。
10.8 在全部或部分带电的运行屏(柜)上进行工作时,应将检修设备与运行设备前后以明显的标志隔开。
10.9 在继电保护装置、安全自动装置及自动化监控系统屏(柜)上或附近进行打眼等振动较大的工作时,应采取防止运行中设备误动作的措施,必要时向调度申请,经值班调度员或运行值班负责人同意,将保护暂时停用。
10.10 在继电保护、安全自动装置及自动化监控系统屏间的通道上搬运或安放试验设备时,不能阻塞通道,要与运行设备保持一定距离,防止事故处理时通道不畅,防止误碰运行设备,造成相关运行设备继电保护误动作。清扫运行设备和二次回路时,要防止振动,防止误碰,要使用绝缘工具。10.11 继电保护、安全自动装置及自动化监控系统做传动试验或一次通电时,应通知运行人员和有关人员,并由工作负责人或由他指派专人到现场监视,方可进行。
10.12 所有电流互感器和电压互感器的二次绕组应有一点且仅有一点永久性的、可*的保护接地。
10.13 在带电的电流互感器二次回路上工作时,应采取下列安全措施: 10.13.1 严禁将电流互感器二次侧开路;
10.13.2 短路电流互感器二次绕组,必须使用短路片或短路线,严禁用导线缠绕; 10.13.3 在电流互感器与短路端子之间导线上进行任何工作,应有严格的安全措施,并填用“二次工作安全措施票”。必要时申请停用有关保护装置、安全自动装置或自动化监控系统。
10.13.4 工作中严禁将回路的永久接地点断开。
10.13.5 工作时,必须有专人监护,使用绝缘工具,并站在绝缘垫上。10.14 在带电的电压互感器二次回路上工作时,应采取下列安全措施:
10.14.1 严格防止短路或接地。应使用绝缘工具,戴手套。必要时,工作前申请停用有关保护装置、安全自动装置或自动化监控系统; 10.14.2 接临时负载,必须装有专用的刀闸和熔断器;
10.14.3 工作时必须有专人监护,严禁将回路的安全接地点断开。
10.15 二次回路通电或耐压试验前,应通知运行人员和有关人员,并派人到现场看守,检查二次回路及一次设备上确无人工作后,方可加压。
电压互感器的二次回路通电试验时,为防止由二次侧向一次侧反充电,除应将二次回路断开外,还应取下电压互感器高压熔断器或断开电压互感器一次刀闸。10.16 检验继电保护、安全自动装置、自动化监控系统和仪表的工作人员,不准对运行中的设备、信号系统、保护压板进行操作,但在取得运行人员许可并在检修工作盘两侧开关把手上采取防误操作措施后,可拉合检修断路器(开关)。10.17 试验用闸刀必须有熔丝并带罩,被检修设备及试验仪器禁止从运行设备上直接取试验电源,熔丝配合要适当,要防止越级熔断总电源熔丝。试验接线要经第二人复查后,方可通电。
10.18 继电保护装置、安全自动装置和自动化监控系统的二次回路变动时,应按经审批后的图纸进行,无用的接线应隔离清楚,防止误拆或产生寄生回路。
10.19 试验工作结束后,按“二次工作安全措施票”逐项恢复同运行设备有关的接线,拆除临时接线,检查装置内无异物,屏面信号及各种装置状态正常,各相关压板及切换开关位置恢复至工作许可时的状态。电气试验 11.1 高压试验
11.1.1 高压试验应填用变电站(发电厂)第一种工作票。
在一个电气连接部分同时有检修和试验时,可填用一张工作票,但在试验前应得到检修工作负责人的许可。在同一电气连接部分,高压试验工作票发出时,应先将已发出的检修工作票收回,禁止再发出第二张工作票。如果试验过程中,需要检修配合,应将检修人员填写在高压试验工作票中。
如加压部分与检修部分之间的断开点,按试验电压有足够的安全距离,并在另一侧有接地短路线时,可在断开点的一侧进行试验,另一侧可继续工作。但此时在断开点应挂有“止步,高压危险!”的标示牌,并设专人监护。11.1.2 高压试验工作不得少于两人。试验负责人应由有经验的人员担任,开始试验前,试验负责人应向全体试验人员详细布置试验中的安全注意事项,交待邻近间隔的带电部位,以及其它安全注意事项。
11.1.3 因试验需要断开设备接头时,拆前应做好标记,接后应进行检查。
11.1.4 试验装置的金属外壳应可*接地;高压引线应尽量缩短,并采用专用的高压试验线,必要时用绝缘物支持牢固。
试验装置的电源开关,应使用明显断开的双极刀闸。为了防止误合刀闸,可在刀刃上加绝缘罩。
试验装置的低压回路中应有两个串联电源开关,并加装过载自动掉闸装置。11.1.5 试验现场应装设遮栏或围栏,遮栏或围栏与试验设备高压部分应有足够的安全距离,向外悬挂“止步,高压危险!”的标示牌,并派人看守。被试设备两端不在同一地点时,另一端还应派人看守。
11.1.6 加压前应认真检查试验结线,使用规范的短路线,表计倍率、量程、调压器零位及仪表的开始状态均正确无误,经确认后,通知所有人员离开被试设备,并取得试验负责人许可,方可加压。加压过程中应有人监护并呼唱。
高压试验工作人员在全部加压过程中,应精力集中,随时警戒异常现象发生,操作人应站在绝缘垫上。
11.1.7 变更结线或试验结束时,应首先断开试验电源、放电,并将升压设备的高压部分放电、短路接地。
11.1.8 未装接地线的大电容被试设备,应先行放电再做试验。高压直流试验时,每告一段落或试验结束时,应将设备对地放电数次并短路接地。11.1.9 试验结束时,试验人员应拆除自装的接地短路线,并对被试设备进行检查,恢复试验前的状态,经试验负责人复查后,进行现场清理。
11.1.10 变电站、发电厂升压站发现有系统接地故障时,禁止进行接地网接地电阻的测量。
11.1.11 特殊的重要电气试验,应有详细的安全措施,并经单位主管生产的领导(总工程师)批准。
11.2 使用携带型仪器的测量工作
11.2.1 使用携带型仪器在高压回路上进行工作,至少由两人进行。需要高压设备停电或做安全措施的,应填用变电站(发电厂)第一种工作票。
11.2.2 除使用特殊仪器外,所有使用携带型仪器的测量工作,均应在电流互感器和电压互感器的二次侧进行。11.2.3 电流表、电流互感器及其他测量仪表的接线和拆卸,需要断开高压回路者,应将此回路所连接的设备和仪器全部停电后,始能进行。11.2.4 电压表、携带型电压互感器和其他高压测量仪器的接线和拆卸无需断开高压回路者,可以带电工作。但应使用耐高压的绝缘导线,导线长度应尽可能缩短,不准有接头,并应连接牢固,以防接地和短路。必要时用绝缘物加以固定。使用电压互感器进行工作时,先应将低压侧所有接线接好,然后用绝缘工具将电压互感器接到高压侧。工作时应戴手套和护目眼镜,站在绝缘垫上,并应有专人监护。
11.2.5 连接电流回路的导线截面,应适合所测电流数值。连接电压回路的导线截面不得小于1.5 mm2。
11.2.6 非金属外壳的仪器,应与地绝缘,金属外壳的仪器和变压器外壳应接地。11.2.7 测量用装置必要时应设遮栏或围栏,并悬挂“止步,高压危险!”的标示牌。仪器的布置应使工作人员距带电部位不小于表2-1规定的安全距离。11.3 使用钳形电流表的测量工作
11.3.1 运行人员在高压回路上使用钳形电流表的测量工作,应由两人进行。非运行人员测量时,应填用变电站(发电厂)第二种工作票。
11.3.2 在高压回路上测量时,严禁用导线从钳形电流表另接表计测量。
11.3.3 测量时若需拆除遮栏,应在拆除遮栏后立即进行。工作结束,应立即将遮栏恢复原状。
11.3.4 使用钳形电流表时,应注意钳形电流表的电压等级。测量时戴绝缘手套,站在绝缘垫上,不得触及其他设备,以防短路或接地。观测表计时,要特别注意保持头部与带电部分的安全距离。
11.3.5 测量低压熔断器(保险)和水平排列低压母线电流时,测量前应将各相熔断器(保险)和母线用绝缘材料加以包护隔离,以免引起相间短路,同时应注意不得触及其他带电部分。
11.3.6 在测量高压电缆各相电流时,电缆头线间距离应在300mm以上,且绝缘良好,测量方便者,方可进行。当有一相接地时,严禁测量。
11.3.7 钳形电流表应保存在干燥的室内,使用前要擦拭干净。11.4 使用摇表测量绝缘的工作
11.4.1 使用摇表测量高压设备绝缘,应由两人进行。
11.4.2 测量用的导线,应使用相应的绝缘导线,其端部应有绝缘套。
11.4.3 测量绝缘时,必须将被测设备从各方面断开,验明无电压,确实证明设备无人工作后,方可进行。在测量中禁止他人接近被测设备。在测量绝缘前后,必须将被测设备对地放电。
测量线路绝缘时,应取得许可并通知对侧后方可进行。11.4.4 在有感应电压的线路上测量绝缘时,必须将相关线路同时停电,方可进行。雷电时,严禁测量线路绝缘。
11.4.5 在带电设备附近测量绝缘电阻时,测量人员和摇表安放位置,必须选择适当,保持安全距离,以免摇表引线或引线支持物触碰带电部分。移动引线时,必须注意监护,防止工作人员触电。12 电力电缆工作
12.1 电力电缆工作的基本要求
12.1.1工作前应详细核对电缆名称、标志牌与工作票所写的相符,安全措施正确可*后,方可开始工作。
12.1.2 填用电力电缆第一种工作票的工作应经调度的许可,填用电力电缆第二种工作票的工作可不经调度的许可。若进入变配电站、发电厂工作,都应经当值运行人员许可。
12.1.3 电力电缆设备的标志牌要与电网系统图、电缆走向图和电缆资料的名称一致。
12.1.4 变配电站的钥匙与电力电缆附属设施的钥匙应专人严格保管,使用时要登记。
12.2 电力电缆作业时的安全措施 12.2.1 电缆施工的安全措施
12.2.1.1 电缆直埋敷设施工前应先查清图纸,再开挖足够数量的样洞和样沟,摸清地下管线分布情况,以确定电缆敷设位置及确保不损坏运行电缆和其它地下管线。
12.2.1.2 为防止损伤运行电缆或其它地下管线设施,在城市道路红线范围内不应使用大型机械来开挖沟槽,硬路面面层破碎可使用小型机械设备,但应加强监护,不得深入土层。若要使用大型机械设备时,应履行相应的报批手续。
12.2.1.3 掘路施工应具备相应的交通组织方案,做好防止交通事故的安全措施。施工区域应用标准路栏等严格分隔,并有明显标记,夜间施工人员应佩带反光标志,施工地点应加挂警示灯,以防行人或车辆等误入。
12.2.1.4 沟槽开挖深度达到1.5m及以上时,应采取措施防止土层塌方。
12.2.1.5 沟槽开挖时,应将路面铺设材料和泥土分别堆置,堆置处和沟槽应保持通道供施工人员正常行走。在堆置物堆起的斜坡上不得放置工具材料等器物,以免滑入沟槽损伤施工人员或电缆。
12.2.1.6挖到电缆保护板后,应由有经验的人员在场指导,方可继续进行,以免误伤电缆。
12.2.1.7 挖掘出的电缆或接头盒,如下面需要挖空时,应采取悬吊保护措施。电缆悬吊应每1~1.5m吊一道;接头盒悬吊应平放,不得使接头盒受到拉力;若电缆接头无保护盒,则应在该接头下垫上加宽加长木板,方可悬吊。电缆悬吊时,不得用铁丝或钢丝等,以免损伤电缆护层或绝缘。
12.2.1.8 移动电缆接头一般应停电进行。如必须带电移动,应先调查该电缆的历史记录,由有经验的施工人员,在专人统一指挥下,平正移动,以防止损伤绝缘。12.2.1.9 锯电缆以前,应与电缆走向图图纸核对相符,并使用专用仪器(如感应法)确切证实电缆无电后,用接地的带绝缘柄的铁钎钉入电缆芯后,方可工作。扶绝缘柄的人应戴绝缘手套并站在绝缘垫上。
12.2.1.10 开启电缆井井盖、电缆沟盖板及电缆隧道入孔盖时应使用专用工具,同时注意所立位置,以免滑脱后伤人。开启后应设置标准路栏围起,并有人看守。工作人员撤离电缆井或隧道后,应立即将井盖盖好,以免行人碰盖后摔跌或不慎跌入井内。
12.2.1.11 电缆隧道应有充足的照明,并有防火、防水、通风的措施。电缆井内工作时,禁止只打开一只井盖(单眼井除外)。进入电缆井、电缆隧道前,应先用吹风机排除浊气,再用气体检测仪检查井内或隧道内的易燃易爆及有毒气体的含量是否超标,并作好记录。电缆沟的盖板开启后,应自然通风一段时间后方可下井沟工作。电缆井、隧道内工作时,通风设备应保持常开,以保证空气流通。12.2.1.12 充油电缆施工应做好电缆油的收集工作,对散落在地面上的电缆油要立即覆上黄沙或砂土,及时清除,以防行人滑跌和车辆滑倒。
12.2.1.13 在10kV跌落熔丝与10kV电缆头之间,宜加装过渡连接装置,使工作时能与熔丝上桩头有电部分保持安全距离。在10kV跌落熔丝上桩头有电的情况下,未采取安全措施前,不得在熔丝下桩头新装、调换电缆尾线或吊装、搭接电缆终端头。如必须进行上述工作,则应采用专用绝缘罩隔离,在下桩头加装接地线。工作人员站在低位,伸手不得超过熔丝下桩头,并设专人监护。上述加绝缘罩的工作应使用绝缘工具。雨天禁止进行以上工作。
12.2.1.14 使用携带型火炉或喷灯时,火焰与带电部分的距离:电压在10kV及以下者,不得小于1.5m;电压在10kV以上者,不得小于3m。不得在带电导线、带电设备、变压器、油开关附近以及在电缆夹层、隧道、沟洞内对火炉或喷灯加油及点火。12.2.1.15 制作环氧树脂电缆头和调配环氧树脂工作过程中,应采取有效的防毒和防火措施。
12.2.1.16 电缆施工完成后应将穿越过的孔洞进行封堵,以达到防水或防火的要求。
12.2.1.17 非开挖施工的安全措施
1)采用非开挖技术施工前,应首先探明地下各种管线及设施的相对位置; 2)非开挖的通道,必须离开地下各种管线及设施足够的安全距离;
3)通道形成的同时,应及时对施工的区域进行灌浆等措施,防止路基的沉降。12.2.2 电力电缆线路试验安全措施
12.2.2.1 电力电缆试验要拆除接地线时,应征得工作许可人的许可(根据调度员指令装设的接地线,必须征得调度员的许可),方可进行。工作完毕后立即恢复。12.2.2.2 电缆耐压试验前,加压端应做好安全措施,防止人员误入试验场所。另一端应挂上警告牌。如另一端是上杆的或是锯断电缆处,应派人看守。
12.2.2.3 电缆的试验过程中,更换试验引线时,应先对设备充分放电,作业人员应戴好绝缘手套。
12.2.2.4 电缆耐压试验分相进行时,另两相电缆应接地。
12.2.2.5 电缆试验结束,应对被试电缆进行充分放电,并在被试电缆上加装临时接地线,待电缆尾线接通后才可拆除。
12.2.2.6 电缆故障声测定点时,禁止直接用手触摸电缆外皮或冒烟小洞,以免触电。一般安全措施
13.1 任何人进入生产现场(办公室、控制室、值班室和检修班组室除外),应戴安全帽。
13.2工作场所的照明,应该保证足够的亮度。在操作盘、重要表计、主要楼梯、通道、调度室、机房、控制室等地点,还必须设有事故照明。
13.3 变、配电站及发电厂遇有电气设备着火时,应立即将有关设备的电源切断,然后进行救火。消防器材的配备、使用、维护,消防通道的配置等应遵守DL-5027-93《电力设备典型消防规程》的规定。
13.4 电气工具和用具应由专人保管,定期进行检查。使用时,应按有关规定接入漏电保护装置、接地线。使用前必须检查电线是否完好,有无接地线,不合格的不准使用。
13.5 凡在离地面(坠落高度基准面)2m及以上的地点进行的工作,都应视作高处作业。
13.6 高处作业必须使用安全带(绳),安全带(绳)使用前应进行检查,并定期进行试验。安全带(绳)必须挂在牢固的构件上或专为挂安全带用的钢架或钢丝绳上,并不得低挂高用,禁止系挂在移动或不牢固的物件上[如避雷器、断路器(开关)、隔离开关(刀闸)、电流互感器、电压互感器等支持件上]。在没有脚手架或者在没有栏杆的脚手架上工作,高度超过1.5m时,必须使用安全带或采取其他可*的安全措施。
13.7 高处作业应使用工具袋,较大的工具应固定在牢固的构件上,不准随便乱放,上下传递物件应用绳索栓牢传递,严禁上下抛掷。13.8 在未做好安全措施的情况下,不准登在不坚固的结构上(如彩钢板屋顶)进行工作。
13.9 梯子应坚固完整,梯子的支柱应能承受作业人员及所携带的工具、材料攀登时的总重量,硬质梯子的横木应嵌在支柱上,梯阶的距离不应大于40cm,并在距梯顶1m处设限高标志。梯子不宜绑接使用。
13.10 在户外变电站和高压室内搬动梯子、管子等长物,应两人放倒搬运,并与带电部分保持足够的安全距离。
在变、配电站(开关站)的带电区域内或临近带电线路处,禁止使用金属梯子。13.11 在带电设备周围严禁使用钢卷尺、皮卷尺和线尺(夹有金属丝者)进行测量工作。
第五篇:工作票_电业安全工作规程(发电厂和变电所电气部分)
附 录 A倒闸操作票格式
附 录 B
第一种工作票格式
(补充件)
发电厂(变电所)第一种工作票第____号
1.工作负责人(监护人):_________________班组:______________________
2.工作班人员:______________________共__________________________人
3.工作内容和工作地点:__________________________________________________________________________________________________________________
4.计划工作时间:自年月日时分
至年月日时分
5.安全措施:
下列由工作票签发人填写下列由工作许可人(值班员)填写
(发电厂值长签名:)
6.许可开始工作时间:____________年______月______日_______时______分工作许可人签名:___________工作负责人签名:_____________________
7.工作负责人变动:
原工作负责人____________离去,变更______________为工作负责人。变动时间:_____________年_______月______日_______时________分,工作票签发人签名:___________________
8.工作票延期,有效期延长到:__________年____月____日______时____分工作负责人签名:__________值长或值班负责人签名:________________
9.工作终结:
工作班人员已全部撤离,现场已清理完毕。
全部工作于____________年______月_____日______时_______分结束。工作负责人签名:工作许可人签名:
接地线共_____________组已拆除。
值班负责人签名:____________
10.备注:_____________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________
附 录 C
第二种工作票格式
(补充件)
发电厂(变电所)第二种工作票编号:
1.工作负责人(监护人):_________________________班组__________________工作班人员:_________________________
2.工作任务:__________________________________________________________________________________________________________________________________
3.计划工作时间:自__________年_______月______日______时______分至__________年_______月______日______时______分
4.工作条件(停电或不停电):
__________________________________________________________________________________________________________________________________________________________________________________________________________________
5.注意事项(安全措施):___________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________
工作票签发人签名:__________________
6.许可开始工作时间:___________年________月_____日______时________分工作许可人(值班员)签名:________________工作负责人签名:_______________
7.工作结束时间:_______________年________月_____日_______时________分工作负责人签名:_____________工作许可人(值班员)签名:_______________
8.备注:___________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________